GB/T 25387.1-2021Wind turbines generator system—Full-power converter—Part 1:Technical condition (English PDF)
风力发电机组 全功率变流器 第1部分:技术条件
This is a limited preview
Buy now to download the full PDF (33 pages)
Need quotation for your management?
Get a formal quotation for GB/T 25387.1-2021 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
March 9, 2021
Implementation date
October 1, 2021
Scope
GB/T 25387.1-2021 is the English-translated version of 风力发电机组 全功率变流器 第1部分:技术条件.
GB/T 25387.1-2021 is the first part of the Chinese standard on the full-power converter of a wind turbine generator system, and it gives the technical conditions.
It sets the terms and definitions, the general requirements - the electrical performance and efficiency, the grid behaviour and fault ride-through, the protections, the cooling, the insulation and the environmental conditions - the inspection rules and the product information to be supplied.
It applies to the full-power AC-DC-AC voltage source converters of wind turbines. Converter makers, turbine manufacturers and wind farm owners use it. It replaces GB/T 25387.1-2010, was issued on 9 March 2021 and has applied since 1 October 2021.
Found what you need?
Document preview — GB/T 25387.1-2021
National Standard of the People's Republic of China
- ICS
- 27.180
- Classification
- F 11
- Replacing
- GB/T 25387.1-2010
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- 1 Scope7
- 2 Normative References7
- 3 Terms and Definitions8
- 4 General Requirements12
- 5 Test Methods28
- 6 Inspection Rules28
- 7 Marking, Packaging, Storage and Transportation30
- Appendix A (informative) Topological Structures of Commonly Used Full-power AC- DC-AC Voltage-type Converter33
1 Scope
This Part of GB/T 25387 specifies the terms and definitions, general requirements, inspection rules and product-related information of full-power AC-DC-AC voltage-type converters for wind turbines generator system.
This Part is applicable to the full-power AC-DC-AC voltage-type converters for wind turbines generator system (hereinafter referred to as "the converters").
2 Normative References
The following documents are indispensable to the application of this document. In terms of references with a specified date, only versions with a specified date are applicable to this document. In terms of references without a specified date, the latest version (including all the modifications) is applicable to this document.
GB/T 191 Packaging - Pictorial Markings for Handling of Goods
GB/T 2423.56 Environmental Testing - Part 2: Test Methods - Test Fh. Vibration, Broadband Random and Guidance
GB/T 2900.53 Electrotechnical Terminology - Wind Turbine Generator Systems
GB/T 3797 Electrical Control Assemblies
GB/T 3859.1 Semiconductor Converters - General Requirements and Line Commutated Converters - Part 1-1.Specification of Basic Requirements
GB/T 3859.2-2013 Semiconductor Converters- General Requirements and Line Commutated Converters - Part 1-2.Application Guide
GB/T 4208-2017 Degrees of Protection Provided by Enclosure (IP code)
3 Terms and Definitions
What is defined in GB/T 3859.1 and GB/T 2900.53, and the following terms and definitions are applicable to this document.
3.1 Generator-side converter
A conversion unit that converts the AC electricity of the voltage, current amplitude and frequency change output by the wind turbines into DC electricity.
3.2 Grid-side converter
A conversion unit that converts the DC electricity output by the generator-side converter into AC electricity that satisfies the requirements of the power grid, and feeds back to the power grid.
3.10 Grid-side rated voltage
The root mean square value of the fundamental wave of the conductor line voltage between the low-voltage side of the boosting transformer adapted to the wind turbine and the grid-side converter.
3.11 Grid-side operating voltage range
The grid-side voltage variation interval corresponding to the continuous operation of the grid-side converter.
3.12 Grid-side rated current
The root mean square value of the fundamental wave current output by the grid-side converter under the operating conditions of the lower limit of the voltage operating range of the grid-side converter, the rated power and the unity power factor of the grid-side converter.
3.20 DC current content
Within a grid electrical cycle, in the current fed into the grid by the converter, the average DC current as a percentage of the root mean value of the current.
3.21 DC voltage ripple coefficient
The ratio of the effective value of AC harmonic component in the DC voltage to the average value of the DC voltage.
3.22 Efficiency of converter
Under the operating conditions of the grid-side rated voltage, grid-side rated frequency and unity power factor of the grid-side converter, the ratio of the output active power of the grid-side converter to the input active power of the generator-side converter, expressed as a percentage.
3.23 Function of fault recorder
When a fault occurs in the converter, the converter has the function of automatically storing the waveform at the time of the fault.
4 General Requirements
4.1 Requirements for Conditions of Use
4.1.1 Environmental conditions of normal operation
The environmental conditions of the operation of the converter shall comply with the stipulations of GB/T 4798.3. The requirements are as follows.
4.1.2 Electrical conditions
4.1.2.1 Grid-side frequency range
When the frequency deviation of the power grid is within the range of -2.5 Hz ~ +2.5 Hz of the rated frequency, the converter shall be able to normally operate.
