GB/T 22390.2-2008Control and protection equipment of HVDC transmission systems - Part 2: AC and DC station control equipment (English PDF)
高压直流输电系统控制与保护设备 第2部分:交直流系统站控设备
Open the GB/T 22390.2-2008 preview as PDF
This is a limited preview
Buy now to download the full PDF (18 pages)
Issued by
General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC
Level / Type
National · Recommended
Issue date
September 24, 2008
Implementation date
August 1, 2009
Scope
GB/T 22390.2-2008 is the English-translated version of 高压直流输电系统控制与保护设备 第2部分:交直流系统站控设备.
China's national standard for the AC and DC station control equipment of a high voltage direct current transmission scheme. It is Part 2 of GB/T 22390 and specifies the technical requirements, the test methods, the inspection rules and the supply and documentation requirements for the station control equipment. Station control sits between the operator layer of Part 1 and the pole control of Part 3, and it governs everything in the converter station that is not the conversion itself. On the alternating current side that means the AC switchyard and its switching sequences, the converter transformers and their tap changers, and the filters - which matter more here than anywhere else in a power system, because a line-commutated converter draws heavily distorted current and absorbs a great deal of reactive power. The harmonic filters that absorb the distortion are also the source of the reactive power the converter needs, so the filter banks have to be switched in and out as the transmitted power changes, and getting that wrong causes either a voltage excursion or a harmonic limit violation. Station control does that switching. On the direct current side it governs the switchyard, the earth electrode line, the neutral bus arrangement and the transfer between bipolar, monopolar metallic return and monopolar earth return operation, which is how a link keeps transmitting after losing one pole. It also handles the station auxiliary systems, the cooling plant on which the valves depend, and the coordination with the remote station, since the two ends of an HVDC link operate as one machine and every mode change has to be agreed across the telecommunication link between them. Issued on 24 September 2008 and in force since 1 August 2009.
Document preview — GB/T 22390.2-2008
National Standard of the People's Republic of China
- ICS
- 29.240.01
- Classification
- K 45
Issued by: General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC
Contents
- 1 Scope1
- 2 Normative references1
- 3 Terms and definitions 24
- 5 Test methods 911
- 6 Inspection Rules 7 signs, labels, Owner's Manual 12 8 packaging, transportation and storage 14 9 sets of supply14
- 10 Quality Assurance14
Foreword
According to the 2003 National Science and Technology Science and Technology Platform project focused "DC power transmission system core technology and infrastructure standard Research "(Project No. 2003DIA7J034) requirements formulated standard" HVDC system control and protection equipment. " GB/T 22390 "HVDC system control and protection equipment" is divided into six parts.
--- Part 1. Operator Control System;
--- Part 2. AC and DC station control system equipment;
--- Part 3. DC pole control system equipment;
--- Part 4. DC system protection equipment;
--- Part 5. DC line fault location device;
--- Part 6. Converter Station transient fault recorder. This is Part 2 GB/T 22390 of. This section proposed by the China Electrical Equipment Industry Association and the China Electricity Council. This part of the National Standardization Technical Committee of HVDC equipment (SAC/TC333) centralized. This part mainly drafted by: Nanjing NARI-RELAYS Electric Co., XJ Group Co., Ltd., Beijing Network of DC engineering technology Ltd., China Southern Power Grid Co., Ltd., Xuchang Relay Research Institute, Chinese Academy of Sciences electricity. The main drafters of this section. Cao Dongming, Haojun Fang, Yu Tao, Yao Zhiqing, Maoshi Tao, around, Li Yaping, Li Yan, Li Zhiyong, Wang Mingxin, Han Wei, Shiyan. This section first release. HVDC system control and protection equipment Part 2. AC and DC station control system equipment
1 Scope
China's national standard for the AC and DC station control equipment of a high voltage direct current transmission scheme. It is Part 2 of GB/T 22390 and specifies the technical requirements, the test methods, the inspection rules and the supply and documentation requirements for the station control equipment. Station control sits between the operator layer of Part 1 and the pole control of Part 3, and it governs everything in the converter station that is not the conversion itself. On the alternating current side that means the AC switchyard and its switching sequences, the converter transformers and their tap changers, and the filters - which matter more here than anywhere else in a power system, because a line-commutated converter draws heavily distorted current and absorbs a great deal of reactive power. The harmonic filters that absorb the distortion are also the source of the reactive power the converter needs, so the filter banks have to be switched in and out as the transmitted power changes, and getting that wrong causes either a voltage excursion or a harmonic limit violation. Station control does that switching. On the direct current side it governs the switchyard, the earth electrode line, the neutral bus arrangement and the transfer between bipolar, monopolar metallic return and monopolar earth return operation, which is how a link keeps transmitting after losing one pole. It also handles the station auxiliary systems, the cooling plant on which the valves depend, and the coordination with the remote station, since the two ends of an HVDC link operate as one machine and every mode change has to be agreed across the telecommunication link between them. Issued on 24 September 2008 and in force since 1 August 2009.
