GB/T 3836.2-2021 (Explosive atmospheres - Part 2: Equipment protection by flameproof enclosures 'd') is available as an English-translated PDF.

GB/T 3836.2-2021 — This Document contains specific requirements for the construction and testing of electrical equipment with the type of protection flameproof enclosure "d", intended for use in explosive gas atmospheres. This Document is applicable to electrical equipment protected by flameproof enclosure "d" intended to be used in explosive gas atmospheres.

Document preview — GB/T 3836.2-2021

National Standard of the People's Republic of China

Issued by: SAMR; SAC

Contents

  • Foreword...4
  • Introduction...12
  • 1 Scope...15
  • 2 Normative References...15
  • 3 Terms and Definitions...16
  • 4 Level of Protection (Equipment Protection Level, EPL)...19
  • 5 Flameproof Joints...21
  • 6 Sealed Joints...34
  • 7 Operating Rods...36
  • 8 Supplementary Requirements for Shafts and Bearings...37
  • 9 Light-Transmitting Parts...40

Foreword

This Document was drafted as per the rules specified in GB/T 1.1-2020 Directives for

Standardization - Part 1.Rules for the Structure and Drafting of Standardizing

Documents.

This Document is Part 2 of GB/T 3836 Explosive Atmospheres. GB/T 3836 has

published the following parts.

--- Part 1.Equipment - General Requirements;

--- Part 2.Equipment Protection by Flameproof Enclosure "d";

--- Part 3.Equipment Protection by Increased Safety "e";

--- Part 4.Equipment Protection by Intrinsic Safety "i";

--- Part 5.Equipment Protection by pressurized Enclosure "p";

--- Part 6.Equipment Protection by Liquid Immersion "o";

--- Part 7.Equipment Protection by Powder Filling "q";

--- Part 8.Equipment Protection by Type of Protection "n";

--- Part 9.Equipment Protection by Encapsulation "m";

--- Part 11.Material Characteristics for Gas and Vapour Classification - Test

Methods and Data;

--- Part 12.Material Characteristics for Combustible Dusts - Test Methods;

--- Part 13.Equipment Repair, Overhaul, Reclamation and Modification;

--- Part 14.Classification of Areas - Explosive Gas Atmosphere;

--- Part 15.Electrical Installations Design, Selection and Erection;

--- Part 16.Electrical Installations Inspection and Maintenance;

--- Part 17.Equipment Protection by Pressurized Room "p" and Artificially Ventilated

Room "v";

--- Part 18.Intrinsically Safe Electrical Systems;

--- Part 20.Equipment with Equipment Protection Level (EPL) Ga;

--- Part 21.Application of Quality Systems for Equipment Manufacture;

--- Part 22.Protection of Equipment and Transmission System Using Optical

Radiation;

--- Part 23.Group I, Category EPL Ma Equipment Intended to Remain Functional in

Atmospheres Endangered by Firedamp and/or Coal Dust;

--- Part 24.Equipment Protection by Special Protection "s";

--- Part 25.Requirements for Process Sealing between Flammable Process Fluids

and Electrical Systems;

--- Part 26.Electrostatic Hazards - Guidance;

--- Part 27.Electrostatic Hazards - Test;

--- Part 28.Non-Electrical Equipment for Explosive Atmospheres - Basic Method

and Requirements;

--- Part 29.Non-Electrical Equipment for Explosive Atmospheres - Constructional

Safety "c", Control of Ignition Source "b", Liquid Immersion "k";

--- Part 30.Equipment and Components in Explosive Atmospheres in Underground

Mines;

--- Part 31.Equipment Dust Ignition Protection by Enclosure "t";

--- Part 32.Intrinsically Safe Systems with Electronically Controlled Spark Duration

Limitation;

--- Part 33.Equipment in Adverse Service Conditions;

--- Part 34.Equipment Assemblies;

--- Part 35.Classification of Areas for Explosive Dust Atmospheres.

This Document replaced GB 3836.2-2010 Explosive Atmospheres - Part 2.Equipment

Protection by Flameproof Enclosures "d". Compared with GB 3836.2-2010, this

Document made the major technical changes besides the structural adjustments and

editorial modifications.

--- Delete the clause of equipment category and temperature group (see Clause 4

of 2010 Edition);

--- Add the Clause of protection level (see Clause 4 of this Edition);

--- Add special conditions of use that the flameproof joints are not expected to be

repaired (see 5.1 of this Edition);

Explosive Atmospheres - Part 2.Equipment

Protection by Flameproof Enclosures "d"

1 Scope

This Document contains specific requirements for the construction and testing of

electrical equipment with the type of protection flameproof enclosure "d", intended for

use in explosive gas atmospheres.

This Document is applicable to electrical equipment protected by flameproof enclosure

"d" intended to be used in explosive gas atmospheres.

2 Normative References

The provisions in following documents become the provisions of this Document

through reference in this Document. For the dated documents, only the versions with

the dates indicated are applicable to this Document; for the undated documents, only

the latest version (including all the amendments) is applicable to this Document.

