Scope

GB/T 15284-2022 is the English-translated version of 多费率电能表 特殊要求.

GB/T 15284-2022 sets the particular requirements for multi-rate electricity meters, meters that hold several energy registers and bill by rate plan.

It classifies them by how they are connected and what they measure, by accuracy class, by whether the rate plan sits in the meter or in a remote billing system, and by whether they measure in both directions.

It then gives the standard values of voltage, current, frequency and power consumption, the functional, mechanical, climatic, electrical and metrological requirements, and the matching test methods, inspection rules, marking, documentation, packaging and storage.

It applies to newly made meters for 50 Hz or 60 Hz networks up to 600 V whose time switch has a digital display, not to analogue dial or electromechanical meters.

It replaces GB/T 15284-2002, was issued on 15 April 2022 and has applied since 1 November 2022.

Found what you need?

Document preview — GB/T 15284-2022

National Standard of the People's Republic of China

ICS
17.220.20
Classification
N22
Replacing
GB/T 15284-2002

Issued by: State Administration for Market Regulation; Standardization Administration of China

Contents

  • Foreword3
  • 1 Scope6
  • 2 Normative references6
  • 3 Terms and definitions7
  • 4 Classification9
  • 4.1 According to the way of access to the circuit and the type of electricity measured9
  • 4.2 According to the level of accuracy of measuring electricity9
  • 4.3 According to where the rate plan is set10
  • 4.4 According to with or without the function of bidirectional measurement of electricity10
  • 5 Standard power value10
  • 5.1 Voltage10
  • 5.2 Current10
  • 5.3 Frequency10
  • 5.4 Power consumption10
  • 6 Technical requirements11
  • 6.1 Functional requirements11
  • 6.2 Mechanical and structural requirements12
  • 6.3 Climatic conditions14
  • 6.4 External effect14
  • 6.5 Metrological performance protection requirements14
  • 6.6 Electrical requirements14
  • 6.7 Metrological performance requirements16
  • 7 Test methods18
  • 7.1 Function inspection18
  • 7.2 Mechanical and structural tests18
  • 7.3 Climate impact test19
  • 7.4 External effect test19
  • 7.5 Metrological performance protection test19
  • 7.6 Electrical test19
  • 7.7 Metrological performance test21
  • 8 Inspection rules21
  • 9 Meter identification and documentation22
  • 10 Packaging and storage22
  • Annex A (normative) Test items for multi-rate electricity meters23

1 Scope

This Standard specifies the terms and definitions, technical requirements, test methods, inspection rules, identification and documentation, packaging and storage for multi-rate electricity meters hereinafter referred to as "the meters".

This Standard applies to newly manufactured meters for measuring and controlling electricity in a 50Hz or 60Hz grid with a voltage not exceeding 600V. This Standard is only applicable to the meters whose time switch is digital display and use battery or capacitor as working reserve.

This Standard does not apply to meters whose time switch is an analog dial, nor does it apply to electromechanical meters.

2 Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

GB/T 2423.5-2019, Environmental testing - Part 2: Test methods - Test Ea and guidance: Shock

GB/T 2423.43-2008, Environmental testing for electric and electronic products - Part 2: Test methods - Mounting of specimens for vibration, impact and similar dynamic tests

GB/T 2423.56-2018, Environmental testing - Part 2: Test methods - Test Fh: Vibration, broadband random and guidance

GB/T 2900.77-2008, Electrotechnical terminology - Electrical and electronic measurements and measuring instruments - Part 1: General terms relating to measurements

GB/T 13384-2008, General specifications for packing of mechanical and electrical product

GB/T 16935.1-2008, Insulation coordination for equipment within low-voltage systems - Part 1: Principles, requirements and tests

GB/T 17215.211-2021, Electricity metering equipment (AC) - General requirements, tests and test conditions - Part 11: Metering equipment

GB/T 17215.321-2021, Electricity metering equipment (AC) - Particular requirements - Part 21: Static meters for active electricity (classes A, B, C, D and E)

GB/T 17215.323-2008, Electricity metering equipment (a.c.) - Particular requirements - Part 23: Static meters for reactive electricity (classes 2 and 3)

GB/T 17215.324-2017, Electricity metering equipment (a.c.) - Particular requirements - Part 24: Static meters for reactive electricity at fundamental frequency (classes 0.5S, 1S and 1)

JJF 1245.2-2019, Program of Pattern Evaluation of Fixed AC Electricity Meters - Software Requirements

DL/T 1490-2015, Functional specification for smart electricity meters

IEC 62052-31:2015, Electricity metering equipment (AC) - General requirements, tests and test conditions - Part 31: Product safety requirements and tests

3 Terms and definitions

For the purposes of this document, the terms and definitions defined in GB/T 17215.211-2021, GB/T 2900.77-2008, DL/T 1490-2015 as well as the followings apply.

