GB 28184-2011Power supply monitoring system for fire protection equipments (English PDF)
消防设备电源监控系统
Open the GB 28184-2011 preview as PDF
This is a limited preview
Buy now to download the full PDF (16 pages)
Issued by
General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China; Standardization Administration of China
Level / Type
National · Mandatory
Issue date
December 30, 2011
Implementation date
August 1, 2012
Scope
GB 28184-2011 is the English-translated version of 消防设备电源监控系统.
GB 28184-2011 is the Chinese national standard on power supply monitoring system for fire protection equipments, in the field of environment and health protection, safety. It carries no /T suffix, which in the Chinese system means compliance is mandatory: a product or a practice within its scope has to meet it to be lawfully made, sold or carried out in China. It was issued on 30 December 2011 by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China; Standardization Administration of China, and has been in force since 1 August 2012. Classification: ICS 13.220.20, CCS C81. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
Document preview — GB 28184-2011
National Standard of the People's Republic of China
- ICS
- 13.220.20
- Classification
- C81
Issued by: General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China; Standardization Administration of China
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
- 4 Requirements
- 4.2 Basic Functions
- 4.2.1 Fire Equipment Power Status Monitor
- 4.2.2 Voltage signal of the sensor
- 4.2.3 Current sensor signal
- 4.3 The main portion (device) member performance
- 4.3.2 LEDs and a display device
- 4.3.3 Audio Device
- 4.3.9 Appearance
- 5 Test methods
- 5.1 General Table
- 5.2 Basic Monitor function test
- 5.2.8 Checking additional features described in the specification. Table
- 5.3 Basic function test voltage sensor
- 5.4 Current sensor basic function test
- 5.5 Voltage/current sensor Basic function test
- 5.6 Insulation resistance test sqrt 6
- 5.6.1 Test procedure
- 5.7 Electric strength test sqrt 7
- 5.7.1 Test procedure
- 5.8 RFEMS test sqrt 8
- 5.8.1 Test procedure
- 5.9 RF field immunity test conducted disturbances induced sqrt 9
- 5.10 Electrostatic discharge immunity test sqrt 10
- 5.11 Electrical fast transient burst immunity test sqrt 11
- 5.12 Surge (impact) immunity test sqrt 12
- 5.13 Voltage dips, short interruptions and voltage variations immunity tests sqrt 13
- 5.14 Power transient test sqrt 14
- 5.15 Low temperature (operation) test sqrt 15
- 5.16 Damp heat (run) test sqrt 16
- 5.17 Damp heat (endurance) test sqrt 17
- 5.18 Vibration (sinusoidal) (run) test sqrt 18
- 6 Positive and negative >=1
- 7 Marking and instructions
Foreword
The standard Chapter 4, Chapter 6, Chapter 7 content mandatory, the rest are recommended. This standard was drafted in accordance with GB/T 1.1-2009 given rules. Please note that some of the content of this document may involve patents. Release mechanism of the present document does not assume responsibility for the identification of these patents. This standard by the National Standardization Technical Committee on Fire fire detection and alarm Technical Committee (SAC/TC113/SC6) centralized. This standard is drafted by: Ministry of Public Security Shenyang Fire Research Institute. It participated in the drafting of this standard. Sunny Beijing Century Technology Co., Ltd., Beijing original electronic limited liability company. The main drafters of this standard. Ding Hongjun, Liu Cheng, Liu Ziwei, Lihui Jing, Yang Bo, Dingwan Jun, Zhang Xuejun, Guo Shulin, Heng Su, Li Donghai. This standard is the first release. Fire fighting equipment power monitoring system
1 Scope
GB 28184-2011 is the Chinese national standard on power supply monitoring system for fire protection equipments, in the field of environment and health protection, safety. It carries no /T suffix, which in the Chinese system means compliance is mandatory: a product or a practice within its scope has to meet it to be lawfully made, sold or carried out in China. It was issued on 30 December 2011 by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China; Standardization Administration of China, and has been in force since 1 August 2012. Classification: ICS 13.220.20, CCS C81. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
This standard specifies the terms and definitions firefighting equipment power monitoring system, requirements, test methods, inspection rules, signs and the use of said Manual. This standard applies to the installation of fire fighting equipment power monitoring system for use in general industrial and civil buildings, installed in other environments extinction Security Equipment power monitoring system can also refer to this standard.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein Member. For undated references, the latest edition (including any amendments) applies to this document.
GB/T 156 standard voltage
GB/T 9969 General Instructions industrial products
GB 12978 fire electronic products inspection rules
GB 16838 fire electronic products environment test methods and severities
GB/T 17626.2 Electromagnetic compatibility Testing and measurement techniques - Electrostatic discharge immunity test
GB/T 17626.3 electromagnetic compatibility test and measurement technology RFEMS test
GB/T 17626.4 Electromagnetic compatibility Testing and measurement techniques - Electrical fast transient burst immunity test
GB/T 17626.5 electromagnetic compatibility test and measurement technology surge (impact) immunity test
GB/T 17626.6 Electromagnetic compatibility Testing and measurement techniques Immunity to conducted disturbances induced field
GB/T 17626.11 Electromagnetic compatibility Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests
GB 23757 fire protection requirements for electronic products
3 Terms and Definitions
The following terms and definitions apply to this document.
3.1 Fire Equipment Power powersupplyforfireprotectionequipments For the various types of fire equipment supply AC or DC power, including the main and backup power supply.
3.2 Fire fighting equipment used to monitor the work of state power, occurs in the power supply overvoltage, undervoltage, overcurrent, when the lack of equal fault monitor alarm signal can be issued Control system, the part of the fire equipment power status monitor, voltage sensor, current sensor, voltage/current sensors or all of the equipment composition.
4 Requirements
4.1 General Fire fighting equipment power monitoring system should first comply with the requirements of
4.2 to 4.3, then the provisions of Chapter 5, test, test results should meet Together with the relevant requirements of Chapter 4.
4.2.1 Fire Equipment Power Status Monitor
4.2.1.1 fire fighting equipment power status monitor (hereinafter referred to as the monitor) should be able to supply components for its connection DC operating voltage should be consistent GB/T 156 provides priority DC 24V.
4.2.1.2 Monitor should have Chinese features marked with Chinese characters should be used to display information.
4.2.1.3 Monitor the power should be set the main power and backup power. Main power should be 220V, 50Hz AC power and set the overcurrent protection Measures the power input terminals should be located. When the AC mains supply voltage fluctuation range of the rated voltage of 220V at 85% to 110% range When the inner circle, the frequency deviation of less than standard frequency of 50Hz ± 1%, the monitor should be able to work properly. Power supply section
4.2.1.4 Monitor should have the main power supply and backup power conversion function, and should be the main and backup power supply status indicator. when When the main power fails, can automatically switch to the backup power supply; when the mains power returns, can be automatically converted to the main power supply; main and backup power conversion should Movies Sound working properly monitor. Monitor backup power charged in discharge to the termination voltage condition obtained 24h capacity should be able to provide Monitor in the normal monitoring state for at least 8h.
Note. The normal monitoring state ie monitor under normal power supply conditions, no failure alarm, working state when the self-test operation.
4.2.1.5 monitor should be able to receive and display real-time job status information to monitor the main power supply for all its fire-fighting equipment and standby power.
4.2.1.6 Monitor under the following conditions shall be issued within 100s failure sound and light signals, display and record the fault location, type and time.
a) fire fighting equipment being monitored power interruption;
b) the grounding between the monitor and the outer connecting cable open circuit, short circuit and system functionality;
c) Monitor and its split between the ground power cable open circuit, short circuit and affect the function;
d) monitor the supply voltage is greater than 110% of the rated voltage or less than 85% of rated voltage (applies only to monitor with this feature Controller);
e) be monitored power supply phase is missing, wrong phase and overload power anomalies (This feature is only applicable to a monitor);
f) to monitor its own charger for charging between standby power and standby power cable open circuit, short circuit;
g) main power undervoltage monitor itself.
4.2.2 Voltage signal of the sensor
4.2.2.1 voltage signal of the sensor should follow the manufacturer's requirements transmitted signal will be collected to monitor.
4.2.2.2 Signal voltage operating range of the sensor should meet the manufacturer's specifications, the output signal should not exceed 12V.
4.2.2.3 For continuous acquisition can signal voltage sensor voltage value, the voltage acquisition error should not be greater than 5%.
4.2.3 Current sensor signal
4.2.3.1 Current sensor signal should follow the manufacturer's requirements transmitted signal will be collected to monitor.
4.2.3.2 Current sensor operating signal range should meet the manufacturer's specifications, the output signal should not exceed 12V.
