GB/T 31365-2015Testing code for photovoltaic power station connected to power grid (English PDF)
光伏发电站接入电网检测规程
This is a limited preview
Buy now to download the full PDF (20 pages)
Need quotation for your management?
Get a formal quotation for GB/T 31365-2015 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
February 4, 2015
Implementation date
September 1, 2015
Scope
GB/T 31365-2015 is the English-translated version of 光伏发电站接入电网检测规程.
GB/T 31365-2015 is the testing code for photovoltaic power stations connected to the power grid.
Clause 1 states that the standard specifies the test items, test conditions, test equipment and test methods for photovoltaic power plants connected to the grid, and that it applies to photovoltaic power plants connected to the grid at voltage levels of 35kV and above and to newly built, expanded and reconstructed photovoltaic power plants connected to the public grid at the 10kV voltage level.
The contents list runs 1 Scope, 2 Normative references, 3 Terms and definitions, 4 General, 5 Measurement device, 6 Power features, 7 Operation suitability, 8 Low voltage ride through capability, 9 Power quality and 10 Test file, followed by four informative annexes: Appendix A on inspection records, Annex B on the method for determining the response time and precision of power setpoint control, Annex C on the method for determining and calculating reactive current injection, and Appendix D on the method for determining active power recovery.
Clause 3 defines five terms: the photovoltaic power unit, a set of photovoltaic modules connected in series and parallel within the plant and collected through DC combiner boxes and DC distribution cabinets, then raised by inverter and step-up transformer to a supply matching the grid frequency and voltage; the active power change, the difference between the maximum and minimum active power of the plant within a given time interval; the solar global irradiance, the total solar radiation flux incident per unit area on a horizontal surface, in W per square metre; the module temperature, the actual operating temperature at the back of the solar module; and the grid simulator, a controllable AC power source whose output characteristics are analogous to those of the power system.
The draft breaks off after 3.5, so the content of clauses 4 to 10 is not shown. Clause 2 cites GB/T 12325, GB/T 12326, GB/T 14549, GB/T 15543, GB/T 15945, GB/T 17626.15, GB/T 17626.30, GB/T 19964-2012, GB 20840.2 and GB 20840.3.
The page records the standard as proposed and managed by the China Electricity Council and drafted by the China Electric Power Research Institute and the State Grid Electric Power Research Institute. It was issued on 4 February 2015 and has applied since 1 September 2015.
Found what you need?
Document preview — GB/T 31365-2015
National Standard of the People's Republic of China
- ICS
- 27.160
- Classification
- F 12
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 General
- 5 measurement device
- 6 Power Features
- 7 5 Operation Suitability
- 8 7 low voltage ride through capability
- 9 Power Quality
- 10 detects file
- Appendix A (informative) inspection records
- Annex B (informative) power setpoint control response time and precision control method for determining
- Annex C (informative) reactive current injection method for the determination and calculation of Active determination Appendix D (informative) recovery method
Foreword
This standard was drafted in accordance with GB/T 1.1-2009 given rules.
1 Scope
This standard specifies the photovoltaic power plants connected to the grid test items, test conditions, test equipment and testing methods.
This standard applies to 35kV and above voltage level through the grid, and connected via 10kV voltage level and a new public grid Construction, expansion and renovation of photovoltaic power plants.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein Member. For undated references, the latest edition (including any amendments) applies to this document.
GB/T 12325 power quality supply voltage tolerance
GB/T 12326 Power quality voltage fluctuation and flicker
GB/T 14549 Power quality utility grid harmonic
GB/T 15543 Power quality Unbalance
GB/T 15945 Power quality power system frequency deviation
GB/T 17626.15 electromagnetic compatibility test and measurement technology scintillation Functional and design specifications
GB/T 17626.30 electromagnetic compatibility test and measurement techniques - Power quality measurement methods
GB/T 19964-2012 provisions of photovoltaic power plants power system access technology
GB 20840.2 transformers - Part 2: Additional technical requirements for current transformers
GB 20840.3 transformers - Part 3: Electromagnetic Voltage Transformer additional technical requirements
3 Terms and Definitions
The following terms and definitions apply to this document.
3.1 Photovoltaic cells
Photovoltaic power plant, a certain number of PV modules in series and parallel connections, via the DC combiner box and DC distribution cabinet multilevel collection, By photovoltaic inverter unit step-up transformer and a boost to conform to the requirements of the grid frequency and voltage of the power supply.
3.2 Active change
Within a certain time interval, photovoltaic power stations and the minimum difference between the maximum active power.
3.3 Total irradiance
Incident on a horizontal surface per unit area of all of the solar radiation flux (W/m2).
3.4 Module temperature
Solar components back in the actual operating temperature.
3.5 Network simulator
Analog Power controllable AC power output characteristics.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 20 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 12325Power quality - Deviation of supply voltage
- GB/T 12326Power quality - Voltage fluctuation and flicker
- GB/T 14549Quality of electric energy supply--Harmonics inpublic supply network
- GB/T 15543Power quality - Three-phase voltage unbalance
- GB/T 15945Power quality - Frequency deviation for power systems
- GB/T 17626.15Electromagnetic compatibility -- Testing and measurement techniques -- Flicker meter -- Functional and design specifications
Similar standards
How to Download GB/T 31365-2015
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 20840.2-2014 — Instrument transformers -- Part 2: Additional requirements for current transformers
GB 20840.3-2013 — Instrument transformers -- Part 3: Additional requirements for inductive voltage transformers
GB/T 12325-2008 — Power quality - Deviation of supply voltage
Secure payment via Stripe
Payments accepted
GB/T 31365-2015
$360.00