3.1 Multi-rate electricity meter

A meter that has one or more electricity registers and the rate plan is set in the local meter or on the remote billing system side.

NOTE: The rate plan is set in the meter or in the remote billing system. It works on time or consumption baselines, or via external control signals. [Source: GB/T 17215.211-2021, 3.1.7, with modifications]

3.2 Static multi-rate electricity meter

A meter that the measurement unit produces an output proportional to the electricity by applying current and voltage to a solid-state (electronic) device, and its rate electricity metering function is realized by electronic circuit or remote billing system.

3.3 Local static multi-rate electricity meter

A meter that the rate plan is set in the meter, the meter records the electricity data of each rate according to the rate plan and stores it in the corresponding register.

4 Classification

- According to the accuracy of reactive electricity: 0.5S, 1S, 1, 2 and 3.

4.3 According to where the rate plan is set

According to where the rate plan is set, it is divided into:

- Local static multi-rate electricity meter;

- Remote static multi-rate electricity meter.

4.4 According to with or without the function of bidirectional measurement of electricity

According to with or without the function of bidirectional measurement of electricity, it is divided into:

- Bidirectional multi-rate electricity meter;

- One-way multi-rate electricity meter.

5 Standard power value

5.1 Voltage

The nominal voltage and voltage range shall comply with the provisions of 4.1 in GB/T 17215.211-2021.

5.2 Current

For active meters, the current shall comply with the provisions of 4.2 in GB/T 17215.321-2021. For reactive meters, the current shall comply with the provisions of Chapter 4 in GB/T 17215.323-2008 and Chapter 4 in GB/T 17215.324-2017.

5.3 Frequency

It shall comply with the provisions of 4.3 in GB/T 17215.211-2021.

5.4 Power consumption

It shall comply with the provisions of 4.4 in GB/T 17215.211-2021.

6 Technical requirements

6.1 Functional requirements

6.1.1 Basic functions

Unless otherwise specified, under normal operating conditions, the design of the meter shall meet the following requirements:

- The clock has calendar, timing, leap year automatic conversion function;

- It has the function of time being calibrated;

- The date and time are set with security measures to prevent operations by unauthorized persons;

- If the power outage time misses the freezing time, it has a supplementary freezing mechanism when the power is turned on;

- It supports the setting of rates and time intervals for holidays and special days;

- It records the date of the last 10 programming and the total number of programming;

- It records the tiered electricity for different electricity price tiers.

6.1.2 Local meter functions

Unless otherwise specified, under normal operating conditions, local meters shall be designed to meet the following requirements:

- At least 14 time intervals can be set arbitrarily within 24h (minimum interval is 5min). Time interval can be set across zero;

- At least 4 rate registers are supported. Each register records power data at a specified time corresponding to different rates;

- Store at least the last two months or the last two billing cycles of total electricity and electricity data of each rate. It can be read out through the data communication interface. The data storage boundary time is the end of the month or other (1st to 28th) designated days;

- Record the total electricity and the number of times each rate register is cleared and the data before clearing;

- It can process the rate parameter form or other electricity price contract parameters remotely issued by the master station. Locally realize rate management and electricity price contract update.

6.2 Mechanical and structural requirements

6.2.4 Seal regulations

It shall comply with the provisions of 5.4 in GB/T 17215.211-2021.

6.2.5 Display of measured values

It shall comply with the provisions of 5.5 in GB/T 17215.211-2021.

For local meters, the indicating display shall show the current effective rate. The measured value indication of each rate register shall be read locally, and each rate register clearly identified.

For remote meters, the indicating display shall support the display of electricity data recorded at predetermined time intervals.

6.2.6 Storage of measured values

It shall comply with the provisions of 5.6 in GB/T 17215.211-2021.

6.2.7 Output

It shall comply with the provisions of 5.7.1, 5.7.2.1, 5.7.2.2, 5.7.3.1 in GB/T 17215.211-2021.

6.2.8 Electrical pulse input

It shall comply with the provisions of 5.8.1 in GB/T 17215.211-2021.

6.2.9 Work indicator

It shall comply with the provisions of 5.9 in GB/T 17215.211-2021.

6.2.10 Protection against mechanical hazards

The meter shall not present a mechanical hazard under normal operating conditions.

The protection test against mechanical hazards shall be carried out according to 7.2 of IEC 62052-31:2015.

6.2.11 Measures to protect the connection

The requirements for the protective earth terminal shall comply with the provisions of 6.5.2.3 in IEC 62052-31:2015. The protective connection impedance requirements of permanently connected equipment shall comply with the provisions in 6.5.2.4 of IEC 62052-31:2015.