4.2.3.3 For continuously collect current value of the sensor signal, which collect current error should not exceed 5%.
4.2.4 voltage/current signal sensor Voltage/current signal sensor should also comply with the provisions of
4.2.2 and 4.2.3.
4.3 The main portion (device) member performance
4.3.1 Basic requirements Protective performance of each device within the fire-fighting equipment power monitoring system shall comply with the requirements of GB 23757, and its main components should be used in line with Off standard stereotypes products, and should comply with the corresponding provisions of 4.3.2 - 4.3.9.
4.3.2 LEDs and a display device
4.3.2.1 Indicator should be color-coded, yellow indicates a fault condition; the main power supply and standby power supply is working properly with green indicator. The use of Chinese should be clearly marked on the function indicator
4.3.2.2 or near the location.
4.3.2.3 In 100lx ~ 500lx ambient light conditions in front of 22.5 ° angle range, status and power LEDs should 3m in place clearly visible; the other indicators (unit) should be clearly visible at 0.8m.
4.3.2.4 using flash mode indicator lights up each time should not be less than 0.25s, fault indicator flashing frequency should not be less than 1Hz. When
4.3.2.5 show different parts of the state with a particular indicator (device), you should be able to clearly distinguish.
4.3.2.6 In 100lx ~ 500lx ambient light conditions, letter (character) - character digital display should be 22.5 ° viewing angle in front of Inside, 0.8m at readable.
4.3.3 Audio Device
4.3.3.1 Under normal operating conditions, sound device SPL (A weighted) at 1m directly in front of it should be greater than 65dB, less than 115dB.
4.3.3.2 at 85% of rated voltage power supply conditions should be audible.
4.3.4 Terminals On each of the terminals should be clear, firmly marked number or symbol corresponding use shall be stated in the relevant documents.
4.3.5 Switches and buttons Its functions should be clearly marked on the switches and buttons on or near the location.
4.3.6 Fuse Rated current power line fuses or other overcurrent protection devices shall not be greater than 2 times the product of the maximum operating current, when most Large operating current is greater than 6A, fuse current value can be
1.5 times, and should clearly near the fuses or other overcurrent protection devices at Marked its parameter values.
4.3.7 charger and backup power
4.3.7.1 Connect the positive power lead to red, black or blue is extremely negative.
4.3.7.2 Battery charge current should not exceed the manufacturer's specified rating.
4.3.8 Ground Fire fighting equipment power monitoring system should be clearly marked and the ground terminal.
4.3.9 Appearance
4.3.9.1 text, symbols and signs clear and complete.
4.3.9.2 The surface should be free from corrosion, coating loss and blistering, cracks should be no scratches, burrs and other mechanical damage.
4.4 Insulation resistance Fire fighting equipment power monitoring system insulation resistance value of the external charging terminals and the chassis between the insulation requirements should be not less than 20MOmega; adopt 220V AC power supply of fire-fighting equipment insulation resistance of the power supply monitoring system between input and chassis shall be not less than 50MOmega.
4.5 Electric strength Room with 220V AC power supply of fire fighting equipment power monitoring system and plug housing should be able to withstand a frequency of 50Hz, RMS voltage is 1250V AC voltage, which lasted 1min the electric strength test. During the test, the breakdown should not occur; After the test, The basic functions should be consistent with the previous test.
4.6 Electromagnetic compatibility Power monitoring systems and fire-fighting equipment of each device within the system should be able to adapt to the testing requirements of the table under a predetermined condition. Trial period Room should remain normal monitoring state; After the test, the basic functions should be consistent with the previous test.
4.7 Supply Transients Tolerance Main power supply fire fighting equipment monitoring system by "power (9s) ~ power (1s)" fixed program continuously off 500 times. Trial period Room should remain normal monitoring state; After the test, the basic functions should be consistent with the previous test. Table 1 EMC test conditions Name of test Test conditions Anti-static discharge Interference Test Discharge voltage/kV discharge polarity INTERSPIKE Septum/s Each point of discharge Power Ups Working condition Air discharge (housing insulator).
8 Contact discharge (shell conductor).
5.1 General Table
4 Test procedure 5.1.1.
5.1.2 before the test, the manufacturer shall provide two test samples (hereinafter referred to as the sample) and related accessories, load, etc., and prior to the test to be Numbering.
5.1.3 The test shall be carried out under the following atmospheric conditions.
--- Temperature. 15 °C ~ 35 °C;
--- Humidity. 25% RH ~ 75% RH;
--- Atmospheric pressure. 86kPa ~ 106kPa.
5.1.4 tolerance test data is ± 5%. Environmental conditions parameter deviation should be consistent with GB 16838 requirements.
5.1.5 before the test, the sample should be visually examined to check the main components and protective performance checks, the test can be carried out to meet the requirements.
5.2 Basic Monitor function test
5.2.1 The sample connect more than two real sensors can be connected to other circuits equivalent load, the power, the sample in the normal Monitoring status.
5.2.2 Turn on the main power source of the sample, observe and record the working status of the sample.
5.2.3 disconnect the main power source of the sample, as required observe and record the working status of the sample in the standby state of the power supply.
5.2.4 observe the specimen displays real-time job status information to monitor the power supply, the recording of work status of the sample.
5.2.5 simulating various fault conditions, observe and record the working status of the sample.
5.2.6 Operation sample self-test mechanism, observe and record the working status of the sample.
5.2.7 simulate a variety of co-existing work status information, observe and record the working status of the sample.
5.3 Basic function test voltage sensor
5.3.1 The sample with the monitor connected to power, the sample in the normal monitoring state. Standard operating range of fluctuation voltage signal provided by the manufacturer 5.3.2, observe and capture the output parameter values and sample records.
5.3.3 Checking additional features described in the specification.
5.4 Current sensor basic function test
5.4.1 The sample with the monitor connected to power, the sample in the normal monitoring state. Standard operating range of fluctuation voltage signal provided by the manufacturer 5.4.2, observe and capture the output parameter values and sample records.
5.4.3 Checking additional features described in the specification.
5.5 Voltage/current sensor Basic function test
5.5.1 The sample with the monitor connected to power, the sample in the normal monitoring state. Fluctuations in operating range standard voltage supplied by the manufacturer 5.5.2/current signal, and output parameters and observed values of the sample collection record.
5.5.3 Checking additional features described in the specification.
5.6.1 Test procedure
5.6.1.1 After the sample have external charging terminals shorted insulation requirements, connected to the positive output terminal of the insulation resistance test device, then cabinet To the negative output terminal of the insulation resistance test device. 5.6.1.2 500V ± 50V DC voltage is applied, continued 60s ± 5s after recording insulation resistance value.
5.6.1.3 A sample power plug (or power terminals) after a short, connected to the positive output terminal of the insulation resistance test device, then cabinet To the negative output terminal of the insulation resistance test device. 5.6.1.4 500V ± 50V DC voltage is applied, continued 60s ± 5s after recording insulation resistance value.
5.6.2 Test Equipment With insulation resistance test device satisfy the following technical requirements (also available or megger shake table test).
a) Test voltage. 500V ± 50V;
b) measuring range. 0MOmega ~ 500MOmega;
c) minimum scale. 0.1MOmega;
d) the chronograph. 60s ± 5s.
5.7.1 Test procedure
5.7.1.1 before the test, ground protection element of the sample removed.
5.7.1.2 By means test to 100V/s ~ 500V/s boost rate of the sample between the power line and chassis applied to 50Hz, 1250V (rms voltage) test voltage, duration 60s ± 5s, observe and record the phenomena that occur in the test.
5.7.1.3 to 100V/s ~ 500V/s down rate of the voltage drops below the rated voltage value, the output voltage of the test apparatus off.
5.7.1.4 Sample power is turned on, it is in the normal monitoring state.
5.7.1.5 basic function test, and compared with the basic functions before the test.
5.7.2 Test Equipment Using the test device satisfies the following condition.
a) Test voltage. voltage 0V ~ 1250V (RMS) continuously adjustable, frequency 50Hz;
b) liters, down rate. 100V/s ~ 500V/s;
c) Timing. 60s ± 5s, the breakdown current. 20mA.
5.8.1 Test procedure
5.8.1.1 according to the provisions of GB/T 17626.3 of the test arrangement, the power is turned on the sample, it is in the normal monitoring state, holding 20min. Electromagnetic interference test
5.8.1.2 Test methods according to GB/T 17626.3 specified conditions shown in Table 1 for the sample is applied to observe and record the test Kind of working condition.
5.8.1.3 basic function test, and compared with the basic functions before the test.
