GB 18484-2020Standard for pollution control on hazardous waste incineration (English PDF)
Also coversGB18484-2020
Open the GB 18484-2020 preview as PDF
This is a limited preview
Buy now to download the full PDF
Issued by
MEE; SAMR
Level / Type
National · Mandatory
Issue date
December 8, 2020
Implementation date
July 1, 2021
Scope
GB 18484-2020 (Standard for pollution control on hazardous waste incineration) is available as an English-translated PDF.
GB 18484-2020 — This Standard specifies the requirements for ecological and environmental protection during the site selection, operation, monitoring, waste storage, mixing and incineration disposal of hazardous waste incineration facilities, as well as implementation and supervision. This Standard applies to pollution control and environmental management of existing hazardous waste incineration facilities (excluding special PCB waste and medical waste incineration facilities), as well as environmental impact assessment of new hazardous waste incineration facility construction projects, design and construction of hazardous waste incineration facilities, completion acceptance, pollution discharge permit management, and pollution control and environmental management during operation after completion. Special standard implemented by hazardous waste incineration facilities of the published special national pollution control standards or environmental protections standards. The pollutant emission limits of high-temperature heat treatment facilities such as hazardous waste melting, pyrolysis, and gasification, if there are no special national pollution control standards or environmental protection standards, it shall be implemented in accordance with this Standard. This Standard does not apply to the coordinated disposal of hazardous waste using boilers and industrial furnaces.
Document preview — GB 18484-2020
National Standard of the People's Republic of China
Issued by: MEE; SAMR
Contents
- Foreword4
- 1 Scope6
- 2 Normative References6
- 3 Terms and Definitions9
- 4 Requirements for Site Selection14
- 5 Technical Requirements for Pollution Control14
- 6 Requirements for Emission Control16
- 7 Operation Environment Management Requirements18
- 8 Environmental Monitoring Requirements19
- 9 Implementation and Supervision23
- Appendix A (Normative) Toxic Equivalency Factor (TEF) of PCDDs/PCDFs25
1 Scope
This Standard specifies the requirements for ecological and environmental protection during the site selection, operation, monitoring, waste storage, mixing and incineration disposal of hazardous waste incineration facilities, as well as implementation and supervision.
This Standard applies to pollution control and environmental management of existing hazardous waste incineration facilities (excluding special PCB waste and medical waste incineration facilities), as well as environmental impact assessment of new hazardous waste incineration facility construction projects, design and construction of hazardous waste incineration facilities, completion acceptance, pollution discharge permit management, and pollution control and environmental management during operation after completion.
Special standard implemented by hazardous waste incineration facilities of the published special national pollution control standards or environmental protections standards.
The pollutant emission limits of high-temperature heat treatment facilities such as hazardous waste melting, pyrolysis, and gasification, if there are no special national pollution control standards or environmental protection standards, it shall be implemented in accordance with this Standard.
This Standard does not apply to the coordinated disposal of hazardous waste using boilers and industrial furnaces.
2 Normative References
The following documents are essential to the application of this Document. For the dated documents, only the versions with the dates indicated are applicable to this Document; for the undated documents, only the latest version (including all the amendments) is applicable to this Document.
GB 8978 Integrated wastewater discharge standard
GB 12348 Standard of noise at boundary of industrial enterprises
GB 14554 Emission standards for odor pollutants
GB 16297 Integrated emission standard of air pollutants The process by which hazardous waste undergoes combustion and other reactions under high temperature conditions to achieve harmlessness and reduction.
3.3 Incineration facility
A device that disposes of hazardous waste by incineration to reduce its quantity, size and eliminate its hazardous characteristics, including a feeding device, incinerator, flue gas purification device and control system, etc.
3.4 Incineration capacity
The design capacity of an incineration facility to incinerate hazardous waste per unit time.
3.5 Incineration residues
Incineration residues, fly ash and wastewater treatment sludge discharged after the incineration of hazardous waste.
3.6 Loss of ignition
The percentage of the mass reduction of the incineration residue after burning to the original mass of the incineration residue. It is calculated according to Formula (1):
Where:
P - loss of ignition, in %;
A - the mass of the original incineration residue at room temperature after drying at (105 +/- 25)°C for 1 h, in g;
B - the mass of the incineration residue after being calcined at (600 +/- 25)°C for 3h and then cooled to room temperature, in g.
