GB 5135.7-2018Automatic sprinkler systems - Part 7: Water flow indicators (English PDF)
自动喷水灭火系统 第7部分:水流指示器
Open the GB 5135.7-2018 preview as PDF
This is a limited preview
Buy now to download the full PDF (15 pages)
Issued by
State Administration for Market Regulation; