Scope
GB 16806-2006 is the English-translated version of 消防联动控制系统.
GB 16806-2006 specifies the definition, general requirements, requirements and test methods, inspection rules and marking of automatic control systems for fire protection installed in general industrial and civil buildings, and of the equipment that makes them up: fire linkage controllers, gas extinguishing controllers, fire electrical control devices, emergency power supplies for fire equipment, fire emergency broadcast equipment, fire telephones, transmission equipment, graphic display devices for the fire control room, modules, fire motorized devices and fire hydrant buttons.
The general requirements cover access levels for operating functions, indicator lamps, displays, audible devices (65 dB to 115 dB at 1 m), fuses, terminals and earthing, standby batteries, wiring, component temperature rise, instructions and software; each device then has its own functional requirements, such as a start signal within 3 s of a fire alarm and feedback within 10 s for the fire linkage controller.
Clause 5 gives the basic performance test of each device together with insulation resistance, leakage current, electric strength, electromagnetic immunity and climatic and mechanical environmental tests, followed by inspection rules, marking and a normative annex on storage battery tests.
It replaces GB 16806-1997, splitting the former basic function test by device, replacing the withstand voltage test with leakage current and electric strength tests, and adding endurance damp heat, surge, conducted disturbance and voltage dip immunity tests; Clauses 4 to 7 are mandatory.
Issued on 17 July 2006, in force from 1 April 2007. Classification: ICS 13.220.20, CCS C81. The document runs to 63 pages, delivered complete in English translation.
Found what you need?
Document preview — GB 16806-2006
National Standard of the People's Republic of China
- ICS
- 13.220.20
- Classification
- C81
- Replacing
- GB 16806-1997
Issued by: General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China; Standardization Administration of China
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 General requirements
- 5 Requirements and test methods
- 6 Inspection rules
- 7 Marking
- Annex A (normative) Electromagnetic performance requirements
3 Terms and definitions
4 General requirements
5 Requirements and test methods
6 Inspection rules
7 Marking
Foreword
Clauses 4, 5, 6 and 7 of this standard are mandatory; the rest is recommended.
This standard replaces GB 16806-1997 General technical requirements for fire linkage control equipment.
The main changes of this standard compared with GB 16806-1997 are as follows:
- the basic function test of the former standard has been divided into several parts: basic performance test of the fire linkage controller, of the gas extinguishing controller, of the fire electrical control device, of the emergency power supply for fire equipment, of the fire emergency broadcast equipment, of the fire telephone, of the transmission equipment, of the graphic display device for the fire control room, of modules, of fire hydrant buttons and of fire motorized devices;
- the leakage current test and the electric strength test replace the withstand voltage test for assessing safety performance;
- the damp heat, steady state (endurance) test, the surge immunity test, the immunity test to conducted disturbances induced by radio-frequency fields and the voltage dips, short interruptions and voltage variations immunity test have been added;
- some former test items have been deleted, such as the power-on test, the high temperature test and the low temperature storage test.
This standard was proposed by the Ministry of Public Security of the People's Republic of China.
This standard is under the jurisdiction of Subcommittee 6 of the National Technical Committee for Fire Protection Standardization.
Organization responsible for drafting this standard: Shenyang Fire Research Institute of the Ministry of Public Security.
Organizations participating in drafting: Shenyang Fire Electronic Equipment Factory, Xi'an Shengsaier Electronics Co., Ltd., Shanghai Songjiang Electronic Instrument Factory, Beijing Shizong Intelligent Co., Ltd., Shenzhen Fu'an Security System Co., Ltd., Beijing Lida Huaxin Electronics Co., Ltd., Beijing Shidao Fire Electronics Co., Ltd., Gulf Security Technology Co., Ltd., Xi'an Laikesi Electronic Engineering Co., Ltd., Beijing Chongzheng Huasheng Emergency Lighting System Co., Ltd., Dalian Guobiao Emergency Power Supply Co., Ltd., Hefei Sungrow Power Supply Co., Ltd., Guangdong Zhicheng Champion Group Co., Ltd., Qingdao Chuangtong Technology Group, Beijing Hengye Shiji Electric Technology Co., Ltd., Beijing Yuanjie Electronics Co., Ltd., Qinhuangdao Gulf Alarm Network Co., Ltd.
Main drafters of this standard: Song Xiwei, Guo Tienan, Zhu Liping, Ding Hongjun, Zhang Yingcong, Liu Cheng, Zhang Decheng, Zhang Xuejun, Wang Xuelai, Sun Shuang, Sui Hulin, Tong Ruitao, Wang Jun, Yang Bo, Lv Xinchi, Lu Shaoran, Liu Meihua, Wang Yan'e, Yang Ying, Li Haitao, Wang Yuxiang, Guo Chunlei, Lin Qiang, Liu Chang'an, Kang Weidong, Sun Zhenhui, Guo Lizhi, Liu Ziwei, Guo Rui, Ma Qingbo, Ma Li, Li Huijing, Li Ding, Chen Yingxiong, Zhao Yingran, Luan Jun, Li Ning, Cai Jun, Sun Yibiao, Cao Renxian, Sui Xueli, Yan Zhiming.
Previous editions of the standard replaced by this standard:
- GB 16806-1997.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 63 pages — is available in the English PDF.
Referenced standards
Normative references
- GB 3380Ringing and tone for telephone automatic switching network
- GB 12978Rules for test of fire electronic products
- GB/T 14716-1993Generic specification for stored program control analogue private automatic branch telephone exchange system
- GB/T 15279-2002Technical requirements and test methods for fixed-line telephone sets
- GB 16838Environmental test and severities for fire electronic products
- GB/T 17626.2-1998Electromagnetic compatibility -- Testing and measurement techniques -- Electrostatic discharge immunity test
GB 156-2003 · GB 4706.1-1998 · GB 9969.1
Cited by
- GB 6245-2025Fire pumps
- GB 17945-2024Fire emergency lighting and evacuate indicating system
- GB 4717-2024Fire alarm control units
- GB/T 19960-2024Wind energy generation systems - General technical specification and test methods for wind turbines
- GB/T 44481-2024Technical specification for inspection and testing of building fire protection facilities
- GB/T 36545-2023Technical specification of mobile electrochemical energy storage system
Similar standards
How to Download GB 16806-2006
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 12978-2003 — Rules for test of fire electronic products
GB 12978-2025 — Rules for test of fire electronic products
GB 16838-2005 — Environmental test and severities for fire electronic products
Secure payment via Stripe
Payments accepted
GB 16806-2006
$770.00