GB/T 3048.4-2025Test methods for electrical properties of electric cables and wires — Part 4: Test of DC resistance of conductors (English PDF)
电线电缆电性能试验方法 第4部分:导体直流电阻试验
Open the GB/T 3048.4-2025 preview as PDF
This is a limited preview
Buy now to download the full PDF (15 pages)
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
August 29, 2025
Implementation date
March 1, 2026
Scope
GB/T 3048.4-2025 is the English-translated version of 电线电缆电性能试验方法 第4部分:导体直流电阻试验.
GB/T 3048.4-2025 is the Chinese national standard covering measuring a conductor's DC resistance — the bridge and the four-terminal connection, the specimen length and its temperature which must be known because copper changes about four parts in a thousand per degree, the correction to 20 degrees and to unit length, and the uncertainty. Part 4 of the series. It replaces GB/T 3048.4-2007, under the China Electrical Equipment Industry Association. In force from 1 March 2026. Issued on 29 August 2025, it has been in force since 1 March 2026, replacing GB/T 3048.4-2007.
Document preview — GB/T 3048.4-2025
National Standard of the People's Republic of China
- ICS
- 29.060.20
- Classification
- K 13
- Replacing
- GB/T 3048.4-2007
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- Introduction6
- 1 Scope8
- 2 Normative references8
- 3 Terms and definitions8
- 4 Test equipment9
- 5 Specimen preparation10
- 6 Test conditions12
- 7 Test procedure13
- 8 Test results and calculations14
- 9 Test records16
1 Scope
This document describes the test methods for the DC resistance of conductors of electric wires and cables, including test equipment, specimen preparation, test conditions, test procedure, test results, calculations, and test records.
This document applies to measuring the DC resistance of conductors of wires and cables, the measurement ranges are as follows.
- double-arm bridge. 1 x 10-7 ohm ~ 99.9 ohm;
- single-arm bridge. 1 ohm and above.
This document does not apply to measuring the DC resistance of installed wires and cables.
2 Normative references
GB/T 2900.10
GB/T 3048.1
1 General
3 Terms and definitions
For the purpose of this document, the terms and definitions defined in GB/T 2900.10 and GB/T 3048.1 and the following apply.
3.1 cables of spooled cables & cables of cables coils
Samples of wires and cables of manufactured length arranged on cable drums or rolled into coils.
4 Test equipment
4.1 The schematic diagram of the single-arm bridge is shown in Figure 1, and the schematic diagram of the double-arm bridge is shown in Figure 2.
4.2 Resistance measurements should be made using a portable bridge or a laboratory-
specific fixed bridge, or a digital DC resistance tester. Laboratory-specific fixed bridges and accessories shall be wired and installed according to the instrument’s technical manual.
4.3 When the resistance being measured is less than 1 ohm, a four-terminal measuring fixture should be used for wiring. The outer pair of electrodes of the four-terminal fixture are current electrodes, and the inner pair are potential electrodes. Potential electrodes shall consist of metal electrodes with sharp edges or sharp needle electrodes, and a pair of potential electrodes shall be parallel to each other and perpendicular to the specimen. The distance between each potential contact and the corresponding current contact shall be no less than 1.5 times the circumference of the specimen cross section.
5 Specimen preparation
5.1 General specimen preparation method
5.1.1 Specimen cutting and preparation
In addition to the provisions of this document, other requirements for specimen preparation shall comply with the provisions of GB/T 3048.1.
A specimen of the length required for the test is cut from the tested wire or cable, the effective length between the potential electrodes shall not be less than 1 m. If the product standard specifies a sample length does not meet the effective length between the potential electrodes, the distance between the potential electrodes may be appropriately shortened, provided that the measurement error meets the requirements.
The result is converted to the conductor resistance value at 1 m. Alternatively, cables of spooled cable or cables of cables coil can be used as the specimen.
When removing insulation, protective sheaths, and other coverings (if any) from the conductor, damage to the conductor shall be avoided. For multi-core stranded cable specimens, the conductor covering shall be retained as much as possible along the effective length between the potential electrodes. For stranded conductor specimens, only the covering at the ends where they connect to the measurement system should be removed, exposing the conductor. For stranded bare conductors, measures shall be taken to prevent the conductor from loosening during sampling.
5.1.2 Specimen straightening
If straightening or alignment of the specimen is necessary, there shall be no distortion or damage that would alter the cross-section of the specimen conductor, nor shall the specimen conductor be stretched.
5.1.3 Specimen preparation
Before connecting the specimen to the measurement system, the conductor surface at the connection point shall be cleaned to remove any debris, dirt, and grease. All insulation between individual wires of the conductor at the connection point (such as oxide layers, insulating varnish, or water-blocking materials) shall be removed. If reagents are used, they shall be thoroughly cleaned with a volatile solvent such as water or alcohol to remove any residual reagents.
