Valid

NB/T 10327-2019Low-voltage active three-phase unbalanced load regulator (English PDF)

低压有源三相不平衡调节 装置

Preview PDF

This is a limited preview

Buy now to download the full PDF (25 pages)

Need quotation for your management?

Get a formal quotation for NB/T 10327-2019 in 30 minutes.

Issued by

NEA

Level / Type

Industry · Recommended

Issue date

December 30, 2019

Implementation date

July 1, 2020

Scope

NB/T 10327-2019 is the English-translated version of 低压有源三相不平衡调节 装置.

NB/T 10327-2019 covers low-voltage active three-phase unbalance regulators, power electronic devices that use converter technology to rebalance load currents automatically in AC distribution networks of 1 000 V and below, with 1 140 V systems treated by reference.

It defines terms such as three-phase current unbalance rate, rated capacity, rated loss, control range and step response time, and gives model naming, normal and special service conditions, and requirements for the basic circuit and components such as reactors, capacitors, breakers and fuses.

Further clauses set clearances and creepage distances, insulation levels, protection and alarms, operating modes and performance, environment and electromagnetic compatibility, followed by routine, type and field tests, nameplate and packaging.

Annexes explain the operating principle, grid connection point and filter and DC capacitor sizing. Issued on 30 December 2019, it has applied since 1 July 2020.

Found what you need?

Document preview — NB/T 10327-2019

National Standard of the People's Republic of China

ICS
29.240.99
Classification
K 46

Issued by: National Energy Administration of the People's Republic of China

Contents

  • Foreword
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 4 Model naming
  • 5 Conditions of use
  • 5.1 Normal use conditions
  • 5.2 Special conditions of use
  • 6 Technical requirements for basic circuit and component equipment
  • 6.1 Basic circuit
  • 6.2 Technical requirements for component equipment
  • 7 Technical requirements
  • 7.1 Appearance and structure
  • 7.2 Selection and installation of components and accessories
  • 7.3 Safety and protection
  • 7.4 Clearance and creepage distance
  • 7.5 Insulation level of the device
  • 7.6 Protection and alarm functions
  • 7.7 Operating mode requirements
  • 7.8 Operating performance requirements
  • 7.9 Operating environment
  • 7.10 Electromagnetic compatibility
  • 8 Test
  • 8.1 Test conditions
  • 8.2 Test items
  • 9 Inspection Rules
  • 9.1 Overview
  • 9.2 Routine test
  • 9.3 Type test
  • 9.4 Field test
  • 10 Logo, nameplate
  • 10.1 Marks and labels
  • 10.2 Nameplate
  • 11 Packaging, transportation and storage
  • 11.1 Packaging
  • 11.2 Transport
  • 11.3 Storage
  • 11.4 Documents supplied with the device
  • 11.5 Accessories provided with the device
  • Appendix A (informative appendix) How the device works
  • A.1 Overview
  • A.2 Device working principle and typical circuit
  • Appendix B (informative appendix) Electrical conditions of grid connection points
  • B.1 Overview
  • B.2 Device access point
  • B.3 Calculation formula of device compensation current
  • Appendix C (informative appendix) Parameter selection of device filter unit and DC capacitor
  • C.1 Overview
  • C.2 Filter unit parameter selection
  • C.3 DC side capacitor bank parameter selection

Foreword

The preparation of this standard is based on the rules given in GB/T 1.1-2009 "Guidelines for Standardization Part 1: Standard Structure and Compilation".

1 Scope

This standard specifies the terms and definitions, model naming, usage conditions, basic circuits and components of low-voltage active three-phase unbalanced regulators Equipment technical requirements, technical requirements, test, inspection rules, marking, packaging, transportation, and storage requirements.

This standard is applicable to AC power systems with a nominal voltage of 1 000 V and below. The variable current technology is used to balance the automatic adjustment of the three-phase load current.

Section device (hereinafter referred to as device), see Appendix A for the working principle of the device.

Note: Refer to this standard for devices used in 1140 V AC power systems.

