GB/T 5773-2016The method of performance test for positive displacement refrigerant compressors (English PDF)
容积式制冷剂压缩机性能试验方法
This is a limited preview
Buy now to download the full PDF (56 pages)
Need quotation for your management?
Get a formal quotation for GB/T 5773-2016 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 13, 2016
Implementation date
July 1, 2017
Scope
GB/T 5773-2016 is the English-translated version of 容积式制冷剂压缩机性能试验方法.
GB/T 5773-2016 is the Chinese standard "The method of performance test for positive displacement refrigerant compressors".
Its scope clause reads: This Standard specifies the terms and definitions, test regulations, test methods, as well as calculation of input power, cooling (heating) coefficient of performance, volume efficiency, isentropic efficiency and test deviation for positive displacement refrigerant compressors.
This Standard applies to the performance test for single-stage positive displacement refrigerant compressor (hereinafter referred to as "single-stage compressor"), positive displacement refrigerant compressor equipped with economizer (hereinafter referred to as "compressor equipped with economizer") and positive displacement refrigerant compressor equipped with flash-tank (hereinafter referred to as "compressor equipped with flash-tank").
It applies as a reference to the tests for other types of compressors.
Its clauses include terms and definitions; test regulations; test methods; input power calculation; calculation of cooling (heating) coefficient of performance; volume efficiency calculation; isentropic efficiency calculation; deviation between method x and method y; performance measurement uncertainty analysis.
It was issued by the General Administration of Quality Supervision, Inspection and Quarantine on DECEMBER 13, 2016 and took effect on JULY 01, 2017.
Found what you need?
Document preview — GB/T 5773-2016
National Standard of the People's Republic of China
- ICS
- 27.200
- Classification
- J 73
- Replacing
- GB/T 5773-2004
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- 1 Scope4
- 2 Normative references4
- 3 Terms and definitions5
- 4 Test regulations6
- 5 Test methods15
- 6 Input power calculation46
- 7 Calculation of cooling (heating) coefficient of performance47
- 8 Volume efficiency calculation49
- 9 Isentropic efficiency calculation49
- 10 Deviation between method X and method Y49
- 11 Performance measurement uncertainty analysis50
- Appendix A (Informative) Oil content measurement method51
- Appendix B (Informative) Symbols and meanings used in formulas52
- Appendix C (Informative) Performance measurement uncertainty analysis example56
1 Scope
This Standard specifies the terms and definitions, test regulations, test methods, as well as calculation of input power, cooling (heating) coefficient of performance, volume efficiency, isentropic efficiency and test deviation for positive displacement refrigerant compressors.
This Standard applies to the performance test for single-stage positive displacement refrigerant compressor (hereinafter referred to as "single-stage compressor"), positive displacement refrigerant compressor equipped with economizer (hereinafter referred to as "compressor equipped with economizer") and positive displacement refrigerant compressor equipped with flash-tank (hereinafter referred to as "compressor equipped with flash-tank"). It applies as a reference to the tests for other types of compressors.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
GB/T 2624.1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 1: General principles and requirements
GB/T 2624.2, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 2: Orifice plates
GB/T 2624.3, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 3: Nozzles and Venturi nozzles
GB/T 2624.4, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 4: Venturi tubes
GB 9237, Refrigerating systems and heat pumps - Safety and environmental requirements
GB/T 29030-2012, Positive displacement CO2 refrigerant compressor (unit)
JB/T 7249, Refrigeration and air conditioning apparatus - Terminology
3 Terms and definitions
For the purpose of this document, the following terms and definitions, as well as those given in JB/T 7249, apply.
3.1 Positive displacement refrigerant compressor
The refrigerant compressor that relies on the reduction of the internal volume of the compression chamber to increase the refrigerant vapor pressure.
3.2 Compressor refrigerating capacity
Under the specified refrigeration capacity test conditions, the mass flow rate of refrigerant flowing through the evaporator in the refrigeration cycle where the compressor is located multiplied by the difference between the refrigerant gas specific enthalpy at the compressor suction port and the refrigerant liquid specific enthalpy before expansion in the evaporator in the refrigeration cycle where the compressor is located.
3.3 Compressor heating capacity
Under the specified heating capacity test conditions, the mass flow rate of refrigerant flowing through the exhaust side of the compressor multiplied by the difference between the specific enthalpy of the refrigerant gas at the compressor exhaust port and the specific enthalpy of the refrigerant liquid before expansion in the evaporator (air supply circuit) in the refrigeration cycle where the compressor is located.
Note: The unit is W.
4 Test regulations
4.1 General regulations
4.1.1 Remove non-condensable gases from the test system. Check that there is no refrigerant leakage.
4.2 Test regulations
4.2.1 The compressor refrigerating capacity performance test of a single-stage compressor includes two test methods, namely, method X and method Y. The two methods shall be tested simultaneously; the deviation between the test results of method X and method Y shall be within ±4%; the average value of the measurement and calculation results of method X and method Y shall prevail.
4.2.2 For the compressor heating capacity test of the compressor and the compressor refrigerating capacity test of the compressor equipped with economizer or flash-tank, only one test method (method X or method Y) may be used for measurement.
4.2.4 Types of test methods
The compressor test shall comply with the requirements of 4.2.1 and 4.2.2. During each test cycle, the data specified in the test report (see 4.5.2) shall be measured, together with any additional data required for each test method.
4.2.5 Selection between test method X and method Y
For subcritical cycle compressors, any of the performance test methods A, B, C, D1, D2, F, G and K may be used as method X.
4.2.6 Combination of test method X and method Y
4.4 Provisions for measuring instruments and accuracy
4.4.1 General provisions
4.4.2 Temperature measurement
4.4.2.1 Instrumentation
Instruments for measuring temperature include. glass mercury thermometer, thermocouple, resistance thermometer, semiconductor thermometer and differential thermometer.
4.4.2.2 Accuracy
The accuracy requirements of the measuring instrument are as follows. […]
4.4.2.3 Measurement regulations
The following requirements shall also be met during measurement.
4.4.3 Pressure measurement
4.4.3.1 Instrumentation
Instruments for measuring pressure include. spring tube pressure gauge, pressure sensor and mercury column atmospheric pressure gauge, etc.
4.4.3.2 Accuracy
For all pressure measuring instruments, the accuracy of absolute pressure reading or differential pressure reading shall be within ±1.0%.
4.4.3.3 Measurement regulations
When measuring atmospheric pressure using a mercury barometer, the reading shall be corrected for temperature.
4.4.4 Flow measurement
4.4.5 Electrical measurements
4.4.5.1 Instrumentation
Electrical measuring instruments include. power meter (including indicating and integrating types), ammeter, voltmeter, power factor meter, frequency meter and transformer.
4.4.5.2 Accuracy
The accuracy requirements of the measuring instrument are as follows. […]
4.4.5.3 Measurement regulations
The power meter measurement value shall be above 1/3 of the full scale (when using the "two-power meter" method for measurement, the measured value of one of the power meters can be less than 1/3 of the full scale). When using the "two-power meter" method or the "three-power meter" method to measure the power of a three-phase AC motor, the indicated current and voltage values shall not be less than 60% of the rated current and voltage values of the power meter.
For digital power meters. If a current transformer is used, the actual displayed current value shall not be less than 20% of the transformer range.
4.4.6 Compressor power measurement
4.5.2 Test report
4.5.2.1 General data
It mainly includes.
4.5.2.2 Test conditions
It mainly includes.
4.5.2.3 Test method
Method X and method Y.
4.5.2.4 Average value of test measured values
It mainly includes.
4.5.2.5 Test result data
It mainly includes.
5 Test methods
5.1 Test methods for subcritical cycle compressors
5.1.1 Method A. Second refrigerant calorimeter method (Figure 1)
The performance test process of single-stage compressor is shown in Figure 1a); the performance test process of compressor equipped with economizer is shown in Figure 1b); the performance test process of compressor equipped with flash-tank is shown in Figure 1c).
