GB 50243-2016Code of Acceptance for Construction Quality of Ventilation and Air (English PDF)
通风与空调工程施工质量验收规范
Also coversGB50243-2016
This is a limited preview
Buy now to download the full PDF
Need quotation for your management?
Get a formal quotation for GB 50243-2016 in 30 minutes.
Issued by
Ministry of Housing and Urban-Rural Development
Level / Type
National · Mandatory
Issue date
October 25, 2016
Implementation date
July 1, 2017
Scope
GB 50243-2016 is the English-translated version of 通风与空调工程施工质量验收规范.
GB 50243-2016 is the Chinese standard "Code of Acceptance for Construction Quality of Ventilation and Air". Its scope clause reads: This code is developed with a view to unifying the quality acceptance for construction of ventilation and air conditioning and guaranteeing the work safety and quality.
This code is applicable to construction quality acceptance of the ventilation and air conditioning for industrial and civil buildings. This code shall be used in conjunction with the current national standard GB 50300 Unified Standard for Constructional Quality Acceptance of Building Engineering.
The requirements for constructional quality of work which are specified for ventilation and air conditioning works in engineering technical document and work contract shall not be lower than those specified in this code. Its clauses include general provisions; terms; basic requirements.
Found what you need?
Document preview — GB 50243-2016
National Standard of the People's Republic of China
- Replacing
- GB 50243-2002
Issued by: Ministry of Housing and Urban-Rural Development
Contents
- Foreword
- 1 General provisions
- 2 Terms
- 3 Basic requirements
- 4 Duct making
- 4.1 General requirements
- 4.2 Dominant items
- 4.3 General items
- 5 Duct accessory
- 5.1 General requirements
- 5.2 Dominant items
- 5.3 General items
- 6 Duct system installation
- 6.1 General requirements
- 6.2 Dominant items
- 6.3 General items
- 7 Installation of fan and air handling equipment
- 7.1 General requirements
- 7.2 Dominant items
- 7.3 General items
- 8 Cold/heat source and auxiliary equipment installation
- 8.1 General requirements
- 8.2 Dominant items
- 8.3 General items
- 9 Installation of pipeline and equipment of air conditioning water system
- 9.1 General requirements
- 9.2 Dominant items
- 9.3 General items
- 10 Anticorrosion and thermal insulation
- 10.1 General requirements
- 10.2 Dominant items
- 10.3 General items
- 11 System commissioning
- 11.1 General requirements
- 11.2 Dominant items
- 11.3 General items
- 12 Final acceptance
- Annex A Recording table for acceptance of project quality
- Annex B Sampling procedures for inspection
- Annex C Duct Strength and Leakage Test
- Annex D Clean rooms (areas) engineering inspection and testing
- Annex E Basic requirements of system commissioning
- Explanation of wording in this code
- List of quoted standards
1 General provisions
1.0.1
This code is developed with a view to unifying the quality acceptance for construction of ventilation and air conditioning and guaranteeing the work safety and quality.
1.0.2
This code is applicable to construction quality acceptance of the ventilation and air conditioning for industrial and civil buildings.
1.0.3
This code shall be used in conjunction with the current national standard GB 50300 Unified Standard for Constructional Quality Acceptance of Building Engineering.
1.0.4
The requirements for constructional quality of work which are specified for ventilation and air conditioning works in engineering technical document and work contract shall not be lower than those specified in this code.
1.0.5
The construction quality acceptance for ventilation and air conditioning works shall comply with not only this code but also the current relevant standards of the nation.
2 Terms
2.0.1 ventilation works
generic term for air supply, air exhaust, smoke control/exhaust, dedusting and pneumatic conveying system works
2.0.2 air conditioning works
generic term for comfort air conditioning, constant temperature and humidity air conditioning, cleanroom air purification and air conditioning system works
2.0.3 duct
duct, made from metallic, nonmetallic sheet or other material, for ventilation.
2.0.4 nonmetallic duct
duct made from such nonmetallic materials as rigid PVC and glass reinforced plastic (GRP)
2.0.5 foil-insulant composite duct
duct with incombustible surface course, made from thermal insulation material of flame resisting grade or above
2.0.6 refractory duct
duct made from composite incombustible and fire-resistant thermal insulation materials and reaching a specific fire endurance limit
2.0.7 duct fittings
components of duct system, e.g. elbow, tee, cross, special pipe, guide vane and flange
2.0.8 duct accessory
functional parts of duct system, e.g. vent, valve, hood, cowl, silencer, air filter, inspection door and determination hole
2.0.9 air channel
channel, made from such building materials as concrete and brick, for ventilation.
2.0.10 ventilating ducts for kitchen and bathroom
channels for discharging the fume generated by cooking appliance from kitchen and foul gas from bathroom in residential building
2.0.11 design working pressure
maximum design working pressure at the main duct of system
2.0.12 air leakage rate
air volume discharged from or infiltrated into the duct system under a certain static pressure over a unit time, through the main structure or joint of duct.