5.18 Vibration (sinusoidal) (run) test sqrt 18
5.19 vibration (sinusoidal) (endurance) test sqrt Crash Test sqrt 19 5.20
6 Positive and negative >=1
10 Normal prison Depending on the state of Electrical Fast Transient Anti-burst Interference Test Peak voltage/kV repetition frequency/kHz Polarity Time/min working condition AC power cord. 2 × (1 ± 0.1) Other cables. 1 × (1 ± 0.1) AC power cord. 2.5 × (1 ± 0.2) Other cable. 5 × (1 ± 0.2) Positive and negative each time Normal prison Depending on the state of Surge (impact) Immunity Test Surge (impact) Voltage/kV Polarity Duration Room/ms The number of trials work status AC power line (Line - Line). 1 × (1 ± 0.1) AC power cord (cord - to). 2 × (1 ± 0.1) Other cable (wire - ground). 1 × (1 ± 0.1) Positive and negative 10 (decline 100%) AC power cord.
20 Normal prison Depending on the state of Radio frequency electromagnetic Anti-radiation field Interference Test Field/(V/m) Frequency Range/MHz Scan rate / (10oct/s) Modulation amplitude working condition 1080 to 1000 <=1.5 × 10-3 80% (1kHz, Sine) Normal prison Depending on the state of RF induction field Conducted disturbances Immunity Test Frequency range/MHz voltage/dBµV amplitude modulation operation state 0.15 ~ 80 140 80% (1kHz, sine) Normal prison Depending on the state of Voltage dips, Short interruptions and Voltage changes Immunity Test Test Time/ms number of tests work status 20 (40% supply voltage) 10 (0V) Normal prison Depending on the state of Table 2 climate conditions Name of test Test conditions Low temperature (running) test Temperature/°C duration/h working condition 0 ± 3 16 normal surveillance state Damp (run) test Temperature/°C relative humidity /% duration/d working condition 40 ± 2 90 ~ 95 4 normal surveillance state Damp heat (endurance) test Temperature/°C relative humidity /% duration/d working condition 40 ± 2 90 ~ 95 21-energized state
4.8 Climate tolerance Power monitoring systems and fire-fighting equipment of each device within the system should be able to withstand the test under Table 2 under the climatic conditions. Trial period Between each device in energized state should maintain a normal monitoring state; After the test, should be no damage to the coating and corrosion, the basic functions should test Before consistency.
4.9 Mechanical environmental resistance Power monitoring systems and fire-fighting equipment of each device within the system should be able to withstand the test under Table 3 in the predetermined mechanical environmental conditions. During the test, each device is connected to power should maintain a normal monitoring state; after the test should not have mechanical damage and tighten loose parts, The basic functions should be consistent with the previous test. Table
3 Mechanical ambient conditions Name of test Test conditions Vibration (sinusoidal) (Running) test Cycle frequency range / Hz Acceleration Amplitude / (M/s2) Sweep rate / (Oct/min) Each axis Sweep/times The vibration direction of the work of state 10 ~ 150 0.981 1 1 X, Y, Z normal monitoring state Vibration (sinusoidal) (Durability Test Cycle frequency range / Hz Acceleration Amplitude / (M/s2) Sweep rate / (Oct/min) Each axis Sweep/times The vibration direction of the work of state 10 ~ 150 4.905 1 20 X, Y, Z is not energized Crash Test Collision energy/J collisions working condition 0.5 ± 0.04 3 normal surveillance state
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 16 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 9969General principles for preparation of instructions for use of industrial products
- GB 12978Rules for test of fire electronic products
- GB/T 17626.11Electromagnetic compatibility - Testing and measurement techniques - Part 11: Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase
- GB 23757Protection requirements for fire electronic products
GB/T 156 · GB 16838 · GB/T 17626.2 · GB/T 17626.3 · GB/T 17626.4 · GB/T 17626.5 · GB/T 17626.6
Similar standards
Editions of GB 28184
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB 28184-2011 | Power supply monitoring system for fire protection equipments | current edition | Current |
This page sells the current edition, GB 28184-2011. Earlier editions are listed for reference only.
How to Buy GB 28184-2011
- 1Add to cart. Click the "Buy GB 28184-2011" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 12978-2003 — Rules for test of fire electronic products
GB 12978-2025 — Rules for test of fire electronic products
GB 23757-2009 — Protection requirements for fire electronic products
Secure payment via Stripe
Payments accepted
GB 28184-2011
$260.00