5.2 Preparation method for specimens of stranded aluminum conductors
(including aluminum alloy conductors)
5.2.1 General
Except as specified in this subclause, other preparation methods shall be carried out in accordance with 5.1.
5.2.2 Specimen length
The effective length of the specimen between the potential electrodes should be. 3 m for conductors with a nominal cross-sectional area of 185 mm2 or less, and 5 m for conductors with a nominal cross-sectional area greater than 185 mm2. In case of dispute, 5 m for conductors with a nominal cross-sectional area of 185 mm2 or less, and 10 m for conductors with a nominal cross-sectional area greater than 185 mm2.
5.3 Preparation method for specimens of split conductors
5.3.1 General
Except as specified in this subclause, other preparation methods shall be carried out in accordance with 5.1.
5.3.2 Specimen preparation
The cross-section of the split conductor shall be flat. Remove the insulating paper and water-blocking material (if any) between the current electrode and potential electrode strands. For bare conductors, use appropriate means (such as strong clamps) to secure the conductors. For finished cables, remove all coverings except the insulated cores, and covering materials other than the conductor on both sides of the potential electrode shall also be removed, exposing the conductors. In case of dispute, the insulation layer between the current electrode and potential electrode should be retained.
6 Test conditions
6.1 Test temperature
6.1.1 During type tests, the specimen shall be placed in a test environment with a temperature of (20 ± 5) °C and an air humidity of no more than 85 % for a minimum of
12 H, or as specified in the applicable product standard. During specimen placement
and testing, the ambient temperature shall not fluctuate by more than ±1 °C. Ambient temperature shall be measured with a thermometer with a graduation of 0.1 °C, to the nearest 0.1 °C. The thermometer shall not be less than 1 m from the ground, not be less than 10 cm from the wall, not more than 1 meter from the specimen, and the two shall be approximately at the same height and shall be protected from the influence of thermal radiation and air convection.
6.1.2 During routine tests, the specimen shall be placed in a test environment with a temperature of (20 ± 15) °C for a sufficient period of time to allow temperature equilibrium to occur. In case of dispute, the placement time should not be less than 24 h. Ambient temperature shall be measured with a thermometer with a graduation of 1 °C, accurate to the nearest 1 °C. The thermometer shall not be less than 1 m from the ground, not more than 1 meter from the specimen, and be protected from the influence of thermal radiation and air convection.
6.2 Measurement error
......
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
GB/T 2900.10
Cited by
- GB/T 28427-2026Cables for electrified railways - 27.5 kV single-phase AC power cables and cable accessories
- GB/T 28429-2025Cables for electrified railways - DC traction power cables and accessories up to 1500 V
- GB/T 29631-2025Flexible torsion-resistant cables of rated voltages up to and including 1.8/3 kV for wind power generation
- GB/T 31840.1-2025Aluminium alloy power cables with extruded insulation for rated voltages from 1 kV up to 35 kV — Part 1: Cables for rated voltages of 1 kV and 3 kV
- GB/T 31840.2-2025Aluminium alloy power cables with extruded insulation for rated voltages from 1 kV up to 35 kV — Part 2: Cables for rated voltages from 6 kV up to 30 kV
- GB/T 31840.3-2025Aluminium alloy power cables with extruded insulation for rated voltages from 1 kV up to 35 kV - Part 3: Cables for rated voltage 35 kV
Editions of GB/T 3048.4
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 3048.4-2025 | Test methods for electrical properties of electric cables and wires - Part 4: Test of DC resistance of conductors | current edition | Current |
| GB/T 3048.4-2007 | Test methods for electrical properties of electric cables and wires -- Part 4: Test of DC resistance of conductors | previous edition | In force |
| GB/T 3048.4-1994 | Test methods for determining electrical properties of electric cables and wires. Measurement of D. C. resistance of conductors | previous edition | Obsolete |
| GB 3048.4-1983 | Electric wires and cables--Test methods for measurement of D. C. resistance of conductors | previous edition | Obsolete |
This page sells the current edition, GB/T 3048.4-2025. Earlier editions are listed for reference only.
How to Buy GB/T 3048.4-2025
- 1Add to cart. Click the "Buy GB/T 3048.4-2025" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 3048.1-2007 — Test methods for electrical properties of electric cables and wires - Part 1: General
GB/T 3048.10-2007 — Test methods for electrical properties of electric cables and wires - Part 10: Spark test of extruded protective sheaths
GB/T 3048.11-2025 — Test methods for electrical properties of electric cables and wires — Part 11: Test for dielectric dissipation factor
Secure payment via Stripe
Payments accepted
GB/T 3048.4-2025
$200.00