GB 19577-2024Minimum allowable values of energy efficiency and energy efficiency grades for heat pumps and water chillers (English PDF)

热泵和冷水机组能效限定值及能效等级

Preview PDF

This is a limited preview

Buy now to download the full PDF (20 pages)

Need quotation for your management?

Get a formal quotation for GB 19577-2024 in 30 minutes.

Issued by

State Administration for Market Regulation; Standardization Administration of China

Level / Type

National · Mandatory

Issue date

April 29, 2024

Implementation date

February 1, 2025

Scope

GB 19577-2024 is the English-translated version of 热泵和冷水机组能效限定值及能效等级.

GB 19577-2024 is the Chinese national standard that sets the minimum allowable values of energy efficiency and the energy efficiency grades for heat pumps and water chillers.

It covers water chilling (heat pump) packages using the vapour compression cycle, low ambient temperature air source heat pump packages, water-source and ground-source heat pumps, lithium bromide absorption chillers and heaters, water-source high temperature heat pumps, indirect evaporative cooling chillers and integrated packages.

Efficiency is divided into three grades, grade 1 being the highest, with the values in Tables 1 to 8, and the minimum allowable values are those of grade 3. It also describes the test and calculation methods, including Annex A for air-cooled comfort chillers of 50 kW or less.

It replaces GB 19577-2015, GB 29540-2013, GB 30721-2014 and GB 37480-2019, was issued on 29 April 2024 and has applied since 1 February 2025.

Found what you need?

Document preview — GB 19577-2024

National Standard of the People's Republic of China

ICS
27.010
Classification
F01
Replacing
GB 19577-2015

Issued by: State Administration for Market Regulation; Standardization Administration of China

Contents

  • Foreword3
  • 1 Scope5
  • 2 Normative references5
  • 3 Terms and definitions6
  • 4 Energy efficiency grades8
  • 5 Technical requirements12
  • 6 Tests and calculation methods13
  • 7 Implementation of the document14
  • Annex A (normative) Tests and calculation methods for the cooling seasonal performance factor of air-cooled comfort chillers (CC <= 50 kW)15

1 Scope

This document specifies the technical requirements for the minimum allowable values of the energy efficiency and energy efficiency grades for heat pumps and water chillers, describes the corresponding test methods, and clarifies the implementation of this document.

The types of heat pumps and chillers to which this document applies include water chilling (heat pump) packages using the vapor compression, low ambient temperature air source heat pump (water chilling) packages, water-source (ground-source) heat pumps, lithium bromide absorption water chillers (heaters), water-source high temperature heat pumps using the vapor compression cycle, indirect evaporative cooling water chillers, and integrated water chilling (heat pump) packages.

2 Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

GB/T 10870 The methods of performance test for water chilling (heat pump) packages using the vaper compression cycle

GB/T 18362 Direct-fired lithium bromide absorption water chiller (heater)

GB/T 18430.1 Water chilling (heat pump) packages using the vapor compression cycle - Part 1: Water chilling (heat pump) packages for industrial & commercial and similar application

GB/T 18430.2 Water chilling (heat pump) packages using the vapor compression cycle - Part 2: Water chilling (heat pump) packages for household and similar application

GB/T 18431 Steam and hot water type lithium bromide absorption water chiller

GB/T 19409 Water-source (ground-source) heat pumps

GB/T 25127.1 Low ambient temperature air source heat pump (water chilling) packages - Part 1: Heat pump (water chilling) packages for industrial & commercial and similar application

GB/T 25127.2 Low ambient temperature air source heat pump (water chilling) packages - Part 2: Heat pump (water chilling) packages for household and similar application

GB/T 25861 Water-source high temperature heat pumps using the vapor compression cycle

JB/T 12839 Integrated water chilling (heat pump) package

JB/T 12840 Air source heat pump high temperature hot air & hot water unit

JB/T 14640 Composite indirect evaporative cooling water chiller for computer and data processing room

JB/T 14642 High-leaving water temperature chiller base on dew point indirect evaporative cooling

3 Terms and definitions

For the purpose of this document, the terms and definitions defined in GB/T 18430.1,

GB/T 18430.2, GB/T 18362, GB/T 18431, GB/T 10870, GB/T 19409, GB/T 25127.1,

GB/T 25127.2, GB/T 25861, JB/T 14640, JB/T 14642 and JB/T 12839 and the following apply.

