Scope
GB/T 3048.5-2007 is the English-translated version of 电线电缆电性能试验方法 第5部分:绝缘电阻试验.
GB/T 3048.5-2007 is the Chinese standard "Test methods for electrical properties of electric cables and wires - Part 5: Test of insulation resistance".
Its scope clause reads: This Part of GB/T 3048 specifies the terms and definitions, test equipment, sample preparation, test procedures, test results and calculation, cautions, and test record of DC comparison method and voltage-current method for the measurement of insulation resistance.
This Part is applicable to the measurement of the insulation resistance of electric wires and cables, including DC comparison method and voltage-current method: the measurement range of DC comparison method is (10 5 ~ 2×10 35 )ohm; the measurement range of voltage-current method is (10 4 ~ 10 16 )ohm; in general, measurement voltage is (100 ~500)V. For voltage-current method, if the measured voltage and current are directly expressed in resistance on the same instrument, then it can also be called "megger method".
This Part shall be used together with GB/T 3048.1. Its clauses include terms and definitions; sample preparation; test procedures; test result and calculation; test data sheet.
Found what you need?
Document preview — GB/T 3048.5-2007
National Standard of the People's Republic of China
- ICS
- 29.060
- Classification
- K 13
- Replacing
- GB/T 3048.6-1994
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- 1 Scope7
- 2 Normative References7
- 3 Terms and Definitions7
- 4 Test Equipment8
- 5 Sample Preparation11
- 6 Test Procedures11
- 7 Test Result and Calculation13
- 8 Precautions14
- 9 Test Data Sheet15
1 Scope
This Part of GB/T 3048 specifies the terms and definitions, test equipment, sample preparation, test procedures, test results and calculation, cautions, and test record of DC comparison method and voltage-current method for the measurement of insulation resistance.
This Part is applicable to the measurement of the insulation resistance of electric wires and cables, including DC comparison method and voltage-current method:
the measurement range of DC comparison method is (10
5
~ 2×10
35
)ohm; the measurement range of voltage-current method is (10
4
~ 10
16
)ohm; in general, measurement voltage is (100 ~500)V.
For voltage-current method, if the measured voltage and current are directly expressed in resistance on the same instrument, then it can also be called
"megger method".
This Part shall be used together with GB/T 3048.1.
2 Normative References
The provisions in following documents become the provisions of this Standard through reference in this Standard. For dated references, the subsequent amendments (excluding corrections) or revisions do not apply to this Standard, however, parties who reach an agreement based on this Standard are encouraged to study if the latest versions of these documents are applicable. For undated references, the latest edition of the referenced document applies.
GB/T 2900.5-2002 Electrotechnical terminology - Insulating solids, liquids and gases [eqv IEC 60050 (212): 1990]
GB/T 3048.1 Test methods for electrical properties of electric cables and wires - Part 1: General
3 Terms and Definitions
The following terms and definitions that are established by GB/T 2900.5-2002 are […]
5 Sample Preparation
5.1
The effective length of the sample shall not be less than 10m, unless
otherwise specified in the product standard. The coverings on the insulation at the both ends of the sample shall be peeled carefully and avoid damage to the insulating surface.
5.2
The sample shall be kept in the test environment for enough time to make the sample temperature and the test temperature in balance. Keep the temperature stable.
5.3
When the sample is tested in the water, the exposed length of the two ends of the sample shall not be less than 250mm; the exposed length of the insulating part shall not be less than 150mm.
When the sample is tested in the air, the exposed length of the insulating part at the sample ends shall not be less than 100mm.
The exposed insulating surface shall be kept dry and clean.
6 Test Procedures
6.1 Connection of the sample
6.1.1 Cable samples with metal sheath, shielding layer or armor
For single-core cables, the insulation resistance of the conductor to the metallic sheath or shielding layers or armor layers shall be measured; as for multi-core cables, each wire core shall be connected to the metallic sheath or shielding layer or armor layer for testing against the rest wire cores. If it is required to measure the insulation resistance between the shield and the wire cores of multi-core cables, it shall measure the shield after all of the wire cores are in parallel connection.
