GB/T 1985-2023High-voltage alternating current disconnectors and earthing switches (English PDF)

高压交流隔离开关和接地开关

Open the GB/T 1985-2023 preview as PDF

Preview — first pages of GB/T 1985-2023 (full document: 85 pages)

This is a limited preview

Buy now to download the full PDF (85 pages)

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

September 7, 2023

Implementation date

April 1, 2024

Scope

GB/T 1985-2023 is the English-translated version of 高压交流隔离开关和接地开关.

GB/T 1985-2023 sets out what a high-voltage alternating current disconnector or earthing switch has to satisfy, from service conditions through to the rules that follow it into the field. It covers alternating current disconnectors and earthing switches designed for indoor or outdoor installation and operating at 50 Hz or below in systems of nominal voltage 3 kV and above, together with their operating mechanisms and auxiliary equipment; switching devices that carry an isolating or earthing function alongside another one, such as high-speed earthing switches, circuit-breakers and switches, fall within it too, while disconnectors and earthing switches built into metal-enclosed assemblies are covered in addition by GB/T 3906-2020 and GB/T 7674-2020. The document fixes normal and special service conditions, ratings, and design and construction requirements, then describes the type tests and the routine tests, one clause each, and closes with a selection guide, the information to be exchanged with enquiries, tenders and orders, rules for transport, storage, installation, operation and maintenance, safety, and the influence of the product on the environment. It is a modified adoption of IEC 62271-102:2022 and replaces GB/T 1985-2014.

Document preview — GB/T 1985-2023

National Standard of the People's Republic of China

ICS
29.130.10
Classification
K 43
Replacing
GB/T 1985-2014

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • 1 Scope1
  • 2 Normative references1
  • 3 Terms and definitions1
  • 3.1 General terms and definitions2
  • 3.2 Assemblies of switchgear and controlgear2
  • 3.3 Parts of assemblies2
  • 3.4 Switching devices2
  • 3.5 Parts of switching devices3
  • 3.6 Operation5
  • 3.7 Characteristic quantities7
  • 4 Normal and special service conditions10
  • 5 Ratings10
  • 6 Design and construction18
  • 7 Type tests24
  • 8 Routine tests63
  • 9 Guide to the selection of disconnectors and earthing switches65
  • 10 Information to be given with enquiries, tenders and orders (informative)67
  • 11 Rules for transport, storage, installation, operation and maintenance70
  • 12 Safety70
  • 13 Influence of the product on the environment71
  • Annex A (informative) Cross-reference of clause numbering between this document and IEC 62271-102:202272
  • Annex B (informative) Technical deviations between this document and IEC 62271-102:2022 and their reasons74
  • Annex C (informative) Rated insulation level of disconnectors used for earthing the neutral point of power transformers77
  • Annex D (informative) Making and breaking current capability required of disconnectors and earthing switches78
  • Annex E (normative) Tolerances on the test quantities of type tests80
  • Annex F (informative) Extension of the validity of type tests81
  • Annex G (informative) Test voltage for the most unfavourable insulation position, that is the minimum transient electrical clearance, during earthing switch operation82
  • Annex H (normative) Alternative test method for the short-circuit making current test83
  • Bibliography85

1 Scope

The document lays down the normal and special service conditions, the rated values and the design and construction requirements for high-voltage alternating current disconnectors and earthing switches; it describes the corresponding type test and routine test methods, provides a guide to selection, and sets rules for transport, storage, installation, operation and maintenance.

It applies to alternating current disconnectors and earthing switches designed for installation indoors and outdoors and operating at a frequency of 50 Hz and below in systems of nominal voltage 3 kV and above.

It applies as well to the operating mechanisms of those disconnectors and earthing switches and to their auxiliary equipment.

The additional requirements for disconnectors and earthing switches inside metal-enclosed switchgear and controlgear are given in GB/T 3906-2020 and GB/T 7674-2020.

It also applies to switching devices which, besides other functions, have an isolating and/or an earthing function, such as high-speed earthing switches, circuit-breakers and switches.