3.7 High temperature section of incinerator
At the outlet of the incinerator combustion chamber and upstream of the outlet, the flue gas temperature generated by combustion is in the range of >=1100°C.
3.8 Flue gas residence time
The duration that the flue gas generated by combustion is in the high temperature section (>=1100°C) can be calculated by the ratio of the effective volume of the high temperature section of incinerator to the flue gas flow rate.
3.13 Toxic equivalency factor (TEF)
The ratio of the affinity properties of dioxin congeners and 2,3,7,8-tetrachlorodibenzo-p-dioxin for aromatic receptors (Ah receptors). Please see Appendix A for the toxic equivalence factors of typical dioxin congeners.
3.14 Toxic equivalent quantity (TEQ)
The concentration of each dioxin congener is converted into an equivalent concentration equal to the toxicity of 2,3,7,8-tetrachlorodibenzo-p-dioxin. The toxic equivalent quantity is the product of the measured concentration by the toxic equivalent factor of the isomer. It is calculated according to Formula (4):
Where:
TEQ - toxic equivalent quantity;
TEF - toxic equivalency factor.
3.15 Standard conditions
The gas state at a temperature of 273.15 K and a pressure of 101.325 kPa. The concentration limits of atmospheric pollutant emissions specified in this Standard are based on dry gas under standard conditions.
3.16 Average value
The arithmetic mean of the test values of pollutant concentration in a certain number of samples collected within a certain period of time. The monitoring of dioxins shall complete the collection of no less than 3 samples within 6h to 12h; the monitoring of heavy metal pollutants shall complete the collection of no less than 3 samples within 0.5h to 8h.
3.17 1-hour average value The arithmetic mean of any pollutant concentration within 1 h; or the arithmetic mean of the test values of 3 to 4 samples collected at equal time intervals within 1 h.
3.18 24-hour average value The arithmetic mean of the 1-hour average values within 24 consecutive hours. The number of valid hourly average values shall be no less than 20.
3.19 Daily average value
The daily average mass concentration of pollutants is calculated using the 1-hour average value (concentration of dioxin toxic congener x TEF)
3.22 New incineration facility
New construction, reconstruction and expansion of hazardous waste incineration facilities with approved environmental impact assessment documents after the implementation date of this Standard.
4 Requirements for Site Selection
4.1 The site selection of hazardous waste incineration facilities shall comply with the laws and
regulations on ecological and environmental protection and relevant statutory planning requirements, and comprehensively consider the basic factors such as the service area of the facilities, transportation, geological environment, etc., to ensure that the facilities are in a relatively stable environment in the long term. Hazardous waste incineration facilities are encouraged to be located in concentrated areas of municipal facilities such as circular economy parks. The functional layout of each facility in this area can be adjusted according to the environmental impact assessment documents.
4.2 The site selection of incineration facilities shall not be located in the ecological protection
red line areas, permanent basic farmland concentration areas and other areas requiring special protection designated by the State Council and relevant competent departments of the State Council and the people's governments of provinces, autonomous regions and municipalities directly under the Central Government.
4.3 The site of the incineration facility shall be set at a certain protective distance from sensitive
targets. The protective distance shall be determined comprehensively based on the site conditions, incineration disposal technology and process, pollutant emission characteristics and their diffusion factors; and shall meet the requirements of the environmental impact assessment documents and approval opinions.
5 Technical Requirements for Pollution Control
5.1 Storage
5.1.1 Storage facilities shall meet the requirements specified in GB 18597.
5.1.2 Storage facilities shall be equipped with temporary storage facilities and partitions for
incineration residues.
5.2 Compatibility
5.2.1 Hazardous wastes entering the furnace shall meet the design requirements of the
incinerator. Hazardous wastes with explosive properties are prohibited from being incinerated.
5.2.2 Before entering the furnace, hazardous wastes shall be taken compatibility according to
the performance requirements of the incinerator so that their calorific value, main harmful component content, combustible chlorine content, metal content, combustible sulfur content, moisture and ash content meet the design requirements of the incineration disposal facilities;
and the physical and chemical properties of the waste entering the furnace shall be stable.
5.2.3 Pollution control measures in the pretreatment and compatibility workshops shall meet
the requirements specified in GB 18597. The generated waste gas shall be collected and introduced into the waste gas treatment device; and the generated waste water shall be collected and introduced into the waste water treatment device.
