GB/T 34120-2023Technical requirements for power conversion system of electrochemical energy storage system (English PDF)
电化学储能系统储能变流器技术要求
Open the GB/T 34120-2023 preview as PDF
This is a limited preview
Buy now to download the full PDF (59 pages)
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 28, 2023
Implementation date
July 1, 2024
Scope
GB/T 34120-2023 is the English-translated version of 电化学储能系统储能变流器技术要求.
GB/T 34120-2023 specifies the converter that stands between a storage battery and the grid. The battery holds the energy, but the power conversion system decides what the installation can actually do: it converts between DC and AC in both directions, and it is what responds when the grid frequency moves, what rides through a voltage dip instead of disconnecting, and what holds the battery within the operating window that determines its life. As storage has grown from a niche to a substantial share of new grid connections, its behaviour during disturbances has stopped being the operator's private business — a fleet of converters that all disconnect at the same threshold turns a local fault into a system event. This document specifies the technical requirements for the power conversion system of an electrochemical energy storage system, including functional requirements such as start-up and shutdown and power control, together with the performance, protection and grid interaction requirements and the corresponding tests. Under CCS F19, it is written for converter manufacturers, for storage system integrators and project developers, and for the grid operators who set connection conditions and the laboratories that verify compliance with them.
Document preview — GB/T 34120-2023
National Standard of the People's Republic of China
- ICS
- 27.180
- Classification
- F19
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- 1 Scope5
- 2 Normative references5
- 3 Terms and definitions6
- 4 Classification and coding8
- 5 Normal operating conditions11
- 6 Appearance and protection grade12
- 7 Basic functions13
- 8 Performance indicators15
- 9 Electromagnetic compatibility39
- 10 Auxiliary systems43
- 11 Inspection rules44
- 12 Marking, packaging, transportation and storage48
- Appendix A (Informative) Typical topologies of power conversion systems for energy storage51
- Appendix B (Normative) Equipment symbols53
- Appendix C (Normative) Clearance and creepage distance55
- Bibliography59
Foreword
This document was issued on 28 December 2023 by the State Administration for Market Regulation; Standardization Administration of the PRC and takes effect on 1 July 2024.
It is a GB/T standard: recommended rather than compulsory, but it is the text a Chinese reviewer applies when assessing a submission.
1 Scope
GB/T 34120-2023 specifies the converter that stands between a storage battery and the grid. The battery holds the energy, but the power conversion system decides what the installation can actually do: it converts between DC and AC in both directions, and it is what responds when the grid frequency moves, what rides through a voltage dip instead of disconnecting, and what holds the battery within the operating window that determines its life. As storage has grown from a niche to a substantial share of new grid connections, its behaviour during disturbances has stopped being the operator's private business — a fleet of converters that all disconnect at the same threshold turns a local fault into a system event. This document specifies the technical requirements for the power conversion system of an electrochemical energy storage system, including functional requirements such as start-up and shutdown and power control, together with the performance, protection and grid interaction requirements and the corresponding tests. Under CCS F19, it is written for converter manufacturers, for storage system integrators and project developers, and for the grid operators who set connection conditions and the laboratories that verify compliance with them.
This document specifies the technical requirements for power conversion system of
electrochemical energy storage system (hereinafter referred to as “power conversion
system”), including functional requirements such as start-up and shutdown, power
control, grid-connected and grid-disconnected switching, alarm and protection,
insulation resistance detection, communication, operation information monitoring,
statistics, data display and storage; the performance requirements such as electrical
performance and safety performance; and the requirements for classification and coding,
normal operating conditions, appearance and protection grade, electromagnetic
compatibility, auxiliary systems, inspection rules, marking, packaging, transportation
and storage, etc.
This document is applicable to the design, manufacture, testing, inspection, operation,
maintenance and repair of power conversion systems using electrochemical cells as the
energy storage medium, with an AC terminal voltage of 35 kV and below.