2 Normative references

The clause states that the contents of the documents listed become indispensable provisions of this document through the normative references made in the text; for dated references only the edition corresponding to that date applies, while for undated references the latest edition, including all amendments, applies.

The documents cited are GB/T 311.1-2012, GB/T 1804-2000, GB/T 1984-2014, GB/T 2900.19-2022, GB/T 2900.20-2016, GB/T 2900.57-2008, GB/T 2900.83-2008, GB/T 3906-2020, GB/T 4208-2017, GB/T 4473-2018, GB/T 7674-2020, GB/T 11022-2020, GB/T 20138-2006 and IEC/TR 62271-305.

3 Terms and definitions

The terms and definitions given in GB/T 2900.19-2022, GB/T 2900.20-2016, GB/T 2900.57-2008, GB/T 2900.83-2008 and GB/T 11022-2020, together with those that follow, apply to this document.

3.1 General terms and definitions

3.1.101 Indoor switchgear and controlgear: switchgear and controlgear that cannot withstand the action of wind, rain, snow, abnormal pollution, ice and heavy frost, and that is suitable for installation inside a building or a shelter. [SOURCE: GB/T 2900.20-2016, 3.4, modified]

3.1.102 Outdoor switchgear and controlgear: switchgear and controlgear able to withstand the action of wind, rain, snow, pollution, condensation, ice and heavy frost, and suitable for installation in the open air. [SOURCE: GB/T 2900.20-2016, 3.5]

3.1.103 User: the individual or the legal entity that uses the disconnector or the earthing switch. A note adds that the user may be the purchaser of the disconnector or earthing switch, an electricity supplier for instance, and may also be a contracting company, the personnel responsible for installation, maintenance or operation, other personnel temporarily or permanently responsible for the disconnector, the earthing switch or the substation, and the operating personnel of the switchgear.

3.2 Assemblies of switchgear and controlgear

3.2.1 Test object: the equipment representative of the switchgear and controlgear on which a given type test is carried out. [SOURCE: GB/T 11022-2020, 3.2.1]

3.4 Switching devices

3.4.101 Disconnector: a switching device which, in the open position, shows between its contacts an insulating distance meeting the specified requirements together with a visible indication of the open state, and which, in the closed position, can carry the current under normal circuit conditions and the current under specified abnormal conditions, a short circuit for instance, for a specified time. A first note explains that the disconnector has the ability to open and close a circuit when the circuit current is negligible or when there is no appreciable change of voltage across the two line terminals of each pole before and after the operation. A second note explains what a negligible current means, giving the capacitive current of bushings, busbars, connections, very short cables, the current of the permanently connected grading impedance of circuit-breakers and the current of voltage transformers and dividers, with a reference to IEC/TR 62271-305; for rated voltages of 363 kV and below, a current not exceeding 0.5 A is a negligible current, while for rated voltages above 363 kV with a current exceeding 0.5 A the manufacturer is to be consulted; the same note explains that no appreciable change of voltage refers to applications such as bypassing induction voltage regulators or circuit-breakers, and busbar transfer. [SOURCE: GB/T 2900.20-2016, 6.5, modified]

3.4.102 Single-column disconnector: a disconnector in which the fixed contact of each pole is suspended from the busbar or from a separate support, the moving contact of each pole is carried by a separate base or frame, and the direction of the isolating gap is perpendicular to the plane of the base. A note gives the pantograph disconnector and the semi-pantograph disconnector as typical examples.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 85 pages — is available in the English PDF.

Referenced standards

Editions of GB/T 1985

EditionTitleRevisionStatus
GB/T 1985-2023High-voltage alternating current disconnectors and earthing switchescurrent editionCurrent
GB/T 1985-2014High-voltage alternating current disconnectors and earthing switchesprevious editionIn force until 2024-04-01

This page sells the current edition, GB/T 1985-2023. Earlier editions are listed for reference only.

How to Buy GB/T 1985-2023

  1. 1Add to cart. Click the "Buy GB/T 1985-2023" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
85 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 1985-2023

$1,265.00

$1,075.00for partners