5.3 Incineration
5.3.1 General provisions
5.3.1.1 Incineration facilities shall adopt negative pressure design or other technical measures
to prevent the escape of harmful gases during operation.
5.3.1.2 Incineration facilities shall be equipped with feeding devices with automatic online and
shutdown functions, flue gas purification devices, and operation monitoring devices integrated with online automatic flue gas monitoring, online monitoring of operating conditions and other functions.
5.3.1.3 Before the environmental protection acceptance of the completed incineration facilities, technical performance tests shall be carried out. The test methods shall be implemented in accordance with HJ 561. Only after the performance test is qualified can it pass the acceptance.
5.3.2 Feeding device
5.3.2.1 The feeding device shall ensure smooth and uniform feeding, and adopt anti-blocking
and clearing design.
5.3.2.2 The liquid waste feeding device shall be set up separately, and shall have filtering
function and flow regulation function, and the corrosion-resistant material shall be selected.
5.3.2.3 The feeding port shall be designed to be airtight and anti-backfire.
5.3.3 Incinerator
5.3.3.1 The technical performance indicators of hazardous waste incinerators shall meet the
requirements of Table 1.
utilization and disposal shall comply with the relevant national and local hazardous waste regulations.
6.6 Wastewater discharge from incineration facilities shall meet the requirements of GB 8978.
6.7 Noise at factory boundaries shall meet the control requirements of GB 12348.
7 Operation Environment Management Requirements
7.1 General provisions
7.1.1 Hazardous waste incineration organizations shall collect, store and transport hazardous
wastes in accordance with the requirements of HJ 2025.
7.1.2 During the operation of the incineration facility, an operation record system shall be
established to truthfully record the operation management situation. The operation record shall at least include the source, type, quantity, storage and disposal information of hazardous wastes;
the physical and chemical characteristics analysis results and compatibility plan of the waste entering the furnace; the facility operation and process parameter information; environmental monitoring data; the quality and amount of activated carbon; the destination and quantity of incineration residues, etc.
7.1.3 The incineration organization shall establish all the archives of the incineration facility, including design, construction, acceptance, operation, monitoring and emergency response, etc.
The archives shall be sorted and filed in accordance with the relevant national laws and regulations on archive management.
7.1.4 The incineration organizations shall prepare an environmental emergency plan and
organize emergency drills regularly.
7.1.5 Incineration organizations shall establish a soil and groundwater pollution risk detection
and control system in accordance with relevant national and local requirements; and conduct regular risk detection. If risks are found, timely measures shall be taken to eliminate them and archives shall be established.
7.2 Operation requirements for incineration facility
7.2.1 When starting up a hazardous waste incineration facility, the temperature in the furnace
shall be raised to the temperature specified in Table 1 before adding hazardous waste. After the incineration facility is started and hazardous waste is added, the amount of input shall be gradually increased, and a stable operating condition shall be reached within 6 h.
7.2.2 When the incineration facility is shut down, the combustion-supporting device shall be
used to ensure that the temperature in the furnace meets the requirements specified in Table 1 until the remaining hazardous waste in the furnace is completely burned.
7.2.3 When a failure occurs during the operation of the incineration facility and cannot be
eliminated in time, the feeding of hazardous waste shall be stopped immediately and the furnace shall be shut down in accordance with the requirements of 7.2.2. The duration of pollutant emissions from a single incineration facility due to start-up, shutdown, failure and accident shall not exceed 60 h in total per natural year. The heating period of the furnace before the hazardous waste is added to the furnace is not included in the start-up time, and the shutdown and cooling period after the hazardous waste in the furnace is burned out is not included in the shutdown time.
7.2.4 During the time specified in 7.2.1, 7.2.2 and 7.2.3, the online automatic monitoring data
shall not be used as the basis for assessing whether the emission limit of this Standard is met, but the 1-hour average value of the flue gas particulate matter concentration shall be no greater than 150 mg/m3.
7.2.5 It shall be ensured that the 5-min average value of the temperature measured by the
thermocouple in the incinerator furnace under normal operating conditions is no less than 1100°C.
8 Environmental Monitoring Requirements
8.1 General provisions
8.1.1 Hazardous waste incineration organizations shall establish enterprise monitoring systems
and formulate monitoring plans in accordance with relevant laws, the Environmental Monitoring and Management Methods and HJ 819; conduct self-monitoring of pollutant emissions and their impact on the surrounding environmental quality; preserve original monitoring records; and publish monitoring results.