This section GB/T 22390 specifies the technical requirements of ± 500kV HVDC System AC and DC station control system equipment, test Test methods, inspection rules, packaging, transportation, storage, marking, labeling, instruction manual, complete sets of supply and quality assurance. This section applies to ± 500kV HVDC System AC and DC station control system equipment (hereinafter referred to as the device).
2 Normative references
The following documents contain provisions which, through reference
GB/T 22390 in this section constitute provisions of this section. For dated reference documents Member, all subsequent amendments (not including errata content) or revisions do not apply to this section, however, encouraged to reach under this section Parties to research agreement to use the latest versions of these documents. For undated reference documents, the latest versions apply to this section.
GB/T 2887-2000 General specification for computer sites
GB 4208-1993 housing protection (IP Code) (eqv
IEC 60529. 1989) Basic testing method
GB/T 7261-2000 and the relay means
GB/T 9361-1988 computer site security requirements
GB 9969.1-1998 Instructions General Industrial Products
GB/T 11287-2000 Electrical relays - Part 21. Measuring relays and protection equipment vibration, shock, bump and seismic Test Section 1. Vibration tests (sinusoidal) (idt IEC 60255-21-1. 1988) GB/T 13498 HVDC term ( GB/T 13498-2007, IEC 60633.1998, IDT)
GB/T 13730-2002 regional dispatching automation system
GB/T 14537-1993 and measure impact crash tests (idt
IEC 60255-21-2. 1988) relays and protection equipment
GB/T 14598.16-2002 Electrical relays - Part 25. Electromagnetic emission tests for measuring relays and protection equipment ( IEC 60255-25.2000, IDT)
GB 16836-2003 General requirements Measuring relays and protection equipment safety design
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 18 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 2887-2000General specification for computer field
- GB/T 7261-2000Basic test methods for protection relays and security automatic equipment
- GB/T 9361-1988Safety requirements for computer field
- GB/T 13730-2002Dispatching automation systems for distric power networks
- GB/T 17626.9-1998Electromagnetic compatibility - Testing and measurement techniques - Part 9: Impulse magnetic field immunity test
GB/T 22390 · GB 4208-1993 · IEC 60529 · GB 9969.1-1998 · GB/T 11287-2000 · IEC 60255 · GB/T 13498-2007 · IEC 60633.1998 · GB/T 14537-1993 · GB/T 14598.16-2002 · GB 16836-2003 · GB/T 17626.2-2006 · IEC 61000 · GB/T 17626.3-1998 · GB/T 17626.4-1998 · GB/T 17626.5-1999 · GB/T 17626.6-1998 · GB/T 17626.8-2006
Similar standards
How to Buy GB/T 22390.2-2008
- 1Add to cart. Click the "Buy GB/T 22390.2-2008" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 13730-2002 — Dispatching automation systems for distric power networks
GB/T 22390.1-2008 — Control and protection equipment of HVDC transmission systems - Part 1: Operator control system
GB/T 22390.3-2008 — Control and protection equipment of HVDC transmission systems - Part 3: DC pole control equipment
Secure payment via Stripe
Payments accepted
GB/T 22390.2-2008