GB 50072-2021 — This standard is applicable to the newly-built, expanded, reconstructed food cold store, which adopts the subcritical vapor compression direct refrigeration systems using ammonia, halogenated hydrocarbons and their mixtures, carbon dioxide as refrigerants, AND the indirect refrigeration systems using carbon dioxide, brine, etc. as refrigerating medium. 1.0.3 The cold store design shall be safe and reliable, energy-saving, environmentally friendly, economically reasonable, advanced and applicable.
Document preview — GB 50072-2021
National Standard of the People's Republic of China
Issued by: MOHURD
Contents
- Foreword6
- 1 General provisions8
- 2 Terms9
- 3 Basic requirements12
- 4 Architecture15
- 5 Structure33
- 6 Refrigeration41
- 7 Electric65
- 8 Water supply and drainage72
- 9 Heating, ventilating, air-conditioning and floor anti-freezing79
- Appendix A The calculation of ground frost-proof heating load and air supply volume of mechanical ventilation in heating region84
- Explanation of wording in this standard89
- List of quoted standards90
1 General provisions
1.0.1 This standard is formulated, in order to standardize and integrate the
technical requirements for design of cold store, guide the design of cold store, meet food refrigeration technology and hygiene requirements, achieve the goals of economical and reasonable, energy-saving, environmentally friendly, safe and reliable.
1.0.2 This standard is applicable to the newly-built, expanded, reconstructed
food cold store, which adopts the subcritical vapor compression direct refrigeration systems using ammonia, halogenated hydrocarbons and their mixtures, carbon dioxide as refrigerants, AND the indirect refrigeration systems using carbon dioxide, brine, etc. as refrigerating medium.
1.0.3 The cold store design shall be safe and reliable, energy-saving, environmentally friendly, economically reasonable, advanced and applicable.
1.0.4 The cold store design shall not only meet the requirements of this
standard, BUT also meet the requirements of relevant national standards.
2 Terms
2.0.1 Cold store
Storage buildings, which adopt artificial refrigeration AND have cold insulation functions, including storehouse, refrigerating machine rooms, power distribution rooms, etc.
2.0.2 Assembly cold store
The cold store, which adopts light-weight composite sandwich panels, such as metal surface insulation sandwich panels, as thermal insulation and envelope structures, AND is assembled on-site.
2.0.4 High rack cold store
The rack cold store, which has a rack height of more than 7 m AND adopts mechanized or automated control.
2.0.5 Storehouse
The main body of the cold store building and its supporting stairwells, elevator rooms, anteroom, other auxiliary rooms.
2.0.6 Anteroom
The passages, which are set up for the entry and exit of goods in the cold storage room, ice storage room, chilling room. It is divided into the temperature-controlled anteroom, which has artificial refrigeration and temperature reduction, AND non-temperature controlled anteroom, which has no artificial refrigeration and cooling.
2.0.9 Chilling room
The room, where the product is cooled.
2.0.10 Freezing room
The room, where the product is frozen.
2.0.11 Cold storage room
A room, which is used to store cold processed products.
2.0.12 Chilled food storage room
A room, which is used to store goods, at a temperature higher than freezing point AND lower than normal temperature.
3 Basic requirements
3.0.1 The design scale of the cold store shall be calculated, based on the
nominal volume of the cold storage room or ice storage room. Those which has a nominal volume greater than 20000 m3 shall be large-scale cold store. Those which has a nominal volume of 5000 m3 ~ 20000 m3 shall be medium-sized cold store.
3.0.2 The calculated capacity of the cold store, for directly stacking cold storage
items, can be calculated as follows.
3.0.7 The design temperature and relative humidity of the cold room shall be
determined, according to the cold storage process requirements of various foods.
3.0.9 The minimum spacing, between rooms using ammonia refrigeration
system, ammonia refrigeration equipment and pipes installed outdoors and civil buildings outside the plant area, shall not be less than 150 m.
4 Architecture
4.1 Site selection and general layout
4.1.1 The site selection of the cold store shall meet the following requirements.
4.1.2 The general layout of the cold store shall meet the following requirements.
4.1.3 The general layout of the cold store shall be a combination of short-term
and long-term, focusing on the short-term. Resources such as storehouse land, railway dedicated lines, water transport wharf, equipment pipelines, roads, carriage return yards, shall be planned as a whole, reasonably arranged, taking into account the needs of future expansion.