2 Normative references

The following documents are indispensable for the application of this document. For dated reference documents, only the dated version applies to this document. For undated references, the latest version (including all amendments) applies to this document.

GB/T 1094.6 Power Transformer Part 6: Reactor

GB/T 2423.1-2008 Environmental testing of electric and electronic products Part 2: Test method Test A. Low temperature

GB/T 2423.2-2008 Environmental testing of electric and electronic products Part 2: Test method Test B. High temperature

GB/T 2423.3 Environmental testing of electrical and electronic products Part 2: Test method Test Cab. Constant damp heat test

GB/T 2423.4 Environmental testing of electrical and electronic products Part 2: Test method Test Db Alternating damp heat (12h + 12h cycle)

GB 2894-2008 Safety signs and guidelines for their use

GB/T 2900.33-2004 Electrical terminology power electronic technology

GB 3096 Acoustic Environmental Quality Standard

GB/T 3859.1 General requirements for semiconductor converters and power grid commutated converters Part 1-1.Basic requirements specification

GB/T 4025 Basic and safety rules for human-machine interface signs and coding rules for indicators and operators

GB/T 4208-2017 Enclosure protection grade (IP code)

GB 4824 Industrial, scientific and medical (ISM) radio frequency equipment disturbance characteristic limits and measurement methods

GB/T 7261 Basic test methods for relay protection and safety automatic devices

GB/T 7947 Basic and safety rules for human-machine interface logo identification Conductor color or alphanumeric identification

GB/T 9969 General Rules for the Use of Industrial Products

GB/T 10233-2005 Basic test methods for low-voltage switchgear and electric control equipment

GB/T 11032 AC gapless metal oxide surge arrester

GB/T 13539.1 Low-voltage fuses Part 1: Basic requirements

GB/T 14048.2 Low Voltage Switchgear and Control Equipment Part 2: Circuit Breaker

GB/T 14048.3 Low-Voltage Switchgear and Control Equipment Part 3: Switches, Isolators, Isolating Switches and Fuse Combinations

GB/T 14048.4 Low-voltage switchgear and control equipment Part 4-1.Contactors and motor starters Electromechanical contactors and electric Motor starter (including motor protector)

GB/T 14549 Power quality public grid harmonics

GB/T 14860.1 Transformers and inductors for electronic and communication equipment Part 1: General specifications

GB/T 15576-2008 Low-voltage complete set of reactive power compensation device

GB/T 16935.1-2008 Insulation coordination of equipment in low-voltage systems Part 1: Principles, requirements and tests

GB/T 17626.2-2006 Electromagnetic compatibility test and measurement technology Electrostatic discharge immunity test

GB/T 17626.3-2016 Electromagnetic compatibility test and measurement technology Radio frequency magnetic field radiation immunity test

GB/T 17626.4-2008 Electromagnetic compatibility test and measurement technology Electrical fast transient pulse group immunity test

GB/T 17626.5-2008 Electromagnetic compatibility test and measurement technology surge (impact) immunity test

GB/T 17626.12-2013 Electromagnetic compatibility test and measurement technology Ring wave immunity test

GB/T 17702 Power Electronic Capacitor

GB/T 20840.1 Transformer Part 1: General Technical Requirements

GB/T 20840.2 Transformers Part 2: Supplementary technical requirements for current transformers

GB/T 20840.3 Transformer Part 3: Supplementary Technical Requirements for Voltage Transformer

JB/T 6319 Basic technical requirements for resistors

3 Terms and definitions

The following terms and definitions apply to this standard.

3.1 Power supply region

(One) The power supply range or area of the transformer.

3.2 Three-phase current unbalance rate

In a three-phase AC circuit, take the absolute maximum value of the difference between the effective value of the three-phase current and its arithmetic average value, and the ratio to the average value in percentage Number representation. The following formula applies to three-phase three-wire and three-phase four-wire. In three-phase four-wire, there is no need to calculate the neutral current.

3.3 Electronic power conversion

[Electricity] [Electronics] Converter (electronics) (power) conversion.

Commutation With the help of electronic valve devices, one or more characteristics of the power system are changed, and there is basically no considerable loss.

Note: For example, the characteristics are voltage, phase number, and frequency (including zero frequency). [GB/T 2900.33-2004, definition 551-11-02]

3.4 Electronic power converter

[Power] [Electronics] Converter (electronics) (power) converter.

Inverter An operating unit consisting of one or more valve devices, transformer/filter (if necessary) and auxiliary equipment (if any).

Note: The English term "converter" is spelled "converter" and "convertor", both of which are correct. This standard uses "converter". [GB/T 2900.33-2004, definition 551-12-01]

3.5 Rated voltage

The nominal voltage of the device to be connected to the grid.

3.6 Rated current

Under rated conditions, the effective value of the allowable power frequency current when the device works continuously for a long time.

Note: Rewrite DL/T 1216-2013, definition 3.7.

3.7 Rated capacity

Under rated conditions, the reactive power output when the device is running at rated current, in kilovar (kvar).

3.8 No-load operation state

After precharging and pulse width modulation, the DC bus voltage is maintained at a given value, and the device does not output compensation current.

3.9 Rated loss

Under rated voltage, when the device output is rated current, the active power measured at its input.

3.10 Control range

The maximum variation range of the controllable output electrical quantity provided by the device at the connection point of the device and the AC system. [DL/T 1193-2012, definition 3.5.2]

3.11 Step response time

When the step control signal is input, the time it takes for the output electrical quantity of the device to reach 90% of the target value from 0 to the target value, and there is no Overshoot. see picture 1. [DL/T 1193-2012, definition 3.5.14]

4 Model naming

The model of the device is composed of five parts. category code, design serial number, rated capacity, rated voltage, and characteristic code. Its specific name The method is shown in Figure 2.

5 Conditions of use

5.1 Normal use conditions

5.1.1 Ambient air temperature

The ambient air temperature should not exceed +40 °C, and its average temperature within 24 h should not exceed +35 °C;

5.1.2 Relative humidity

The ambient air temperature is 30 °C, and the relative humidity is not more than 93%.

5.1.3 Contamination level

The pollution degree does not exceed the c level.

5.1.4 Altitude

The altitude is 2000 m and below.

5.1.5 Anti-seismic level

The horizontal acceleration is not more than 2 m/s²; the vertical acceleration is not more than 1 m/s².

5.1.6 Wind speed

The maximum wind speed at 10 m above the ground does not exceed 35 m/s.

5.1.7 Installation site conditions

The installation site should be free of severe mechanical vibration and impact, no media that can cause fire and explosion hazards, and no corrosion or damage in the surrounding media The gas and conductive medium of the insulation and surface coating layer should be free of harmful gas and steam, and no serious molds are allowed.

The device should not be exposed to strong electric and magnetic fields.

See Appendix B for the electrical conditions of the grid connection points.

5.2 Special conditions of use

If it is used under special conditions that do not comply with 5.1, a special agreement should be signed between the manufacturer and the purchaser.

6 Technical requirements for basic circuits and components

6.1 Basic circuit

The device is mainly composed of grid-connected switch, lightning arrester, charging resistor, bypass switch, filter unit (connected inductance), converter bridge, DC capacitor It consists of a cooling device, a cooling fan, a control and monitoring system and other equipment. The basic circuit diagram is shown in Figure 3.

Note: The inverter unit is in the dotted frame.

6.2 Technical requirements for component equipment

6.2.1 Grid-connected switch (circuit breaker)

Technical requirements include.

a) Should meet the requirements of GB/T 14048.2;

b) It should have the maximum output current of the switching device and the ability to break short-circuit current;

6.2.2 Lightning arrester

Technical requirements include.

a) The incoming line lightning arrester should use gapless metal oxide arrester;

b) The rated voltage should be the upper limit of the normal operating line voltage with a certain margin;

c) The flow capacity of the arrester should be verified to ensure safe operation;

d) Should meet the requirements of GB/T 11032.

