GB/T 22072-2018Specifications and technical requirements for dry-type amorphous alloy core distribution transformers (English PDF)
干式非晶合金铁心配电变压器技术参数和要求
This is a limited preview
Buy now to download the full PDF (22 pages)
Need quotation for your management?
Get a formal quotation for GB/T 22072-2018 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 28, 2018
Implementation date
July 1, 2019
Scope
GB/T 22072-2018 is the English-translated version of 干式非晶合金铁心配电变压器技术参数和要求.
GB/T 22072-2018 fixes the performance parameters and the technical requirements for dry-type distribution transformers with an amorphous alloy core, the low-loss transformers used in urban and industrial networks.
It tabulates the rated parameters for the 6 kV and 10 kV off-circuit tap-changing self-cooled units - no-load and load losses, no-load current and impedance voltage - and then sets the technical requirements, the inspection rules and test methods, and the provisions on marking, packaging, transport and storage.
Utilities and panel builders use it to specify and accept a transformer, and manufacturers to declare its class. It replaces GB/T 22072-2008, was issued on 28 December 2018 and has applied since 1 July 2019.
Found what you need?
Document preview — GB/T 22072-2018
National Standard of the People's Republic of China
- ICS
- 29.180
- Classification
- K 41
- Replacing
- GB/T 22072-2008
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
- 4 performance parameters
- 5 Technical requirements
- 6 Inspection rules and methods
- 7 Marking, packaging, transportation and storage
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
This standard replaces GB/T 22072-2008 "dry amorphous alloy iron core distribution transformer technical parameters and requirements", and GB/T 22072- The main technical changes in.2008 are as follows.
--- Modifications to normative references (see Chapter 2);
--- Adjusted the no-load current and sound level of the 10kV voltage class (see 4.1 and 5.3, Chapter 4 of the.2008 edition)
And 5.11);
--- Increased performance parameters and sound level levels for products at 20kV and 35kV (see 4.2, 4.3 and 5.3).
1 Scope
This standard specifies the terms and definitions, performance parameters, technical requirements, inspection rules and methods of dry amorphous alloy iron core distribution transformers.
Marking, packaging, transportation and storage.
This standard applies to the system nominal voltage of 6kV, 10kV, 20kV and 35kV, rated frequency is 50Hz, rated capacity is 30kVA~2500kVA, three-phase dry amorphous alloy core non-excitation voltage regulating distribution transformer used indoors (hereinafter referred to as "variable voltage" "").
For other rated capacity products, please refer to the use of this standard.
This standard does not apply to inflatable transformers.
2 Normative references
The following documents are indispensable for the application of this document. For dated references, only dated versions apply to this document. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 191 packaging storage and transportation icon
GB/T 1094.1 Power transformers - Part 1. General
GB/T 1094.10 Power transformers - Part 10. Sound level determination
GB/T 1094.11 Power transformers - Part 11. Dry transformers
GB/T 1094.12 Power transformers - Part 12. Load guides for dry power transformers
GB/T 2828.1. Sampling procedures for sampling by sampling - Part 1 . Batch-to-batch sampling plan, searched by AQL
GB/T 2900.95 Electrical terminology transformers, voltage regulators and reactors
GB/T 5273 high-voltage electrical terminal size standardization
GB/T 5465.2 Graphical symbols for electrical equipment - Part 2. Graphical symbols
JB/T 501 Power Transformer Test Guide
3 Terms and definitions
The following terms and definitions as defined in GB/T 1094.1, GB/T 1094.11 and GB/T 2900.95 apply to this document.
3.1 Amorphous alloy
An alloy in which iron atoms, silicon, boron, carbon, cobalt and the like are used as raw materials, and internal atoms are disorderly arranged by a special process such as rapid cooling.
3.2 Amorphous alloy core
A transformer core made of an amorphous alloy strip having soft magnetic properties.
3.3 Dry-type amorphous alloy core distribution transformer
A dry distribution transformer with an amorphous alloy core as a magnetic conductive material.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 22 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 191Graphical symbols marking for handling and storage of packages
- GB/T 1094.1Power transformers-Part 1: General
- GB/T 1094.10Power transformers - Part 10: Determination of sound levels
- GB/T 1094.11Power transformers—Part 11: Dry-type transformers
- GB/T 1094.12Power transformers -- Part 12: Loading guide for dry-type power transformers
- GB/T 2828.1Sampling procedures for inspection by attributes - Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-by-lot inspection
Cited by
- GB 20052-2024Minimum allowable values of energy efficiency and energy efficiency grades for power transformers
- GB/T 32825-2024Technical parameters and requirements for three-phase dry-type tridimensional wound core power transformers
- GB/T 17468-2019Guide for choice power transformers
- RB/T 017-2019Evaluation methods and requirements of low carbon products - Three-phase distribution transformers
- SN/T 3248.2-2017Technical requirements for the inspection of general complete equipment to import - Part 2: Energy-saving power transformers
- NB/T 42066-2016Specification and technical requirements for 6 kV to 35 kV dry-type aluminum winding power transformers
Similar standards
Editions of GB/T 22072
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 22072-2018 | Specifications and technical requirements for dry-type amorphous alloy core distribution transformers | current edition | Current |
| GB/T 22072-2008 | Specifications and technical requirements for dry-type amorphous alloy core distribution transformers | previous edition | Superseded |
This page sells the current edition, GB/T 22072-2018. Earlier editions are listed for reference only.
How to Download GB/T 22072-2018
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 1094.1-2013 — Power transformers-Part 1: General
GB/T 1094.10-2022 — Power transformers - Part 10: Determination of sound levels
GB/T 1094.101-2023 — Power transformers - Part 101: Determination of sound levels - Application guide
Secure payment via Stripe
Payments accepted
GB/T 22072-2018