2 Normative references
The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
GB/T 191, Packaging - Pictorial marking for handling of goods
GB/T 4208, Degrees of protection provide by enclosure (IP code)
GB/T 4798.2, Classification of environmental conditions - Classification of groups
of environmental parameters and their severities - Part 2.Transportation and
handling
GB/T 12325, Power quality - Deviation of supply voltage
GB/T 12326, Power quality - Voltage fluctuation and flicker
GB/T 13384, General specifications for packing of mechanical and electrical
product
GB/T 14549, Quality of electric energy supply - Harmonics in public supply
network
GB/T 15543, Power quality - Three-phase voltage
GB/T 15945, Power quality - Frequency deviation for power system
GB/T 17626.2, Electromagnetic compatibility - Testing and measurement
techniques-Electrostatic discharge immunity test
GB/T 17626.3, Electromagnetic compatibility - Testing and measurement
techniques - Part 3.Radiated, radio-frequency, electromagnetic field immunity test
GB/T 17626.4, Electromagnetic compatibility - Testing and measurement
techniques - Electrical fast transient/burst immunity test
GB/T 17626.5, Electromagnetic compatibility - Testing and measurement
techniques - Surge immunity test
GB/T 17626.6, Electromagnetic compatibility - Testing and measurement
techniques - Immunity to conducted disturbances, induced by radio-frequency
fields
GB/T 17626.8, Electromagnetic compatibility (EMC) - Part 4-8.Testing and
measurement techniques - Power frequency magnetic field immunity test
GB/T 17799.2, Electromagnetic compatibility - Generic standards - Part 2.
Immunity standard for industrial environments
GB/T 20626.1, Specific environmental condition - Electric and electronic products
for plateau - Part 1.General technical requirements
GB/T 24337, Power quality - Interharmonics in public supply network
GB/T 34133, Testing code for power conversion system of energy storage system
DL/T 860 (all parts), Communication networks and systems for power utility
automation
DL/T 2528, General terminology of electrical energy storage
3 Terms and definitions
For the purposes of this document, terms and definitions given in DL/T 2528, as well
as the following, applies to this document.
3.1
The capability of the power conversion system to continuously operate without being
disconnected from the grid within the specified voltage rise range and time interval
when the AC terminal voltage of the power conversion system increases due to power
system accidents or disturbances.
3.8
primary frequency control
The control function in which the power conversion system automatically adjusts active
power in response to the frequency deviation of the power system when the power
system frequency deviates from the target frequency.
[Source. GB/T 40595-2021, 3.1, modified]
3.9
inertia response
The control function in which the power conversion system adjusts active power in
response to the rate of change of power system frequency when the power system
frequency changes rapidly.
3.10
touch current
The current flowing through the body of a person or livestock when the person or
livestock touches one or more accessible parts of an electrical installation or electrical
equipment.
[Source. GB/T 17045-2020, 3.9]
4 Classification and coding
4.1 Product classification
4.1.1 According to the connection relationship with the power grid
Power conversion systems, according to the connection relationship with the power grid,
can be classified into.
-- grid-connected and grid-disconnected switching type power conversion
systems;
-- grid-connected type power conversion systems;
-- grid-disconnected type power conversion systems.
4.1.2 According to the connected voltage level
Power conversion systems, according to the connected voltage level, can be classified
into.
-- Class A1 power conversion system, a power conversion system applied to
energy storage power stations connected to the power grid through a voltage
level of 10(6) kV and above, and with an AC terminal voltage of the power
conversion system not greater than 1 000 V;
-- Class A2 power conversion system, a power conversion system applied to
energy storage power stations connected to the power grid through a voltage
level of 10(6) kV and above, and with an AC terminal voltage of the power
conversion system greater than 1 000 V;
-- Class B1 power conversion system, a power conversion system applied to
connection to the distribution network through 10(6) kV;
-- Class B2 power conversion system, a power conversion system applied to
connection to the distribution network through 380 V;
-- Class B3 power conversion system, a power conversion system applied to
connection to the distribution network through 220 V.
4.1.3 According to installation and service environment
Power conversion systems, according to the installation and service environment, can
be classified into.
-- indoor type power conversion system, a power conversion system installed
inside a building or an enclosure with a protection grade of IP54 and above;
-- outdoor type power conversion system, a power conversion system with its
structure completely or partially exposed outdoors.
4.1.4 According to cooling method
Power conversion systems, according to the cooling method, can be classified into.
-- natural cooling type power conversion system;
-- air cooling type power conversion system;
-- liquid cooling type power conversion system.
4.1.5 According to topology structure
Power conversion systems, according to the topology structure, can be classified into.
Example 1.
A power conversion system with a DC voltage range of 580 V ~ 1 500 V, an AC terminal
rated voltage of 400 V, a rated power of 50 kW, and a single-stage conversion topology,
is marked as. EES-PCS-580~1 500 V-400 V-50 kW-S-xxxxx.