6.2.12 Flame spread prevention

It shall comply with the provisions of 9.3.2.1 in IEC 62052-31:2015.

6.2.13 Instrument temperature limits and heat resistance
6.2.13.1 Surface temperature limits to prevent burns

When the ambient temperature is 40°C, the temperature of the easy-to-contact surface of the meter shall not exceed the value given in 1) in Table 31 of IEC 62052-31:2015 under normal conditions.

When the ambient temperature exceeds 40°C, the temperature of the easy-to-contact surface of the meter is allowed to exceed the value given in 1) in Table 31 of IEC 62052-31:2015. However, the excess value is not greater than the difference between the ambient temperature and 40°C.

The surface of the terminal box covered by the terminal cover, or the surface of the board-mounted instrument protected by the fence, is not regarded as an accessible surface.

6.2.13.2 Temperature limits for terminals

When the ambient temperature is 40°C, the temperature of the terminal shall not exceed the value given in Table 32 of IEC 62052-31:2015 under normal conditions.

When the ambient temperature exceeds 40°C, the temperature of the terminal is allowed to exceed the value given in Table 32 of IEC 62052-31:2015. However, the excess value is not greater than the difference between the ambient temperature and 40°C.

6.3 Climatic conditions

It shall comply with the provisions of 8.1, 8.2 and 8.3 in Chapter 8 of GB/T 17215.211-2021.

6.4 External effect

It shall comply with the provisions of 9.1, 9.2, 9.3.1 and 9.4.1 in Chapter 9 of GB/T 17215.211-2021.

6.5 Metrological performance protection requirements

It shall comply with the provisions of Chapter 10 of GB/T 17215.211-2021.

NOTE: Class I protective equipment requires a protective earth terminal.

6.6 Electrical requirements

6.6.1 Clearance and creepage distances

meter shall not exhibit flashover, destructive discharge or breakdown. After the test, the meter shall be free from mechanical damage and work correctly.

NOTE: Unom is the nominal voltage between line and neutral.

6.6.3 Dielectric strength
6.6.3.1 Pulse voltage

Apply the pulse voltage specified in 6.10.2.3 of IEC 62052-31:2015. The meter shall not exhibit flashover, destructive discharge or breakdown. After the test, the meter shall be free from mechanical damage and work correctly.

6.6.3.2 AC power frequency voltage

Apply the AC power frequency voltage specified in 6.10.2.5 of IEC 62052-31:2015. The meter shall not exhibit flashover, destructive discharge or breakdown. After the test, the meter shall be free from mechanical damage and work correctly.

6.6.4 Voltage interruption effects
6.6.4.1 Effect of voltage interruption on the meter
6.6.4.1.1 Voltage interruption effects of local meters

During the period when the power supply voltage interruption does not exceed the working reserve, when the power supply is restored, the meter shall correctly store the data (if any) at the end of the month or the specified day.

6.6.4.1.2 Voltage interruption effects of remote meters

During the period when the power supply voltage interruption does not exceed the working reserve, when the power supply is restored, the meter shall be able to refreeze the data of the next freezing point at the time of power-off and the data of the previous freezing point at the time of power-on.

6.6.4.2 Effect of voltage interruption on clock

During the period when the power supply voltage interruption does not exceed the working reserve, the meter clock shall maintain the specified accuracy when power is restored. When power is restored to the meter, the meter's clock and calendar shall not be confused.

6.7 Metrological performance requirements

6.7.1 Meter constants

The relationship between the test output and the indicated value of the indicating display shall conform to the constant value of the meter.

6.7.2 No-load condition (creeping)

Current circuit opens. Voltage circuit applies 1.1Unom voltage. Within the specified test time limit, the test output of the meter shall not generate more than one pulse.

6.7.3 Startup

The meter shall startup at the startup current of Ist (polyphase meter with balanced load) specified in relevant standards such as GB/T 17215.321-2021, GB/T 17215.323-2008,

GB/T 17215.324-2017 and when the power factor (or sinphi) is 1. Continuously record electricity.

6.7.4 Basic maximum allowable error (initial inherent error)

It shall comply with the provisions of 7.6 in GB/T 17215.321-2021, 8.1 in GB/T 17215.323-2008 and 8.2 in GB/T 17215.324-2017.

6.7.5 Repeatability

The same measured signal under the same measurement conditions shall produce nearly consistent continuous measurement results.

6.7.6 Variation requirements

The absolute value of the maximum error change between adjacent test results shall comply with the provisions of GB/T 17215.321-2021 for the meters of various accuracy levels.