GB/T 197 General Purpose Metric Screw Threads - Tolerances (GB/T 197-2018,

ISO 965-1.2013, MOD)

GB/T 1406.2 Types and Dimensions of Lamp Caps - Part 2.Pin Lamp Caps (GB/T

1406.2-2008, IEC 60061-1.2005, MOD)

GB/T 2516 General Purpose Metric Screw Threads - Limit Deviations (GB/T

2516-2003, ISO 965-3.1998, MOD)

GB/T 3836.1 Explosive Atmospheres - Part 1.Equipment - General Requirements

(GB/T 3836.1-2021, IEC 60079-0.2017, MOD)

GB/T 3836.3 Explosive Atmospheres - Part 3.Equipment Protection by Increased

Safety "e" (GB/T 3836.3-2021, IEC 60079-7.2015, MOD)

GB/T 3836.4 Explosive Atmospheres - Part 4.Equipment Protection By Intrinsic

Safety "i" (GB/T 3836.4-2021, IEC 60079-11.2011, MOD)

GB/T 3836.8 Explosive Atmospheres - Part 8.Equipment Protection by Type of

Protection "n" (GB/T 3836.8-2021, IEC 60079-15.2017, MOD)

GB/T 5163 Sintered Metal Materials, Excluding Hard Metals - Permeable Sintered

Metal Materials - Determination of Density, Oil Content, and Open Porosity (GB/T

5163-2006, ISO 2738.1999, IDT)

GB/T 5249 Permeable Sintered Metal Materials - Determination of Bubble Test

Pore Size (GB/T 5249-2013, ISO 4003.1977, IDT)

GB/T 5250 Permeable Sintered Metal Materials - Determination of Fluid

Permeability (GB/T 5250-2014, ISO 4022.1987, IDT)

GB/T 9364 (all parts) Miniature Fuses [IEC 60127 (all parts)]

GB/T 19148.2 Types and Dimensions of Lamp Holders - Part 2.Pin Lamp Holders

(GB/T 19148.2-2008, IEC 60061-2.2004, MOD)

ANSI/ASME B1.20.1 Pipe Threads, General Purpose (Inch)

3 Terms and Definitions

For the purposes of this Document, the terms and definitions given in GB/T 3836.1 and

the following apply.

NOTE. Additional definitions applicable to explosive atmospheres can be found in GB/T

2900.35.

3.1 Flameproof enclosure "d"

Enclosure in which the parts which can ignite an explosive gas atmosphere are placed

and which can withstand the pressure developed during an internal explosion of an

explosive mixture, and which prevents the transmission of the explosion to the

explosive gas atmosphere surrounding the enclosure.

4 Level of Protection (Equipment Protection Level, EPL)

4.1 General

Electrical equipment with flameproof enclosure "d" shall be one of the following.

- level of protection "da" (EPL "Ma" or "Ga");

- level of protection "db" (EPL "Mb" or "Gb"); or

- level of protection "dc" (EPL "Gc").

The requirements of this standard shall apply to all levels of protection unless

otherwise stated.

In addition, the empty flameproof enclosure as an Ex component shall meet the

requirements of Annex D; the battery used in the flameproof enclosure shall meet the

requirements of Annex E; the flameproof enclosure with an internal release source

shall meet the additional requirements of Annex G; The motor supply power to the

inverter and with flameproof enclosure "d" shall meet the requirements of Annex H;

electrical equipment of Group I shall meet the supplementary requirements of Annex I.

5 Flameproof Joints

5.1 General requirements

All flameproof joints, whether permanently closed or designed to be opened from time

to time, shall comply, in the absence of pressure, with the appropriate requirements of

Clause 5.

The design of joints shall be appropriate to the mechanical constraints applied to them.

The dimensions given in 5.2 to 5.5 specify the essential parameters of flamepaths. In

instances where any of the following apply (for example, in order to comply with the

test for non-transmission of an internal ignition).

- the minimum length of the flameproof joint as stated by the documentation is

greater than the relevant minimum; or

- the maximum gap of the flameproof joint as stated by the documentation is less

than the relevant maximum; or

6 Sealed Joints

6.1 Cemented joints

6.1.1 General

7 Operating Rods

Where an operating rod passes through the wall of a flameproof enclosure, the

following requirements shall be met.

- if the diameter of the operating rod exceeds the minimum width of the joint

specified in Tables 2 and 3, the width of the joint shall be at least equal to this

diameter but without, however, having to exceed 25 mm;

9 Light-Transmitting Parts

For light-transmitting parts of other than glass, the requirements in Clause 19 of this

standard apply.

NOTE. Mountings of light-transmitting parts, of any material that produces internal mechanical

stress in those parts, can result in failure of the light-transmitting part.

10 Breathing and Draining Devices which form Part of

a Flameproof Enclosure

10.1 General

Breathing and draining devices shall incorporate permeable elements which can

withstand the pressure created by an internal explosion in the enclosure to which they

are fitted, and which shall prevent the transmission of the explosion to the explosive

atmosphere surrounding the enclosure.

They shall also withstand the dynamic effects of explosions within the flameproof

enclosure without permanent distortion or damage which would impair their flame-

arresting properties. They are not intended to withstand continuous burning on their

surfaces.

......

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.

Referenced standards

Normative references

GB/T 197 · GB/T 197-2018 · ISO 965 · GB/T 1406.2 · IEC 60061 · GB/T 2516 · IEC 60079 · GB/T 5163 · ISO 2738.1999 · GB/T 5249 · GB/T 5249-2013 · ISO 4003.1977 · GB/T 5250 · GB/T 5250-2014 · ISO 4022.1987 · GB/T 9364 · IEC 60127 · GB/T 19148.2 · GB/T 19148.2-2008

Cited by

How to Buy GB/T 3836.2-2021

  1. 1Add to cart. Click the "Buy GB/T 3836.2-2021" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 3836.2-2021

$1,010.00

$860.00for partners