Example 2.
A power conversion system with a DC voltage range of 350 V ~ 700 V, an AC terminal
rated voltage of 800 V, a rated power of 200 kW, and a two-stage conversion topology,
is marked as. EES-PCS-350~700 V-800 V-200 kW-D-xxxxx.
Example 3.
A power conversion system with a DC operating voltage range of 500 V ~ 1 200 V, an
AC terminal rated voltage of 10 kV, a rated power of 5 MW, and a cascaded topology,
is marked as. EES-PCS-500~1 200 V-10 kV-5 MW-H-xxxxx.
5 Normal operating conditions
5.1 Environmental conditions
The power conversion system shall operate normally under the following
environmental conditions.
a) Temperature. -20 degrees C ~ +40 degrees C;
b) Relative humidity. <=95%;
c) For power conversion systems applied under high-altitude conditions above 2
000 m, comply with the relevant provisions of GB/T 20626.1;
d) For power conversion systems applied in marine climate, meet the salt spray
resistance requirements.
5.2 Electrical conditions for grid-connected operation
Grid-connected and grid-disconnected switching type power conversion systems and
grid-connected type power conversion systems shall operate normally under the
following power grid conditions.
a) The harmonic voltage shall not exceed the limits specified in GB/T 14549;
b) The interharmonic voltage shall not exceed the limits specified in GB/T 24337;
c) The power grid voltage deviation shall not exceed the limits specified in GB/T
12325;
d) The voltage fluctuation and flicker value shall not exceed the limits specified
in GB/T 12326;
e) The three-phase voltage unbalance factor shall not exceed the limits specified
in GB/T 15543;
f) The power grid frequency deviation shall not exceed the limits specified in
GB/T 15945.
5.3 Grid-disconnected operation conditions
Grid-connected and grid-disconnected switching type power conversion systems and
grid-disconnected type power conversion systems shall operate normally under the
following conditions.
a) The rated power of the load shall not be greater than the rated output power of
the power conversion system;
b) The load starting current shall not be greater than 1.2 times the rated current
of the power conversion system.
6 Appearance and protection grade
6.1 Appearance
The appearance of the power conversion system shall meet the following requirements.
a) The appearance shall be complete, without deformation, peeling, corrosion,
cracks or other phenomena;
b) The cabinet doors and switches shall operate flexibly;
c) The nameplate, signs and marks shall be complete and clear;
d) The texts and symbols shall be neat, standardized and correct.
6.2 Protection grade
The protection grade of the enclosure of the power conversion system shall meet the
following requirements.
a) The protection grade of indoor type power conversion systems shall be not
lower than IP20 specified in GB/T 4208;
b) The protection grade of outdoor type power conversion systems shall be not
lower than IP54 specified in GB/T 4208.
7 Basic functions
7.1 Start-up and shutdown
The power conversion system shall have the start-up and shutdown control function,
and be capable of starting up and shutting down the power conversion system according
to control switches or commands.
7.2 Power control
The power conversion system shall have active power control and reactive power
control functions, and be capable of continuously and smoothly adjusting active power
and reactive power as well as switching between charging and discharging according
to the control mode or received power control commands. Class A1 and Class A2 power
conversion systems should have primary frequency control and inertia response control
functions.
7.3 Grid-connected and grid-disconnected switching
The grid-connected and grid-disconnected switching type power conversion system
shall have the grid-connected and grid-disconnected switching function, and be capable
of switching from grid-connected mode to grid-disconnected mode according to the set
conditions, and establishing stable frequency and voltage; and be capable of switching
from grid-disconnected mode to grid-connected mode according to upper-level
commands, meeting the corresponding power requirements.
7.4 Alarm and protection
7.4.1 The power conversion system shall have a fault diagnosis function, and shall be
capable of giving alarms when abnormal conditions occur. The alarm should adopt
audible, visual and other indication methods. The alarm contents shall include. reverse
polarity connection, incorrect phase sequence of AC incoming line, DC voltage
abnormality, overcurrent, overtemperature, communication fault and cooling system
fault, etc.
7.4.2 After the power conversion system sends an alarm signal, it shall enter an
abnormal operation state or fault protection state.
7.4.3 The power conversion system shall have a fault information recording function,
be capable of recording fault and alarm information, and store the information.
7.5 Insulation resistance detection
7.5.1 The power conversion system shall have the DC terminal insulation resistance
detection function, and this function may be enabled or disabled as required.