8.1.2 The installation of automatic monitoring equipment for pollutant emissions in incineration
facilities shall be carried out in accordance with relevant laws and the Measures for the Administration of Automatic Monitoring of Pollution Sources.
8.1.3 The pollutant monitoring method standards issued by the state after the implementation
of this Standard shall also be applicable to the determination of the corresponding pollutants in this Standard if their applicability meets the requirements.
8.2 Air pollutant monitoring
8.2.1 Sampling shall be carried out at the specified pollutant emission monitoring location
according to the type of air pollutants to be monitored; if there are waste gas treatment facilities, testing shall be carried out after the facilities. The monitoring and sampling of air pollutants in exhaust tubes shall be carried out in accordance with the provisions of GB/T 16157, HJ 916, HJ/T 397, HJ/T 365 or HJ75.
8.2.2 The monitoring of heavy metal pollutants in air pollutants shall be carried out at least once
at least include hydrogen chloride, sulfur dioxide, nitrogen oxides, particulate matter, carbon monoxide and flue gas oxygen content. The collection and transmission of online automatic monitoring data shall meet the requirements of HJ 75 and HJ 212.
8.3 Monitoring of water pollutant
8.3.1 The monitoring of water pollutants shall be carried out in accordance with the
determination methods specified in GB 8978 and HJ 91.1.
8.3.2 Wastewater metering devices and online automatic monitoring equipment shall be set up
in accordance with relevant national and local requirements.
8.4 Other monitoring
8.4.1 The loss on ignition shall be monitored at least once a week. The collection and
preparation methods of the sample shall be carried out in accordance with HJ/T 20; and the test steps shall refer to HJ 1024.
8.4.2 The online automatic monitoring indicators of the incinerator operating conditions shall
at least include the temperature measured by the thermocouple in the furnace.
9 Implementation and Supervision
9.1 The ecological and environmental authorities at or above the county level shall be
responsible for supervising the implementation of this Standard.
9.2 Except for force majeure disasters and other emergency situations, hazardous waste
incineration facilities shall meet the pollution control requirements of this Standard and take necessary measures to ensure the normal operation of pollution prevention and control facilities.
9.3 When conducting supervisory inspections on hazardous waste incineration facilities, the
ecological and environmental authorities at all levels may use the results of on-site real-time sampling or monitoring of water pollutants as the basis for determining whether the discharge behavior complies with the emission standards and the implementation of relevant ecological and environmental protection management measures. For atmospheric pollutants, they may use manual monitoring and any 1-hour average concentration value measured in accordance with the monitoring specifications as the basis for determining whether the discharge behavior complies with the emission standards and the implementation of relevant ecological and environmental protection management measures.
9.4 In addition to the conditions specified in 7.2.4, the CEMS daily average data can be used as
a basis for determining whether the pollution discharge behavior complies with the emission standards. If the thermocouple temperature in the furnace does not meet the requirements of 7.2.5, and that cumulative temperature exceeds 5 times in one natural gate, it shall be determined as "failure to take measures conducive to reducing persistent organic pollutant
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Normative references
- GB 14554Emission standards for odor pollutants
- GB 16297Integrated emission standard of air pollutants
GB 8978 · GB 12348
Cited by
- GB/T 47051-2026Technical specification for the thermal regeneration of spent activated carbon
- GB/T 36380-2025Treatment and disposal specification for waste sulfuric acid from industrial manufacture
- GB/T 45609-2025Technical and evaluation requirement for plasma treatment of hazardous waste
- GB/T 42550-2023Resource utilization of agricultural wastes - Disposal and recycling of packaging waste for agriculture production means
- GB 39707-2020Medical waste disposal pollution control standard
- GB/T 31731-2015General technical specification for the recovery and recycling of waste musical instruments
How to Buy GB 18484-2020
- 1Add to cart. Click the "Buy GB 18484-2020" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 14554-1993 — Emission standards for odor pollutants
GB 16297-1996 — Integrated emission standard of air pollutants
GB 11118-2026 — Hydraulic fluids (L-HL, L-HM, L-HV, L-HS and L-HG type)
Secure payment via Stripe
Payments accepted
GB 18484-2020
$245.00