GB/T 36050-2018Rules of time synchronization for power systems (English PDF)
电力系统时间同步基本规定
This is a limited preview
Buy now to download the full PDF (15 pages)
Need quotation for your management?
Get a formal quotation for GB/T 36050-2018 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
March 15, 2018
Implementation date
October 1, 2018
Scope
GB/T 36050-2018 is the English-translated version of 电力系统时间同步基本规定.
GB/T 36050-2018 sets the rules for time synchronization in power systems, covering the terms, general rules, construction requirements and operation management of the time synchronization system.
It applies to planning, design, construction and operation at dispatch centres, transformer substations, power generation plants and on the users' side.
Dispatch centres, substations and power plants must each have a unified system with a duplicated, redundant master clock; NTP is preferred for dispatch centres and station-level equipment, while bay and process level, measurement-control and protection equipment use IRIG-B codes or PTP messages, preferably IRIG-B. The devices must monitor their own synchronization state, and the system must meet the provisions on the security protection of electric power monitoring systems.
Operation follows unified management and hierarchical maintenance. It was issued on 15 March 2018 and has applied since 1 October 2018.
Found what you need?
Document preview — GB/T 36050-2018
National Standard of the People's Republic of China
- ICS
- 29.240.01
- Classification
- F 20
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword3
- 1 Scope4
- 2 Normative references4
- 3 Terms and definitions4
- 4 Abbreviations5
- 5 General rules5
- 6 Construction requirements6
- 7 Operation management specifications6
1 Scope
This Standard specifies the terms and definitions, general rules, construction requirements, operation management specifications for the time synchronization system for power systems.
This Standard applies to the planning, design, construction and operation management of the time synchronization system for power systems' dispatchers, transformer substations, power generation plants and power systems on the users' side.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition dated applies to this document. For undated references, the latest edition of the referenced documents (including all amendments) applies to this document.
DL/T 1100.1, Time synchronism systems of power system - Part 1. Technical specifications
Provisions on the security protection of the electric power monitoring systems (Order no. 14 of the National Development and Reform Commission)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 Time synchronization system for power system
System which provides standard time signals for all kinds of application systems and equipment of power systems.
NOTE: The time synchronization system for power systems consists of clock source, master clock, slave clock, transmission medium and so on.
5 General rules
5.6 The devices in the time synchronization system for power systems shall have the time synchronization state monitoring management function.
5.7 The time synchronization system for power systems shall be as required by the Provisions on the security protection of the electric power monitoring systems.
6 Construction requirements
6.1 Dispatchers shall be equipped with a unified time synchronization system; the master clock is of a duplicated redundancy configuration; the NTP method is preferably used for the time synchronization of all application systems and equipment of dispatchers.
6.2 Transformer substations shall be equipped with a unified time synchronization system; the master clock is of a duplicated redundancy configuration. The equipment of station level is preferably synchronized using the NTP method; the equipment of bay level and process level is synchronized using IRIG-B codes or PTP messages, preferably IRIG-B codes.
6.3 Power generation plants shall be equipped with a unified time synchronization system; the master clock is of a duplicated redundancy configuration. The background of production control system is preferably synchronized using the NTP method; the equipment such as measurement-control and protection shall be synchronized using IRIG-B codes or PTP messages, preferably IRIG-B codes.
6.4 The power users' side shall be provided with the time synchronization function in relevant equipment in accordance with the technical requirements for time synchronization for power use, electric power measurement and so on.
7 Operation management specifications
7.1 Basic requirements
The operation management of the synchronization system for power systems shall follow the principles of unified management and hierarchical maintenance. All dispatchers, transformer substations, power generation plants and users shall carry out the operation and maintenance of the time synchronization system based on the principle requirements and actual conditions on site.
7.2 Dispatchers
The basic requirements for the time synchronization system management of dispatchers at all levels are as follows. […]
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
Cited by
- GB/T 28583-2025Specification of electricity supply service
- GB/T 45906.9-2025Substation secondary system - Part 9: Construction specifications
- GB/T 46810-2025Technical requirements for the security protection of power time synchronization systems based on the BeiDou navigation satellite system
- GB/T 44360-2024Wind energy generation systems - Technical specification for data acquisition of smart wind farm
- GB/T 44908-2024Safety requirements and evaluation methods for technical transformation of wind farm
- GB/T 40600-2021Technical requirements for dispatching function of wind farm power control system
Similar standards
How to Download GB/T 36050-2018
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
DL/T 1100.1-2018 — Time synchronism systems of power system - Part 1: Technical specifications
GB/T 10003-2026 — Biaxially oriented polypropylene (BOPP) film
GB/T 10004-2026 — Plastic/Plastic laminated films and pouches for packaging
Secure payment via Stripe
Payments accepted
GB/T 36050-2018
$55.00