7.5.2 When the insulation resistance value detected by the power conversion system is
lower than the set protection value, the power conversion system shall give an alarm
and stop operation.
Note. The protection value may be selected by default as the ratio of the maximum
DC voltage to 30 mA.
7.6 Communication
7.6.1 The power conversion system shall have the function of information interaction
with equipment such as battery management systems and monitoring systems.
7.6.2 The communication interfaces between the power conversion system and the
battery management system may adopt controller area network (CAN), RS-485,
Ethernet, wireless and other communication interfaces, and support communication
protocols such as CAN2.0B, Modbus, DL/T 860 (all parts), and Message Queuing
Telemetry Transport (MQTT).
7.6.3 The communication interface between the power conversion system and the
monitoring system may adopt Ethernet communication interface, and support
communication protocols such as Modbus TCP and DL/T 860 (all parts). Dual-network
redundant communication should be adopted.
7.7 Operation information monitoring
7.7.1 The power conversion system shall be capable of monitoring in real time the
voltage, current, power and battery status information of the DC terminal, as well as the
voltage, current, frequency and power information of the AC terminal.
7.7.2 The power conversion system shall be capable of monitoring in real time the
communication status between the power conversion system and equipment such as
battery management systems and monitoring systems.
7.8 Statistics
7.8.1 The power conversion system shall have a fault information statistics function to
realize the query of fault information.
7.8.2 The power conversion system should have charging energy and discharging
energy statistics functions to realize the query of charging and discharging energy
information.
7.9 Data display and storage
7.9.1 The power conversion system shall have a data display function and be capable
of displaying information such as operating status, operating parameters, protection
parameters and event records.
......
Remaining clauses in the full document
- 8 Performance indicators
- 9 Electromagnetic compatibility
- 10 Auxiliary systems
- 11 Inspection rules
- 12 Marking, packaging, transportation and storage
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 59 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 191, Packaging - Pictorial marking for handling of goodsGraphical symbols marking for handling and storage of packages
- GB/T 4208, Degrees of protection provide by enclosure (IP code)Degrees of protection provided by enclosures (IP code)
- GB/T 12325, Power quality - Deviation of supply voltagePower quality - Deviation of supply voltage
- GB/T 12326, Power quality - Voltage fluctuation and flickerPower quality - Voltage fluctuation and flicker
- GB/T 13384, General specifications for packing of mechanical and electricalGeneral specifications for packing of mechanical and electrical product
- GB/T 14549, Quality of electric energy supply - Harmonics in public supplyQuality of electric energy supply--Harmonics inpublic supply network
GB/T 4798.2, Classification of environmental conditions - Classification of groups · GB/T 17626.2, Electromagnetic compatibility - Testing and measurement · GB/T 17626.3, Electromagnetic compatibility - Testing and measurement · GB/T 17626.4, Electromagnetic compatibility - Testing and measurement · GB/T 17626.5, Electromagnetic compatibility - Testing and measurement · GB/T 17626.6, Electromagnetic compatibility - Testing and measurement · GB/T 17626.8, Electromagnetic compatibility (EMC) - Part 4-8.Testing and · GB/T 17799.2, Electromagnetic compatibility - Generic standards - Part 2.
Cited by
- GB/T 32900-2025Technical requirements for the relay protection of photovoltaic power stations
- GB/T 46266-2025Mobile energy storage power supplies for household and similar electrical appliances
- GB/T 43686-2024Guide for post evaluation of electrochemical energy storage station
- GB/T 44111-2024Code of maintenance test for electrochemical energy storage station
- GB/T 44659.3-2024Short-circuit current calculation for renewable energy power stations and connection systems - Part 3
- NB/T 11488-2024General specification for power conversion system of flow battery energy storage system
Similar standards
How to Buy GB/T 34120-2023
- 1Add to cart. Click the "Buy GB/T 34120-2023" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 47310-2026 — Determination of total silicon, aluminium, iron, potassium, sodium, calcium, magnesium, manganese, phosphorus, titanium and sulfur in soil - Monochromatic excitation energy dispersive X-ray fluorescence spectrometry
GB/T 47321-2026 — Specification for the warning data exchange of the national emergency early warning dissemination system
GB/T 47293-2026 — Determination of available mercury in soil
Secure payment via Stripe
Payments accepted
GB/T 34120-2023
$590.00