GB/T 38953-2020Technical requirements for relay protection of microgrid (English PDF)

微电网继电保护技术规定

Preview PDF

This is a limited preview

Buy now to download the full PDF (15 pages)

Need quotation for your management?

Get a formal quotation for GB/T 38953-2020 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

June 2, 2020

Implementation date

January 1, 2021

Scope

GB/T 38953-2020 is the English-translated version of 微电网继电保护技术规定.

GB/T 38953-2020 is the Chinese standard "Technical requirements for relay protection of microgrid".

Its scope clause reads: This Standard specifies the technical requirements which shall be met by distributed resources protection, electrochemical energy storage protection, transformer protection, grid connection point protection, line protection, bus protection and security automatic equipment for microgrids.

This Standard applies to grid-connected AC microgrid and isolated AC microgrid whose voltage level is 35 kV and below.

Its clauses include terms and definitions; basic regulations; distributed resources protection; electrochemical energy storage protection; transformer protection; grid connection point protection; line protection; bus protection; microgrid security automatic equipment.

It was issued by the State Administration for Market Regulation on JUNE 02, 2020 and took effect on DECEMBER 01, 2020.

Found what you need?

Document preview — GB/T 38953-2020

National Standard of the People's Republic of China

ICS
29.240.01
Classification
K 45

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword3
  • 1 Scope4
  • 2 Normative references4
  • 3 Terms and definitions5
  • 4 Basic regulations5
  • 5 Distributed resources protection7
  • 6 Electrochemical energy storage protection8
  • 7 Transformer protection8
  • 8 Grid connection point protection8
  • 9 Line protection10
  • 10 Bus protection11
  • 11 Microgrid security automatic equipment11

1 Scope

This Standard specifies the technical requirements which shall be met by distributed resources protection, electrochemical energy storage protection, transformer protection, grid connection point protection, line protection, bus protection and security automatic equipment for microgrids.

This Standard applies to grid-connected AC microgrid and isolated AC microgrid whose voltage level is 35 kV and below.

2 Normative references

The following documents are indispensable for the application of this document.

For dated references, only the dated version applies to this document. For undated references, the latest edition (including all amendments) applies to this document.

GB/T 14285, Technical code for relaying protection and security automatic equipment

GB/T 22387, Residual current operated relay

GB/T 33589, Technical requirements for connecting microgrid to power system

GB/T 33982, Technical specification for grid connection protection of distributed resources

GB/T 34930, Operation and control specification for microgrids connected to distribution network

GB/T 36558, General technical requirements for electrochemical energy storage system in power system

DL/T 314, General specifications for power system under-voltage load-shedding and separation equipment

DL/T 315, General specifications for power system under-frequency load-shedding and separation equipment

d) Requirements for power distribution reliability and power quality; e) Economy.

4 Basic regulations

4.1.2 The microgrid relay protection shall be able to accurately identify microgrid faults, tie-line faults, unplanned islands, frequency or voltage abnormalities.

4.1.3 The microgrid relay protection shall not cause malfunction due to system oscillation.

4.1.4 When there is a fault inside the grid-connected microgrid, the microgrid relay protection shall remove the fault; if the fault cannot be quickly removed, when the microgrid is connected to the public grid by a dedicated line, the public grid protective action can disconnect the opposite-side switch of the grid connection point; when there are other branches on the microgrid tie line, the grid connection point protection shall disconnect the grid connection point switch before the public grid protection action.

4.1.5 When the grid-connected microgrid tie-line fails, the grid connection point protection shall quickly trip the grid connection point switch.

4.1.6 When the grid-connected microgrid has unplanned islands, the grid connection point protection shall trip the grid connection point switch; the action time is less than the action time of the public grid side standby automatic switching and reclosing.

4.1.7 When formulating a microgrid relay protection configuration plan, it shall be ensured that the fault is removed when two faults occur at the same time.

4.1.8 When the traditional protection principles and methods which are used in the microgrid cannot meet the requirements of reliability, selectivity, sensitivity and quick action, reliable new protection principles, methods and equipment shall be adopted.

4.2 Fix-value setting

4.2.1 The microgrid relay protection fix-value shall be set according to the microgrid working conditions and protection requirements such as the microgrid topological structure, the way of connecting and disconnecting from the grid, the type and status of internal distributed resources.

4.2.2 The microgrid relay protection fix-value shall be coordinated with the fault ride-through capability of microgrid. The setting of the grid-connected microgrid relay protection fix value shall be coordinated with the relay protection of the public grid.

4.3 Fault recording function

generator shall act reliably during out-of-step oscillation; it shall not malfunction during system short-circuit and stable oscillation.

6 Electrochemical energy storage protection

The relay protection configuration of electrochemical energy storage inside the microgrid shall meet the relevant requirements of GB/T 36558, and shall have the ability to link with the operation mode of the energy storage converter.

7 Transformer protection

7.1 General requirements

The protection of the microgrid 10(6) kV ~ 35kV voltage level transformer shall meet the relevant requirements of GB/T 14285.

7.2 Differential protection

The configuration principle of transformer differential protection shall meet the relevant requirements of GB/T 14285, and shall reliably trip the corresponding circuit breaker.

7.3 Non-electricity protection

7.3.1 Oil-immersed transformer shall be equipped with gas protection, heavy gas trip, light gas alarm.

7.3.2 Dry-type transformer shall be equipped with temperature over-limit protection, over-temperature alarm or trip.

7.4 Directional overcurrent protection and overload protection

7.4.1 Transformers without differential protection shall be equipped with current quick-break protection.

7.4.2 The transformer shall be equipped with over-current protection as a backup protection for phase-to-phase short circuit. When the selectivity does not meet the requirements, the overcurrent protection can add directional components.

7.4.3 The transformer shall be equipped with overload protection with constant time-lag or inverse time lag operation characteristics.

8 Grid connection point protection

8.1 General requirements

8.5 Simultaneous closing

For the 380(220) V voltage level microgrid, the point of connection shall be equipped with the synchronous closing function.

8.6 Anti-islanding protection

The point of connection of microgrid shall be equipped with anti-islanding protection. When running in grid-connected mode, the anti-islanding protection shall be used; otherwise, the anti-islanding protection shall be exited. Anti-islanding protection shall be reliable action to trip the grid connection point switch.

9 Line protection

9.1 General requirements

9.1.1 The 10(6) kV ~ 35 kV line protection inside the microgrid shall meet the relevant requirements of GB/T 14285.

9.1.2 The line protection of the microgrid shall be set according to the line type, length and load characteristics; the influence of the operation mode of the microgrid and the characteristics of distributed resources shall be considered comprehensively.

9.2 Differential protection

The internal cable line of the microgrid or the 10(6) kV ~ 35 kV line with difficulty in setting shall be equipped with the longitudinal current differential protection.

9.3 Overcurrent or directional overcurrent protection

9.3.1 The 10(6) kV ~ 35 kV voltage level lines inside the microgrid shall be equipped with overcurrent protection; when the selectivity does not meet the requirements, the overcurrent protection can add directional components.

9.3.2 The 380 (220) V voltage level lines inside the microgrid shall be equipped with instantaneous short-circuit protection, and should be installed with long-time short-circuit protection.

9.4 Ground fault protection

9.4.1 For microgrids that use neutral effective grounding, the 10(6) kV ~ 35 kV voltage level lines shall be equipped with ground fault protection. […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.

Referenced standards

Cited by

Similar standards

How to Download GB/T 38953-2020

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
15 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 38953-2020

$105.00