5.1.1.1 Construction
The second refrigerant calorimeter is composed of a group of direct evaporation coils as an evaporator, which is suspended on the upper part of an insulated pressure container.
The electric heater is installed at the bottom of the container and is immersed in the second refrigerant in the container.
5.1.1.3 Test procedure
5.1.1.3.1 The suction pressure of the compressor refrigerant is regulated by the main circuit expansion valve, and the suction temperature is regulated by the electric heating capacity input to the second refrigerant.
5.1.2 Method B. Fully liquid refrigerant calorimeter method (Figure 2)
The performance test process of single-stage compressor is shown in Figure 2a); the performance test process of compressor equipped with economizer is shown in Figure 2b); the performance test process of compressor equipped with flash-tank is shown in Figure 2c).
5.1.2.3.5 During the test period, the change in the compressor refrigerating capacity caused by the fluctuation of the input heat shall not exceed 1%. If the heater is working intermittently, the change in the saturation temperature (or dew point temperature) corresponding to the refrigerant liquid shall be less than ±0.5 °C.
5.1.2.3.6 Additional data include
5.1.2.4 Refrigerant flow rate calculation
6 Input power calculation
6.1 Motor input power measurement
6.2 Compressor shaft power calculation
6.3 Input power
The input power shall be the above motor input power or compressor shaft power after correction plus the auxiliary power required to maintain the compressor operation. The above power shall be corrected for open or closed compressors according to Formula (24) to obtain the input power.
7 Calculation of cooling (heating) coefficient of performance
7.1 Compressor refrigerating capacity
7.1.1 Calculate the actual compressor refrigerating capacity under specified working conditions as follows.
7.1.2 Calculate the compressor refrigerating capacity based on the measured compressor refrigerating capacity after speed correction or frequency correction according to Formula (28). […]
7.2 Cooling coefficient of performance
Calculate the cooling coefficient of the compressor according to Formula (29).
7.3 Compressor heating capacity
7.4 Heating coefficient of performance
Calculate the heating coefficient of the compressor according to Formula (35).
8 Volume efficiency calculation
Calculate the volume efficiency of the compressor according to Formula (36).
9 Isentropic efficiency calculation
Calculate the isentropic efficiency of single-stage compressor according to Formula (37). […]
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 56 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 2624.1Full differential pressure device installed in a pipe of circular cross-section measuring fluid flow -- Part 1: General principles and requirements
- GB/T 2624.2Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 2: Orifice plates
- GB/T 2624.3Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 3: Nozzles and Venturi nozzles
- GB/T 2624.4Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 4: Venturi tubes
- GB/T 29030-2012Positive displacement CO2 refrigerant compressor(unit)
- JB/T 7249Refrigeration and air-conditioning equipment Terminology
GB 9237
Cited by
- GB/T 22068-2025Electrically driven compressor assembly for automobile air conditioning
- GB/T 26181-2025Hermetic motor-compressors for household and similar application heat pump water heaters using CO2 refrigerant
- GB/T 45595-2025Centrifugal refrigerant compressors
- GB/T 21145-2023Mechanical transport refrigeration units
- GB/T 29780-2023Hermetic motor-compressors for household and similar application heat pump water heater
- GB/T 15765-2021Hermetic motor-compressors for room air conditioners
Similar standards
Editions of GB/T 5773
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 5773-2016 | The method of performance test for positive displacement refrigerant compressors | current edition | Current |
| GB/T 5773-2004 | The method of performance test for positive displacement refrigerant compressors | previous edition | Superseded |
This page sells the current edition, GB/T 5773-2016. Earlier editions are listed for reference only.
How to Download GB/T 5773-2016
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 2624.1-2006 — Full differential pressure device installed in a pipe of circular cross-section measuring fluid flow -- Part 1: General principles and requirements
GB/T 2624.2-2006 — Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 2: Orifice plates
GB/T 2624.3-2006 — Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 3: Nozzles and Venturi nozzles
Secure payment via Stripe
Payments accepted
GB/T 5773-2016
$495.00