GB/T 21087-2020Energy recovery ventilators for outdoor air handling (English PDF)

热回收新风机组

Preview PDF

This is a limited preview

Buy now to download the full PDF (70 pages)

Need quotation for your management?

Get a formal quotation for GB/T 21087-2020 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

September 29, 2020

Implementation date

August 1, 2021

Scope

GB/T 21087-2020 is the English-translated version of 热回收新风机组.

GB/T 21087-2020 is the Chinese standard for energy recovery ventilators for outdoor air handling. It gives the terms and definitions, the classification and marking, the structure and materials, the requirements, the test methods, the inspection rules and the provisions on marking, packaging, transport and storage.

It applies to fresh air and exhaust ventilation units that recover energy from the exhaust air. Ventilation equipment makers, HVAC designers and test laboratories use it.

Issued on 29 September 2020, it has applied since 1 August 2021, replacing GB/T 21087-2007.

Found what you need?

Document preview — GB/T 21087-2020

National Standard of the People's Republic of China

ICS
91.140.30
Classification
P 46
Replacing
GB/T 21087-2007

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword3
  • 1 Scope6
  • 2 Normative references6
  • 3 Terms and definitions7
  • 4 Classification and marking11
  • 5 Structure and materials13
  • 6 Requirements14
  • 7 Test method17
  • 8 Inspection rules23
  • 9 Marking, packaging, transportation, storage25
  • Appendix A (Normative) Test methods for air volume, static pressure loss, available pressure, input power28
  • Appendix B (Normative) Field test method of heat recovery performance37
  • Appendix C (Normative) Test method of internal exhaust air leakage ratio38
  • Appendix D (Normative) Test method of external air leakage ratio41
  • Appendix E (Normative) Test method for net outdoor air volume and net outdoor airflow ratio in supply air44
  • Appendix F (Normative) Test methods for exchange effectiveness, energy efficiency coefficient, energy recovery ratio51
  • Appendix G (Normative) Performance test method of reciprocating heat recovery unit57
  • Appendix H (Normative) Test method of condensation and condensed water64
  • Appendix I (Normative) Noise test method65
  • Appendix J (Normative) Alternating performance test method70

1 Scope

This standard specifies the classification and marking, structure and materials, requirements, test methods, inspection rules, marking, packaging, transportation and storage of energy recovery ventilators for outdoor air handling.

This standard applies to fresh exhaust ventilation units, that recover exhaust energy in heating, ventilation, air conditioning and purification systems and pre-treat outdoor air with cooling, heating, humidity, filtration.

2 Normative references

The following documents are essential to the application of this document. For the dated documents, only the versions with the dates indicated are applicable to this document; for the undated documents, only the latest version (including all the amendments) is applicable to this standard.

GB/T 755-2019 Rotating electrical machines - Rating and performance

GB/T 1236-2017 Industrial fan - Performance testing using standardized airways

GB/T 2423.3 Environmental testing - Part 2: Testing method - Test Cab. Damp heat, steady state

GB/T 3785.1-2010 Electroacoustics - Sound level meters - Part 1: Specifications

GB 4706.1-2005 Household and similar electrical appliances - Safety - Part 1. General requirements

GB 8624 Classification for burning behavior of building materials and products

GB/T 9068 Determination of sound power levels for noise emitted by heating, ventilating and air conditioning equipments - Engineering method

GB/T 14295 Air filter

GB/T 14296 Air cooling and air heating coils

3 Terms and definitions

The terms and definitions as defined in GB/T 16803, as well as the following terms and definitions, apply to this document.

3.1 Energy recovery ventilators for outdoor air handling; ERV

Equipment that uses a sensible heat or total energy recovery component as the core and drives the air flow through a fan to achieve outdoor air to exhaust air energy recovery and outdoor air filtration.

3.2 Energy recovery components; ERC

Heat exchange components that achieve sensible heat or total heat energy exchange between air and air.

3.3 Total heat exchange

Energy exchange in which sensible heat and latent heat conversion occur simultaneously.

3.4 Sensible heat exchange

Energy exchange in which only sensible heat conversion occurs.

3.5 Standard air

Air with an atmospheric pressure of 101.3 kPa, a dry bulb temperature of 20 °C, a wet bulb temperature of 15.8 °C, a density of 1.2 kg/m³.

3.6 Outdoor air

Outdoor air entering from the outdoor air inlet.

4 Classification and marking

4.1 Classification

4.1.1 The code for the energy recovery ventilators for outdoor air handling is "ERV"; the code for the energy recovery components for outdoor air handling is "ERC".

4.1.2 The classification and corresponding codes of ERV and ERC are shown in Table 1.

4.2 Marking

4.2.1 ERV marking

Example:

An energy recovery ventilators for outdoor air handling with a rated air supply of 300 m³/h, total heat, hanging type, rotary type, non-flame retardant and ordinary antibacterial, is marked as.

4.2.2 ERC marking

Example:

5 Structure and materials

5.1 ERV and ERC shall be manufactured according to drawings and technical documents.

5.2 The interior of ERV and ERC shall be clean and free of debris.

5.7 The fireproof characteristics of flame-retardant ERC shall meet the relevant requirements of GB 50016; it shall be graded according to the relevant requirements of GB 8624.

5.8 The line connection of ERV and ERC shall be neat and firm; it shall have reliable grounding. The wire penetration and plug shall use insulating sleeves or other protective measures; the exposed wires outside the shell should be protected by metal hoses.

5.9 Electrical control components shall be sensitive and reliable.

5.10 For ERV or ERC with inspection doors, the inspection doors shall be tight and flexible; the inspection passage doors accessible to personnel shall be open both inside and outside.