6.2.3 Charging resistance

Technical requirements include.

a) It should be able to limit the charging current of the DC capacitor under the design value when the device is put into use;

b) It should be able to withstand the maximum impact power without any thermal and/or mechanical damage;

c) Should meet the requirements of JB/T 6319.

6.2.4 Bypass switch
6.2.5 Filter unit (connect inductance)

Technical requirements include.

a) The filter unit should be able to limit the high frequency harmonic current below the allowable value;

b) The fundamental reactive power generated by the filter capacitor should not exceed the allowable value;

c) The reactor should meet the requirements of GB/T 1094.6 and GB/T 14860.1;

d) The capacitor should meet the requirements of GB/T 17702. Refer to Appendix C.2 for filter unit parameter selection

6.2.6 Converter bridge

The converter bridge should be designed according to the system operating conditions and performance requirements, including.

a) The converter bridge should be able to withstand the impact of overvoltage and overcurrent caused by system faults and switching operations;

b) When designing the converter bridge, full consideration should be given to reducing the possible adverse effects of the distributed parameters of power electronic devices, and appropriate margins should be considered. degree;

c) The converter bridge should have the ability to prevent false triggering or tolerate false triggering;

d) Should meet the requirements of GB/T 3859.1.

6.2.7 DC capacitor

Technical requirements include.

a) It should be able to meet the requirements of device capacity;

b) It should be able to limit the DC voltage fluctuation range within the allowable value;

c) Should meet the requirements of GB/T 17702.

Refer to Appendix C.3 for parameter selection of DC capacitor bank

6.2.8 Cooling fan

The cooling fan should have sufficient heat dissipation capacity, and the protection level of the device, the influence of the installation location, and the cooling of the inverter unit should be considered. But the way matches.

6.2.9 Control and monitoring system

Technical requirements include.

a) The control function can include the following options.

1) Compensation for three-phase unbalanced current;

2) Compensation of reactive current;

3) Compensation of harmonic currents;

4) Comprehensive compensation.

b) The monitoring system should have fault protection function;

c) The device should be equipped with a wireless communication module, which can realize information interaction and remote control with mobile terminals;

d) The device should be able to ensure that data will not be lost after power failure;

e) The device should have the necessary logic interlock function to prevent misoperation.

6.2.10 Other equipment requirements

Other equipment (such as isolation switches, fuses, current transformers, voltage transformers, etc.) refer to the requirements of the corresponding national standards, such as.

a) Refer to GB/T 14048.3 for isolating switch;

b) Refer to GB/T 13539.1 for fuses;

c) Refer to GB/T 20840.1 and GB/T 20840.2 for current transformers, and outdoor opening and closing equipment should be adopted;

d) Refer to GB/T 20840.1 and GB/T 20840.3 for voltage transformer.

7 Technical requirements

7.1 Appearance and structure

The device structure and external dimensions are reasonable in design, suitable for single-pole or double-pole fixing, which is convenient for installation, inspection and maintenance.

The device shell should be made of 2 mm thick stainless steel plate, which should be able to withstand the electric power and thermal stress that may be generated when the device is short-circuited. Meet the mechanical strength requirements during handling, installation and operation.

The device should be equipped with lifting lugs for carrying, and equipped with locks to prevent rain, door shafts to prevent rust, and to prevent scratches and water ingress.

The welded parts of the device should be welded firmly, and the welds should be uniform and beautiful, without weld penetration, cracks, undercuts, residues, pores, etc.

There should be no rust or other mechanical damage on the surface of all metal parts of the device, and there should be a reliable anti-corrosion layer.

The door of the device should be able to open and close flexibly within an angle of not less than 90°.

The nameplate parameters are clearly marked and the data is correct.

7.2 Selection and installation of components and accessories

All independent electrical components and accessories installed in the device shall comply with 6.2 of this standard and the relevant standards of components, and shall be in accordance with the manufacturer's instructions. The book is installed.

The arrangement of electrical components should be neat, correct, easy to install, wire, repair and replace.

Components that need to be operated, adjusted and reset inside the device should be easy to operate.

The colors of the indicator lights and buttons selected in the device should meet the requirements of GB/T 4025.