3.1 Minimum allowable values of energy efficiency for water chilling (heat pump) packages using the vapor compression

Under the specified standard operating conditions, the minimum allowable values of the coefficient of performance (COPc), integrated part load value (IPLV), annual comprehensive cooling coefficient of performance (ACCOP) and (or) cooling seasonal performance factor (CSPF) of water chilling (heat pump) packages using the vapor compression.

3.2 Minimum allowable values of energy efficiency for low ambient temperature air source heat pump (water chilling) packages

Under the specified standard operating conditions, the minimum allowable values of the nominal heating coefficient of performance (COPh), low temperature heating coefficient of performance (COPdh), heating seasonal performance factor (HSPF) and (or) annual performance factor (APF) of low ambient temperature air source heat pump (water chilling) packages.

3.3 Minimum allowable values of energy efficiency for water-source (ground-source) heat pumps

Under the specified standard operating conditions, the minimum allowable values of the annual comprehensive coefficient of performance (ACOP) or heating coefficient of performance (COP) of water-source (ground-source) heat pumps.

NOTE: For heat-pump units, the annual comprehensive coefficient of performance (ACOP) is assessed; for single-heat units, the heating coefficient of performance (COP) is assessed.

3.4 Minimum allowable values of energy efficiency for lithium bromide absorption water chillers (heaters)

Under the specified standard operating conditions, the minimum allowable values of the coefficient of performance (COP) or the maximum values of the heating source consumption per unit cooling capacity of lithium bromide absorption water chillers (heaters).

NOTE: For vapor units, the heating source consumption per unit cooling capacity is assessed; for direct-fired units, the coefficient of performance (COP) is assessed.

3.5 Minimum allowable values of energy efficiency for water-source high temperature heat pumps using the vapor compression cycle

Under the specified standard operating conditions, the minimum allowable values of the heating coefficient of performance of water-source high temperature heat pumps using the vapor compression cycle.

NOTE: For water-source high temperature heat pumps, the heating coefficient of performance (COPH) is assessed; for periodical feeding heat pump high temperature hot water units, the heating coefficient of performance (COP) is assessed.

3.6 Minimum allowable values of energy efficiency for indirect evaporative cooling water chillers

Under specified standard operating conditions, the minimum allowable values of the annual energy efficiency ratio (AEER) or energy efficiency ratio (EER) of indirect evaporative cooling water chillers.

NOTE: For high-leaving water temperature chillers base on dew point indirect evaporative cooling used in data centers and similar places, the annual energy efficiency ratio (AEER) is assessed; for composite indirect evaporative cooling water chillers used in computer and data processing rooms, the energy efficiency ratio (EER) is assessed.

3.7 Minimum allowable values of energy efficiency for integrated water chilling (heat pump) package

Under specified standard operating conditions, the minimum allowable values of the integrated part load value (IPLVI) and nominal operating coefficient of performance (COPI) of integrated water chilling (heat pump) packages.

NOTE: For vapor-cooled, cooling-tower and air-cooled units, the integrated part load value (IPLVI) and nominal operating coefficient of performance (COPI) are assessed.

4 Energy efficiency grades

4.1 The energy efficiency grades for heat pumps and water chillers are divided into 3 grades, among which grade 1 has the highest energy efficiency.

