Scope

GB/T 33593-2017 is the English-translated version of 分布式电源并网技术要求.

GB/T 33593-2017 sets the general principles and the technical requirements to be followed when distributed generation is designed, built and operated on the grid.

It covers power quality, power control and voltage regulation, starting and stopping, operational adaptability, safety, relay protection and safety automatic devices, communication and information, energy metering and grid connection testing, with an informative annex of connection point schematics.

It defines distributed resources as synchronous and asynchronous generators and converter-based plant close to the user, including solar, gas, biomass, wind, water, hydrogen, geothermal, ocean and storage.

Safety clauses fix the switching device at the connection point and the warning signs of GB 2894, separately for 380 V and for 10 (6) kV to 35 kV. It applies at 35 kV and below. Issued on 12 May 2017, it has applied since 1 December 2017.

Found what you need?

Document preview — GB/T 33593-2017

National Standard of the People's Republic of China

ICS
29
Classification
F 21

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword3
  • 1 Scope4
  • 2 Normative references4
  • 3 Terms and definitions5
  • 4 Power quality6
  • 5 Power control and voltage regulation7
  • 6 Start and stop9
  • 7 Operational adaptability9
  • 8 Safety11
  • 9 Relay protection and safety automatic device11
  • 10 Communication and information13
  • 11 Energy metering14
  • 12 Power grid connection testing14
  • Appendix A (Informative) Schematics of power grid connection point and point of common coupling16

Foreword

This standard was drafted in accordance with the rules given in GB/T 1.1-2009.

1 Scope

This standard specifies the general principles and technical requirements that shall be followed in the design, construction and operation of grid connection of distributed resources.

This standard applies to the newly built, reconstructed, and extended distributed power resources which are connected into the power grid via the 35 kV and below voltage level.

2 Normative references

The following documents are essential to the application of this document. For the dated documents, only the versions with the dates indicated are applicable to this document; for the undated documents, only the latest version (including all the amendments) are applicable to this Standard.

GB 2894 Safety signs and guideline for the use

GB/T 12325 Power quality - Deviation of supply voltage

GB/T 12326 Power quality - Voltage fluctuation and flicker

GB 14050 Types and safety technical requirements of system earthing

GB/T 14285 Technical code for relaying protection and security automatic equipment

GB/T 14549 Quality of electric energy supply - Harmonics in public supply network

GB/T 15543 Power quality - Three-phase voltage unbalance

GB/T 15945 Power quality - Frequency deviation for power system

GB/T 19862 General requirements for monitoring equipment of power quality

GB/T 24337 Power quality - Interharmonics in public supply network

GB 50065 Code for grounding design of AC electrical installations

DL/T 448 Technical administrative code of electric energy metering

DL/T 584 Code for setting of 3kV ~ 110kV relaying protection equipment

DL/T 621 Grounding for AC electrical installations4

DL/T 634.5101 Telecontrol equipment and systems - Part 5-101. Transmission protocols - Companion standard for basic telecontrol tasks

DL/T 634.5104 Telecontrol equipment and systems - Part 5-104.

Transmission protocols - Network access for IEC 60870-5-101 using standard transport profiles

3 Terms and definitions

The following terms and definitions apply to this document.

3.1 Distributed resources

It refers to the resources which are connected to the power grid of 35 kV and below voltage level, located close to the user, AND mainly consumed locally at 35 kV and below voltage level, which includes synchronous generators, asynchronous generators, converters, and other types of resources.

Note: It includes solar energy, natural gas, biomass energy, wind energy, water energy, hydrogen energy, geothermal energy, ocean energy, comprehensive utilization of resources (including coal mine gas power generation), and energy storage and other types.

3.2 Converter

It refers to an electrical device for converting electrical power into one or more types of electrical powers that is suitable for use by the power grid or user.

Note: The converter includes rectifiers, inverters, AC converters, and DC converters.

3.3 Converter-type power supply

It refers to the power supply which is connected to the power grid totally or partially through the converter.

3.4 Synchronous-machine-type power supply

8 Safety

8.1 General requirements

8.1.1 The grounding mode of the distributed resource shall be compatible with the grounding mode at the power distribution network side, AND it shall comply with the requirements of personal & equipment safety, protection, and coordination.

8.1.2 As for the distributed resources connected to the power grid through the 380 V voltage level, it shall install a switch at the power grid connection point which is easy to operate, have obvious on/off indication, AND have the fault current on/off capability.

8.1.3 As for the distributed resources connected to the power grid through the 10 (6) kV ~ 35 kV voltage level, it shall install a switching equipment at the power grid connection point which is easy to operate, can be locked, have apparent on/off point, have grounding function, AND have the fault current on/off capability.

8.2 Safety signs

8.2.1 As for the distributed resources connected to the power grid through the 380 V voltage level, the dedicated low voltage switchgear which is connected to the power supply and power grid shall have eye-catching signs. The signs shall be indicated of such suggestive text and symbol as "warning", "dual power supply", etc. The shape, color, size, and height of the sign shall follow the requirements of GB 2894.

8.2.2 As for the distributed resources connected to the power grid through the 10 (6) kV ~ 35 kV voltage level, it shall follow the requirements of GB 2894, to indicate such suggestive text and symbol as "be careful of electric shock", etc., nearby the electric equipment and circuit.

8.3 Lightning protection and grounding

The lightning protection and grounding of the distributed resource shall comply with the relevant requirements of GB 14050 and DL/T 621.

9 Relay protection and safety automatic device

9.1 General requirements

The protection of distributed resource shall comply with the requirements of reliability, selectivity, sensitivity and speed, AND its technical conditions shall comply with the requirements of GB/T 14285 and DL/T 584.

9.2 Voltage protection

shall be matched with the power distribution line side re-closure and safety automatic device action time.

10 Communication and information

10.1 General requirements

10.1.1 As for the distributed resources connected to the power grid through the 380 V voltage level AND the distributed resources connected to the user side through the 10 (6) kV voltage level, it may use such communication methods as wireless, optical fiber, and carrier wave, etc. When using the wireless communication method, it shall take the information communication safety protection measures.

10.1.2 As for the distributed resources directly connected to the public power grid through the 10 (6) kV voltage level AND the distributed resources connected to the power grid through the 35 kV voltage level, it shall use the dedicated network communication method, have the capability of data communication with the power grid scheduling institute, be able to collect the electrical operation status of the power supply, upload it to the power grid scheduling institute, AND meanwhile have the capability of accepting the controlling and regulation order from the power grid scheduling institute.

10.1.3 As for the distributed resources directly connected to the public power grid through the 10 (6) kV voltage level AND the distributed resources connected to the power grid through the 35 kV voltage level, the communication method and information transmission between the power grid scheduling institute shall comply with the secondary safety protection requirements of the power system. The telemetry, remote signaling, remote control, remote regulation signals of the transmission may be based on the communication protocols of DL/T 634.5104 and DL/T 634.5101. […]

10.2 Normal operation

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 18 pages — is available in the English PDF.

Referenced standards

Normative references

GB 50065 · DL/T 621

Cited by

Similar standards

How to Download GB/T 33593-2017

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
18 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 33593-2017

$210.00