The phase sequence arrangement of the busbar is viewed from the front of the device, and the phase sequence identification and arrangement should generally meet the requirements of Table 2.

The long-term allowable current of the main circuit bus should not be less than 1.5 times the rated current; the connection of the bus should be firm and should not shake freely, and the wiring should be Neat and beautiful; the rated voltage of the bus bar shall not be lower than the rated working voltage of the corresponding circuit; the auxiliary circuit wire should have a cross-sectional area not less than 1.5 mm² The copper core multi-strand insulated wire; the cross-sectional area of the wire of the current measurement loop should not be less than 2.5 mm², and the wire should be connected by cold crimping end.

The bus bars and insulated wires in the device should have an insulation level compatible with the rated working voltage.

The material, connection and arrangement method of the bus bar and the insulating support should have the electric power and thermal stress that may be generated when the device is short-circuited. Power capacity.

7.3 Safety and protection

7.3.1 Degree of protection

The protection level of the device shell shall not be lower than IP43.

7.3.2 Safety signs

The device should clearly define relevant warning signs and symbols in accordance with the requirements of GB 2894 and its components.

7.3.3 Protection and grounding

The protection against direct contact can rely on the structural measures of the device itself, or on the additional measures taken during the installation of the device. The manufacturer shall provide relevant information in the installation manual.

The protection of indirect contact should be made by the protective circuit in the device. The protective circuit can be realized by installing a protective conductor separately, or it can be used The structural components of the device (such as housing, frame) are implemented.

Metal shells that are in direct contact, metal parts that may be charged, and metal bases of electrical components that require grounding (including possible insulation damage There should be a reliable electrical connection between the door, board, bracket and the main ground, which can be electrically connected to the main ground.

The resistance value between the points should not be greater than 0.1 ohm.

All components of the protection circuit in the device should be able to withstand the maximum thermal stress and electrical stress that the device may encounter at the installation site.

The color of the protective conductor should be yellow-green, and yellow-green should not be used for other purposes except as the identification color of the protective conductor.

The diameter of the grounding terminal shall not be less than phi 10 mm, and shall be clearly marked.

The DC side of the device should be equipped with a discharge resistor. After the power is cut off, the DC side capacitor should drop to a safe voltage within the specified time. The capacitor is not discharged Before contact will cause danger, warning signs or safety instructions should be installed.

The cross-sectional area of the protective conductor (PE) should not be less than the value given in Table 2. When the neutral conductor (N) current does not exceed 30% of the phase current, the table 2 It can also be used to protect neutral conductors (PEN). The minimum cross-sectional area of copper PEN conductors should be 10 mm².

Note: If the wire selected according to Table 2 is not a standard size, the closest protective conductor with a larger standard cross-sectional area should be used. When phase conductor and protective conductor When the materials are different, corrections should be made to achieve the conductive effect of the same material. The minimum cross-sectional area of the protective conductor should not be less than 2.5 mm².

7.4 Clearance and creepage distance

The electrical clearance and creepage distance of each component in the device should meet the requirements of the respective standards.

Under normal conditions of use, the electrical gaps between exposed live objects of different polarities or phases in the device and between them and the housing and ground The creepage distance shall not be less than that specified in Table 3.

7.5 Insulation level of the device

7.5.1 Insulation resistance verification

Use insulation measuring instruments with a voltage not less than 500 V to measure insulation resistance.

The insulation resistance between live parts, between live parts and bare conductive parts, and between live parts and the ground shall not be less than the power frequency withstand voltage value × 103 ohm.

7.5.2 Power frequency withstand test voltage

The main circuit and the auxiliary circuit directly connected to the main circuit should be able to withstand the power frequency withstand test voltage specified in Table 5.

7.6 Protection and alarm function

7.6.1 Protection function

The device should generally have the following protection functions.

1) DC side over-voltage and under-voltage protection, output should be blocked during operation; […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 25 pages — is available in the English PDF.

Referenced standards

Normative references

GB/T 7947 · GB/T 20840.2 · GB/T 20840.3

Similar standards

How to Download NB/T 10327-2019

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included