4.1.4 The vertical design of the general plan of the cold store shall meet the
following requirements.
4.1.5 The main roads in the storehouse area shall be paved with concrete or
asphalt pavements, which are suitable for vehicles.
4.1.8 When the storehouse covers an area larger than 1500 m2, fire lanes shall
be set, at least along the two long sides of the storehouse.
4.2.3 The partition wall, between the cold storage room and the anteroom or
closed platform, shall be a fire partition wall. The fire resistance rating of the fire partition wall shall not be less than 3.00 h.
4.2.4 When the assembly cold store is not equipped with the fire partition
wall, which is specified in clause 4.2.3 of this standard, the fire resistance grade, number of layers, area shall meet the requirements of Table 4.2.4.
4.6 Refrigerating machine room, electric substation and
control room
4.6.1 The refrigerating machine room, electric substation and control room shall
meet the following requirements.
4.6.2 In addition to the requirements of clause 4.6.1 of this standard, the
ammonia refrigerating machine room shall also meet the following requirements.
4.6.3 The ammonia refrigerating machine room shall have at least one long side
of the building, which is not adjacent to other buildings. It shall have external doors and windows, which can meet natural ventilation.
5 Structure
5.1 General requirements
5.1.1 The cold room should adopt a reinforced concrete structure or a steel
structure. When it is a small cold room, the cold room may also adopt a masonry structure.
5.1.2 The design service life and safety grade of the cold store's structure shall
comply with the relevant provisions of the current national standard "Unified standard reliability design of building structures" GB 50068.
5.1.5 When a reinforced concrete structure is adopted for the cold room, the
maximum spacing between expansion joints should not be greater than 50 m.
Where there is sufficient basis or reliable measures, the maximum spacing of expansion joints can be appropriately increased.
5.1.7 When the cold room's attic roof adopts cast-in-place reinforced concrete
floor AND the distance, between the center lines of the opposite side columns, is greater than or equal to 30 m, the top of the side column and the roof beam should be hinged.
5.3.8 The load-bearing wall brick masonry of rooms, which is not higher than
0 °C, such as frozen food storage room, freezing room, ice storage room, shall use the sintered ordinary bricks, which have a strength grade of not lower than MU20.
5.4 Protection and coating
6 Refrigeration
6.1 General requirements
6.2 Load calculation
6.2.1 The load calculation shall include the cooling equipment load of the cold
room AND the mechanical load of the refrigeration system. It should adopt the steady-state calculation method, which is corrected hourly or by engineering factors.
6.2.4 The heat flow calculation of the cold room's envelope structure shall meet
the following requirements.
6.2.5 The heat flow of goods, in the cold room, shall include the heat flow of
food, the heat flow of food packaging materials and transport vehicles, the heat flow of breathing when food is cooled, the heat flow of breathing when food is refrigerated. The calculation shall meet the following requirements.
6.5 Refrigeration piping
6.5.1 The design of the refrigeration piping system shall comply with the
relevant requirements of the current national standards "Design code for industrial metallic piping" GB 50316, "Pressure piping code - Industrial piping"
GB/T 20801, "Pressure pipe safety technology supervision regulation for industrial pressure pipe" TSG D0001.
7 Electric
7.1 Electric power supply
7.1.1 The cold store, which will cause greater economic losses, if the power
supply is interrupted, shall be powered by the grade 2 load. The cold store, which will not cause greater economic losses, if the power supply is interrupted, can be powered by the grade 3 load. The cold store for national reserve shall be powered by according to the grade 2 load.
7.2 Refrigerating machine room
7.2.1 A control room shall be set up, in the ammonia refrigerating machine room.
Refrigeration compressor units, refrigerant pumps, condenser water pumps and fans, other refrigeration equipment control boxes (cabinets), machine room's exhaust fan control boxes (cabinets), machine room lighting distribution box, refrigerant leakage indication alarm equipment, shall not be arranged in the ammonia refrigerating machine room. They should be centrally arranged in the control room of the refrigerating machine room.