2.0.13 duct system permissible leakage rate
maximum permissible air leakage as per the average unit surface area and unit the specified according to the classification of duct system
2.0.14 duct system leakage ratio
percentage ratio of the air leakage at working pressure, e.g. duct system, air conditioning equipment, deduster, to the rated air flow
2.0.15 jiggle protection support
supports and hangers or pipe racks protecting duct or conduit from jiggling displacement
2.0.16 strength test
determination and inspection on pressure resistance, e.g. pipeline, vessel, valve, carried out at specified pressure and within specified pressure holding time
2.0.17 leakage test
determination and inspection on leakage resistance, e.g. pipeline, vessel, valve, carried out at specified pressure and within holding time
2.0.18 absorption refrigeration device
refrigeration device which is thermally driven and use ammonia-water or water-lithium bromide as refrigerating medium
2.0.19 air cleanliness class
cleanliness level determined by the counts of particles of some size in unit volume of air
2.0.20 fan filter unit
cellular air supply unit for space cleaning which is composed of fan case and high efficiency filter, etc.
2.0.21 as-built
(of cleanroom) with installations set up and all powers switched on and operating but no production equipment, material and operator
2.0.22 at-rest
(of cleanroom) with installations set up, production equipment installed, operated as agreed by the owner and supplier, but with no personnel responsible for production
2.0.23 operation
(of cleanroom) with facilities operating in specified mode, at the presence of specified number of personnel, and production equipment operating in the status as agreed between the owner and the supplier
2.0.24 declared quality level
upper limit of total unqualified product(s) in inspection lot
3 Basic requirements
3.0.1
The acceptance for construction quality of ventilation and air conditioning works shall comply with not only the provisions of this code but also approved design documents and contracted items.
3.0.2
As far as works modification is concerned, a design alteration notice or technical approval from the Designer must be provided. Where the construction enterprise undertakes in-depth design for the construction drawings of ventilation and air conditioning, the drawings shall be confirmed by engineering design organization.
3.0.3
The main raw materials, as well as the material, specification and performance of finished product, semi-finished product and equipment, shall comply with the design documents and current national standards and materials or equipment that are expressly prohibited or obsoleted by the State shall not be adopted. The site acceptance of main raw material, finished product, semi-finished product and equipment shall meet the following requirements:
1 The approaching quality acceptance shall be confirmed by supervision engineer or the relevant person in-charge of the Developer.
2 Imported materials and equipment shall be provided with valid documents such as commodity inspection conformity certificate and Chinese quality certificate.
3.0.4
The new technology, new process, new material and new equipment adopted by ventilation and air conditioning works shall be provided with certificate of special technical appraisal acceptance.
3.0.5
The construction of ventilation and air conditioning works shall be carried out following established procedure and cooperate with civil engineering and other disciplines. The finished civil engineering construction relevant to ventilation and air conditioning system shall be jointly checked by the Developer (or General Contractor), Supervisor, Designer and Constructor. Organization of such joint check should be in the charge of the Developer, Supervisor or General Contractor.
3.0.6
Concealed ventilation and air conditioning works, before being concealed, shall be accepted and confirmed by the Supervisor or Developer and image information shall be kept up where necessary.
3.0.7
The acceptance for construction quality of ventilation and air conditioning division project shall be carry out by the subdivision projects listed in Table 3.0.7 and the section projects they contained, according to actual engineering conditions. Division project acceptance shall be passed provided all the subdivision projects contained are totally passed. Where a ventilation and air conditioning work is accepted as unit project or subunit project, its division projects shall be upgraded to unit project or subunit project, its subdivision projects shall be upgraded to division project, and its section projects shall be classified according to those specified in Table 3.0.7. Quality acceptance records shall meet those specified in Annex A hereof.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Cited by
- GB/T 17790-2025Installation specifications for household and similar air-conditioner
- GB/T 46752-2025Integrated high-efficiency air conditioning cold source systems for buildings
- GB/T 43685-2024General technical requirements for cabin of inflatable membrane structure and controlled environments
- GB/T 41318-2022Ventilation silencer
- GB/T 41740-2022Prefabricated energy station
- GA/T 830-2021Vehicle mounted high-range sprayers with a fan
How to Download GB 50243-2016
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 11118-2026 — Hydraulic fluids (L-HL, L-HM, L-HV, L-HS and L-HG type)
GB 11557-2026 — Provisions for protecting drivers from injury by the steering mechanism of motor vehicles
GB 12021.4-2026 — Maximum allowable values of the energy consumption, water consumption and grades for electric washing machines and washer-dryers
Secure payment via Stripe
Payments accepted
GB 50243-2016
$885.00