5.11 ERV shall ensure that condensate can be removed smoothly during heat exchange.

5.12 The surface air cooler and heater configured for ERV shall meet the relevant requirements of GB/T 14296.

5.14 Antibacterial ERC shall meet the relevant requirements of GB 21551.2.

5.15 ERV should be equipped with energy-saving operation controller. Under the condition of meeting the requirements of outdoor air exhaust air distribution volume, the ERV energy consumption can be reduced, by adjusting the fan speed, bypassing the outdoor air exhaust, etc.

5.16 Independently installed ERV outdoor air inlet and exhaust outlet shall be equipped with insulated and sealed air valves.

6 Requirements

6.1 Appearance

The outer surface of the unit shall be smooth and the color shall be consistent, without obvious scratches, rust spots, indentations, flow marks, bubbles, peeling. Various logos and nameplates affixed to the outer surface shall be firm; the position shall be obvious.

6.5 Static pressure loss

The measured value of the static pressure loss on the outdoor air side and exhaust side of the ERC shall not be greater than 105% of the rated value.

6.6 Input power

For units with a rated input power not exceeding 30 W, the measured value of the input power shall not be greater than 120% of the rated value; for units with a rated input power exceeding 30 W, the measured value of the input power shall not be greater than 110% of the rated value.

6.11 Exchange effectiveness

The measured value of the exchange effectiveness shall not be less than 90% of the rated value, meanwhile it shall meet the requirements of Table 2.

6.23 Outdoor air PM2.5 filtration efficiency

The measured value of the outdoor air PM2.5 filtration efficiency of ERV shall not be less than 95% of the rated value.

6.24 Alternating performance

The test results of the air volume and pressure, net outdoor airflow ratio in supply air and heat exchange effectiveness under high air volume of ERV or ERC, after the alternating performance test, shall not deviate by more than 3%, as compared with those before the alternating performance test; meanwhile it shall meet the requirements of Table 2.

7 Test method

7.1 Test conditions

7.1.1 The ERV and ERC under test shall meet the requirements of Chapter 5.

7.1.2 The ERV and ERC under test shall be tested according to the rated voltage and rated frequency on the nameplate.

7.1.3 The rated performance test conditions of the ERV and ERC under test shall comply with the provisions of Table 3.

7.1.4 The allowable deviation of the readings during the test shall comply with the provisions of Table 4.

7.2 Appearance

The appearance of the tested ERV and ERC shall be inspected visually.

7.3 Startup and operation

7.3.1 During type inspection, adjust the input voltage of ERV/ERC (when applicable) to 90% of the rated voltage; start at rated air volume or rated speed; run stably for 10 minutes; cut off the power supply; stop running; repeat 3 times; check whether the parts are loose, noisy, overheated or have other abnormal phenomena.

7.3.2 During exit-factory inspection, start ERV or ERC at rated voltage; run stably at maximum air speed or maximum speed; check whether the parts are loose, noisy, overheated or have other abnormal phenomena.

7.4 Air volume

7.7 Input power

7.7.1 Measure the input power corresponding to the ERV and ERC (when applicable) according to the test method specified in Appendix A and the test conditions specified in Table 3.

7.7.2 Measure the input power corresponding to the ERV and ERC (when applicable) installed on site, according to the test method specified in Appendix B.

7.8 Internal exhaust air leakage ratio

Measure the internal exhaust air leakage ratio, according to the test method specified in Appendix C and the test conditions specified in Table 3.

7.9 External air leakage ratio

Measure the external air leakage ratio, according to the test method specified in Appendix D and the test conditions specified in Table 3.

7.13 Energy efficiency coefficient

Measure the energy efficiency coefficient of ERV according to the test method specified in Appendix F and the test conditions specified in Table 3.

7.14 Energy recovery ratio

Measure the energy recovery ratio of ERC according to the test method specified in Appendix F and the test conditions specified in Table 3.

7.15 Condensation and condensed water

8 Inspection rules

8.1 Inspection classification

Inspection is divided into exit-factory inspection, sampling inspection, type inspection.

8.2 Exit-factory inspection

8.2.1 Each ERV or ERC must pass the manufacturer's inspection before it can be shipped.

8.4 Type inspection

8.4.1 Type inspection shall be carried out in any of the following situations.

8.4.2 Type inspection shall be carried out according to the items specified in Table 6.

8.5 Judgment rules

8.5.1 For exit-factory inspection, sampling inspection, type inspection, as long as one unit fails one of the items specified in Table 6, the batch of products shall be judged as unqualified.

8.5.2 For type inspection, if one of the electrical safety items 16, 17, 18, 19, 20, 21, 22 specified in Table 6 fails, the products of the production cycle shall be judged as unqualified.

9 Marking, packaging, transportation, storage

9.1 Marking

9.1.1 Each ERV and ERC shall have a nameplate and shall be fixed in a conspicuous position.

9.1.2 The following contents shall be clearly marked on the nameplate.

9.1.3 For products manufactured in accordance with the standard, the performance values marked on the nameplate shall be the values declared by the manufacturer under standard air conditions and standard test conditions; the performance values under non-standard working conditions may be marked in the sample or contract of the manufacturer. When marked on the nameplate, the "nominal value" and the corresponding environmental conditions shall be indicated.

9.4 Accompanying technical documents

The accompanying technical documents shall include at least the following. […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 70 pages — is available in the English PDF.

Referenced standards

Cited by

Similar standards

Editions of GB/T 21087

EditionTitleRevisionStatus
GB/T 21087-2020Energy recovery ventilators for outdoor air handlingcurrent editionCurrent
GB/T 21087-2007Energy recovery ventilators for outdoor air handlingprevious editionSuperseded

This page sells the current edition, GB/T 21087-2020. Earlier editions are listed for reference only.

How to Download GB/T 21087-2020

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
70 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 21087-2020

$530.00