7.3 Storehouse
7.3.1 The power and lighting distribution and control equipment, in the cold
room, should be arranged in a ventilated and dry place, outside the cold room.
7.3.2 The lighting fixtures, in the cold room, shall be energy-saving lighting
fixtures, which meet the food hygiene and safety requirements and the environmental conditions, of the cold room AND can be quickly lit.
8 Water supply and drainage
8.1 General requirements
8.1.1 When the water supply and drainage pipes pass through the thermal
insulation layer of the cold room, measures shall be taken to prevent cold bridges. The length of the thermal insulation of the pipes, for prevention of cold bridges, inside and outside the insulation layer, should not be less than 1.5 m.
8.2 Water supply
8.2.1 The water source of the cold store shall be nearby urban tap water, groundwater or surface water.
8.2.2 The quality of domestic water for cold store, ice-making raw material water, water added during freezing of aquatic products, shall comply with the relevant requirements of the current national standard "Standards for drinking water quality" GB 5749.
8.2.5 The water temperature of the refrigeration process equipment, in the cold
store, shall be determined, according to the process. Meanwhile it shall meet the following requirements.
8.3 Drainage
8.3.1 There should be drainage facilities, on the floor of cold store's anteroom, refrigerating machine rooms and equipment rooms, chilling rooms with a design temperature of not less than 0 °C. When floor drain is used for drainage, the height of the floor drain's water seal shall not be less than 50 mm. Elevator shafts, ground pound pits and other places, which are easy to accumulate water, shall have drainage and backflow-prevention facilities.
8.3.7 The slope and fullness of the frost flushing (thawing) drainage pipeline
shall comply with the relevant requirements of the current national standard "Standard for design of building water supply and drainage" GB 50015.
8.3.8 The drainage pipe of the cold store's frost flushing water system shall
adopt a metal drain pipe.
8.4.6 The design of the automatic fire extinguishing system, for cold store, shall
meet the following requirements.
9 Heating, ventilating, air-conditioning and floor anti- freezing
9.1 General requirements
9.1.1 The heat source of the heating system shall be determined, by technical
and economic analysis, based on energy conditions, energy prices, energy saving, environmental protection requirements. Meanwhile it shall meet the following requirements.
9.1.2 The cold source of the low-temperature air-conditioning system is
determined, by comprehensive analysis, according to the meteorological conditions and the characteristics of the refrigeration process system.
9.2 Heating and air-conditioning
9.3 Ventilating
9.3.1 The ventilation design of the refrigerating machine room shall meet the
following requirements.
9.4 Floor anti-freezing
9.4.1 The anti-freezing method of the cold room's floor shall be reasonably
selected, according to the requirements of storehouse layout, project cost, operation energy consumption, maintenance and management, etc., after a technical and economic comparison.
9.5 Smoke control
9.5.1 Smoke exhaust facilities shall be provided, for anterooms and closed
platforms, which have a building area greater than or equal to 300 m2.The smoke control facilities of anteroom, closed platforms, stairwells, auxiliary rooms, shall comply with the relevant provisions of the current national standard "Technical standard for smoke management systems in buildings" GB 51251.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Cited by
- GB 35181-2025Rules for major fire potential judgement
- GB/T 28009-2025Code of safety practice for cold store
- GB/T 30134-2025Specification for cold store management
- GB/T 31086-2025Requirements and evaluation indicators for cold chain service capabilities of logistics enterprises
- GB 44015-2024Minmum allowable of energy efficiency and energy efficiency grades for cold store(box) and refrigerant compressor condensing unit
- GB/T 42503-2023Specification for agricultural product cold chain logistics services in producing areas
How to Buy GB 50072-2021
- 1Add to cart. Click the "Buy GB 50072-2021" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 11118-2026 — Hydraulic fluids (L-HL, L-HM, L-HV, L-HS and L-HG type)
GB 11557-2026 — Provisions for protecting drivers from injury by the steering mechanism of motor vehicles
GB 12021.4-2026 — Maximum allowable values of the energy consumption, water consumption and grades for electric washing machines and washer-dryers
Secure payment via Stripe
Payments accepted
GB 50072-2021
$889.00