4.1.2.2 Grid voltage range
When the voltage deviation of the low-voltage side grid of the boosting transformer connected to the grid-side converter is within the range of -10% ~ +10%, the converter shall be able to operate continuously and normally.
4.2 Cabinets and Components
4.2.1 Cabinet design requirements
The cabinet design shall satisfy the following requirements. and surface, and shall comply with the stipulations of GB/T 3797.
4.2.2 Component requirements
The components shall satisfy the following requirements. phenomenon of loosening or state changes after vibration.
4.2.3 Electrical connection requirements
4.2.3.1 The correctness of each electrical connection shall be ensured. Auxiliary devices, such as. relays, contactors, micro circuit breakers and electronic components, shall be confirmed to be qualified before the assembly.
4.2.3.2 The laying and connection of cables and wires shall comply with the stipulations of GB/T 5226.1.
4.3 Performance Indicators
4.3.1 Converter efficiency
Under the operating conditions of the grid-side rated voltage, grid-side rated frequency, grid-side rated power and grid-side unity power factor, the converter efficiency shall not be lower than 97%.
4.3.2 Grid-side power factor
The converter shall be equipped with the control function that enables the grid-side power factor to be adjustable between the capacitive 0.95 and the inductive 0.95.
4.3.7 Generator-side voltage change rate (dU/dt)
In accordance with the actual application conditions of the converter (for example, the cable length at the installation site) and the maximum stress that the generator turns can withstand, design the size of the dU/dt suppression filter of the converter. When the converter operates in the wind turbine, the change rate of the generator-side converter output line voltage and the phase-to-ground voltage shall satisfy dU/dt <= 1,000 V/µs.
5 Test Methods
The test methods shall comply with GB/T 25387.2.
6 Inspection Rules
6.1 Type Test
6.1.1 Test requirements
Type test is a test that comprehensively assesses product performance and quality, and verifies whether the product complies with the technical requirements. When one of the following circumstances occurs, type test shall be carried out.
6.1.2 Sampling method
The samples for type test shall be sampled from a batch of products that have passed the exit-factory test, and the number of samples shall be no less than two.
6.1.3 Determination rules
The type test items shall comply with the technical stipulations of the product. If all the items are qualified, the product shall be determined as qualified; if any item is disqualified, then, the product shall be determined as disqualified.
6.2 Exit-factory Test
In order to evaluate the product performance and ensure that the product complies with the relevant requirements of relevant standards and type test, the assembled converter shall undergo exit-factory test.
7 Marking, Packaging, Storage and Transportation
7.1 Marking
7.1.1 Product marking
The converter shall have a nameplate at an appropriate location. The content of the nameplate is as follows.
7.1.2 Packaging marking
On the outer packaging of the converter, there are markings of receipt and delivery, packaging, storage and transportation, as well as safety warning, which shall comply with the relevant stipulations of GB/T 191 and GB/T 13384.
7.3 Storage
7.3.1 The climatic conditions shall satisfy the following requirements.
7.3.2 Specific storage hazards shall satisfy the following requirements.
7.4 Transportation
7.4.1 The climatic conditions shall satisfy the following requirements.
7.4.2 The equipment shall be packaged with part of the packaging box of the supplier. During transportation, there shall be no violent vibration or impact, and the product shall not be tilted or inverted.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 33 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 191Graphical symbols marking for handling and storage of packages
- GB/T 2423.56Environmental testing - Part 2: Test methods - Test Fh: Vibration, broadband random and guidance
- GB/T 2900.53Electrotechnical terminology -- Wind turbine generator systems
- GB/T 3797Electrical control assemblies
- GB/T 3859.1Semiconductor converters -- General requirements and line commutated Converters -- Part 1-1: Specification of basic requirements
- GB/T 3859.2-2013Semiconductor converters -- General requirements and line commutated converters -- Part 1-2: Application guide
Cited by
- GB/T 32077-2025Wind energy generation systems - Pitch system of wind turbines
- GB/T 34524-2025Wind energy generation systems - Main shaft of wind turbines
- GB/T 45854-2025Wind energy generation systems - Hydraulic system of wind turbines
- GB/T 44360-2024Wind energy generation systems - Technical specification for data acquisition of smart wind farm
- GB/T 44908-2024Safety requirements and evaluation methods for technical transformation of wind farm
- GB/T 42600-2023Wind energy generation systems - Tower and foundation design requirements of wind turbines
Similar standards
Editions of GB/T 25387.1
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 25387.1-2021 | Wind turbines generator system—Full-power converter—Part 1:Technical condition | current edition | Current |
| GB/T 25387.1-2010 | Wind turbines generator system—Full-power converter—Part 1:Technical condition | previous edition | Superseded |
This page sells the current edition, GB/T 25387.1-2021. Earlier editions are listed for reference only.
How to Download GB/T 25387.1-2021
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 191-2025 — Graphical symbols marking for handling and storage of packages
GB/T 1910-2015 — Newsprint
GB/T 19100-2003 — Terminology work--Establishment of concept system
Secure payment via Stripe
Payments accepted
GB/T 25387.1-2021
$390.00