6.1.2 Non-metallic sheathed, non-shielded or unarmored cable samples
The single-core cable shall be submerged in the water; the insulation resistance of the conductor to the water shall be measured; as for multi-core cables, each wire core shall be tested against the rest wire cores.
The sample may also be wound around the metallic test bar. For single-core cables, the insulation resistance of the conductor to the test bar shall be measured; as for multi-core cables, each wire core shall be connected to the test bar for testing against the rest. The external diameter of the test bar shall meet […]
6.6 Test charging time
In order to keep the measured insulation resistance stable, the test charging time shall be adequate, not less than 1min and does not exceed 5min. Generally, 1min reading is recommended.
6.7 Measuring error of the test system
The measuring error of the test system shall meet the following requirements:
-- If the insulation resistance value of the tested sample is (1×10
10
)ohm or below, the measuring error shall not be greater than ±10%;
-- If the insulation resistance value of the tested sample is above (1×10
10
)ohm, the measuring error shall not be greater than 20%.
7 Test Result and Calculation
7.1
When DC comparison method is adopted in the test, the insulation resistance value shall be calculated according to the formula provided by the instrument instructions.
When voltage - current method or digital instrument is adopted in the test, the insulation resistance value shall be read according to the requirements of the instrument instructions.
7.2
The insulation resistance of per kilometer length shall be calculated according to Formula (1):
RL=RX L (1)
Where,
RL -- Insulation resistance of per kilometer length; unit: Mohm·km;
RX -- Insulation resistance of the sample; unit: Mohm;
L -- Actual measurement length of the sample; unit: km.
7.3
The insulation resistance of per kilometer length at 20°C shall be calculated according to Formula (2):
R20=KRL (2)
Where,
R20 -- Insulation resistance of per kilometer length at 20°C; unit: Mohm·km;
8.4
When the insulation resistance is measured by adopting a megger whose
output end is suspended over the ground, it is recommended that the measuring end (low voltage end) of the megger to be connected to the conductor of the tested insulated core, and the high voltage end to be connected to the other pole (water, it is permitted to be grounded) of the sample. When a general megger is adopted to measure the insulation resistance, the submerged sample must be of ground insulation; otherwise, it may cause damage to the megger because of the short circuit of the output high voltage side TO the ground; or it may enlarge the test error due to the effects from the heating power supply.
8.5
Attention shall be drawn to the connection methods for the internal and external shield of the whole set apparatus used by the DC comparison method, so as to avoid to enlarge the measuring error.
9 Test Data Sheet
The following contents shall be recorded in the test data sheet:
a) Test type;
b) Sample number, sample type or specification;
c) Sample preparation method;
d) Test methods and test voltage;
e) Test date and the temperature in the test;
f) Test methods shall be recorded if the insulation resistance is measured at high temperature;
g) Test result;
h) Validity period of the test instrument and its calibration.
__________ END __________ […]
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Cited by
- GB/T 29631-2025Flexible torsion-resistant cables of rated voltages up to and including 1.8/3 kV for wind power generation
- GB/T 43673-2024Non-metallic composite coiled tubing with embedded cable
- GB 43069-2023Safety requirements for mine cable
- NB/T 11128-2023Rubber sheathed flexible cable for frequency converter equipment of coal mine
- NB/T 11129-2023Control cable for coal mine
- MH/T 6049-2020Buried cable for airport navigation aid light loop
Similar standards
Editions of GB/T 3048.5
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 3048.5-2007 | Test methods for electrical properties of electric cables and wires - Part 5: Test of insulation resistance | current edition | Current |
| GB/T 3048.6-1994 | Test methods for electrical properties of electric cables and wires - Part 5: Test of insulation resistance | previous edition | Superseded |
This page sells the current edition, GB/T 3048.5-2007. Earlier editions are listed for reference only.
How to Download GB/T 3048.5-2007
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 3048.1-2007 — Test methods for electrical properties of electric cables and wires - Part 1: General
GB/T 3048.10-2007 — Test methods for electrical properties of electric cables and wires - Part 10: Spark test of extruded protective sheaths
GB/T 3048.11-2025 — Test methods for electrical properties of electric cables and wires — Part 11: Test for dielectric dissipation factor
Secure payment via Stripe
Payments accepted
GB/T 3048.5-2007
$75.00