4.2 The measured values and nominal values of the energy efficiency indicators of various types of heat pumps and water chillers shall not be less than the specified values corresponding to the energy efficiency grades in Tables 1 to 8.Among them, the indicators of energy efficiency grades for water chilling (heat pump) packages using the vapor compression adopt dual-channel evaluation indicators, i.e., select the energy efficiency value of one of the indicator systems in the comprehensive part load value (IPLV) (see Table 1) or the coefficient of performance (COPc) (see Table 2) to determine the energy efficiency grade.

5 Technical requirements

5.1 The minimum allowable values of energy efficiency for water chilling (heat pump) packages using the vapor compression, the minimum allowable values of energy efficiency for low ambient temperature air source heat pump (water chilling) packages, the minimum allowable values of energy efficiency for water-source (ground-source) heat pumps, the minimum allowable values of energy efficiency for lithium bromide absorption water chillers (heaters), the minimum allowable values of energy efficiency for water-source high temperature heat pumps using the vapor compression cycle, the minimum allowable values of energy efficiency for indirect evaporative cooling water chillers, and the minimum allowable values of energy efficiency for integrated water chilling (heat pump) packages are the indicator values corresponding to energy efficiency grade 3 in Tables 1 to 8.

5.2 For low ambient temperature air source heat pump (water chilling) packages with electric auxiliary heating, the electric auxiliary heating system shall be manually turned on and off, and its working status shall be expressed in an obvious position.

5.3 The marked values of energy efficiency for heat pumps and water chillers shall be within the range of values corresponding to their rated energy efficiency grades, and the measured values of energy efficiency shall not be less than the provisions in the corresponding product standards in Tables 1 to 8.

6 Tests and calculation methods

6.1 The energy efficiency test method for water chilling (heat pump) packages using the vapor compression shall be carried out in accordance with the relevant provisions of GB/T 18430.1 and GB/T 18430.2. The test and calculation of air-cooled comfort chillers with a nominal cooling capacity not exceeding 50 kW shall be carried out in accordance with the provisions of Annex A.

6.2 The energy efficiency test method for low ambient temperature air source heat pump (water chilling) packages shall be carried out in accordance with the relevant provisions of GB/T 25127.1 and GB/T 25127.2.

6.3 The energy efficiency test method for water-source (ground-source) heat pumps shall be carried out in accordance with the relevant provisions of GB/T 19409.

6.4 The energy efficiency test method of lithium bromide absorption water chillers (heaters) shall be carried out in accordance with the relevant provisions of GB/T 18431 and GB/T 18362.

6.5 The energy efficiency test method for water-source high temperature heat pumps using the vapor compression cycle shall be carried out in accordance with the relevant provisions of GB/T 25861 and JB/T 12840.

6.6 The energy efficiency test method for indirect evaporative cooling water chillers shall be carried out in accordance with the relevant provisions of JB/T 14642 and JB/T 14640. The dry-bulb and wet-bulb temperature distribution coefficients, used for the test conditions and calculation of the annual energy efficiency ratio (AEER) of high-leaving water temperature chillers base on dew point indirect evaporative cooling used in data centers and similar places, are tested and calculated according to the provisions for cold regions (refer to Beijing) in JB/T 14642 (referenced to Beijing).

7 Implementation of the document

Products produced or imported on the date of implementation of this document shall comply with the requirements of this document.

The sales of products produced or imported before the implementation of this document shall only be delayed until the 24th month after the implementation of this document. […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 20 pages — is available in the English PDF.

Referenced standards

Normative references

Similar standards

Editions of GB 19577

EditionTitleRevisionStatus
GB 19577-2024Minimum allowable values of energy efficiency and energy efficiency grades for heat pumps and water chillerssecond revisionCurrent
GB 19577-2015Minimum allowable values of energy efficiency and energy efficiency grades for water chillersfirst revisionSuperseded
GB 19577-2004Minimum allowable values of energy efficiency and energy efficiency grades for water chillersfirst issueSuperseded

This page sells the current edition, GB 19577-2024. Earlier editions are listed for reference only.

How to Download GB 19577-2024

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
20 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB 19577-2024

$320.00