6.7.7 Load current rise and fall

The basic error of the meter is tested twice in the order of load current from small to large, and then from large to small. The absolute value of the error change of the same sample at the same load point shall comply with the provisions of GB/T 17215.321-2021.

6.7.8 Error consistency

The deviation between the test error of the meter under test and the average value of the error at the same test point shall comply with the provisions of GB/T 17215.321-2021 for the meters of various accuracy levels.

6.7.9 Electricity indication error

Only a single rate register (other than the total register) is valid for a local meter at any time. The sum of the recorded values in each multi-rate register shall equal the recorded value of the total register. It is not appropriate to calculate the recorded value of the total register by arithmetically adding the recorded value of each rate register. […]

7 Test methods

7.2 Mechanical and structural tests

The surface temperature limit of the meter to prevent burns and the temperature limit test of the meter terminals shall be carried out in accordance with the provisions of 10.4 in IEC 62052-31:2015.

7.2.2 Output test

The functional test of the optical test output shall be carried out in accordance with the provisions of 5.7.2.3 in GB/T 17215.211-2021. The functional test of electric pulse output shall be carried out in accordance with the provisions of 5.7.4.2 in GB/T 17215.211-2021.

7.2.3 Electrical pulse input test

The functional test of electric pulse input shall be carried out in accordance with the provisions of 5.8.2 in GB/T 17215.211-2021.

7.3 Climate impact test

It shall be carried out in accordance with the provisions of Chapter 8 of GB/T 17215.211-2021.

7.4 External effect test

It shall be carried out in accordance with the provisions of Chapter 9 of GB/T 17215.211-2021.

7.5 Metrological performance protection test

Check the identification and documentation of meter legal related software. Adopt document analysis and software feature function test device. Carry out in accordance with the provisions of Chapter 9 of JJF 1245.2-2019.

7.6 Electrical test

7.6.1 Power consumption test

The power consumption shall be under the reference conditions given in 7.1 of GB/T 17215.211-2021. The reference voltage and reference current shall be applied to the voltage loop and the electricity meter. Turn the meter backlight off. Measure active and apparent power consumption of voltage lines. Apply reference voltage and reference current to the current loop and electricity meter. Turn the meter backlight off. Measure the apparent power consumption of each current line.

7.6.2 Measurement of clearance and creepage distances

It shall be carried out in accordance with the provisions of 6.2 in GB/T 16935.1-2008.

7.6.3 Electrical test procedures

The electrical test procedures related to safety shall be carried out in accordance with the provisions of 11.2 in GB/T 17215.321-2021.

7.6.4 Withstand long-term overvoltage test

Carry out in accordance with the provisions of 6.10.3.2 in IEC 62052-31:2015.

7.6.5 Dielectric strength test
7.6.5.1 Humidity pretreatment

It shall be carried out in accordance with 6.10.4.2 of IEC 62052-31:2015.

7.6.5.2 Test method and test equipment preparation

The dielectric strength test shall be carried out in accordance with the provisions of 6.10.4.3.1 in IEC 62052-31:2015. The test equipment preparation shall meet the requirements of 6.10.4.3.2 in IEC 62052-31:2015.

7.6.5.3 Impulse voltage test

It shall be carried out in accordance with the provisions of 6.10.4.3.3 in IEC 62052-31:2015. The test voltage meets the requirements of Table 7 in IEC 62052-31:2015.

7.6.5.4 AC power frequency voltage test

It shall be carried out in accordance with the provisions of 6.10.4.3.4 in IEC 62052-31:2015. The test voltage meets the requirements of Table 11 in IEC 62052-31:2015.

7.6.6 Voltage interruption effect test
7.6.6.1 Effect test of voltage interruption on meter
7.6.6.1.1 Voltage interruption effects of local meters

The test is carried out under the following conditions:

- Nominal voltage;

- The clock and calendar of the meter are set at 23:50 at the end of the month (or the day before the specified day);

- After reading the current value and stored value of the meter, interrupt the supply voltage;

- After 30min, restore the power supply. Immediately read the current value and […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 26 pages — is available in the English PDF.

Referenced standards

Normative references

GB/T 2900.77-2008 · JJF 1245.2-2019 · DL/T 1490-2015 · IEC 62052-31:2015

Similar standards

Editions of GB/T 15284

EditionTitleRevisionStatus
GB/T 15284-2022Multi-rate electricity meters - Particular requirementssecond revisionCurrent
GB/T 15284-2002Multi-rate electricity meters - Particular requirementsfirst revisionSuperseded
GB/T 15284-1994Multi-rate electricity meters - Particular requirementsfirst issueSuperseded

This page sells the current edition, GB/T 15284-2022. Earlier editions are listed for reference only.

How to Download GB/T 15284-2022

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
26 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 15284-2022

$275.00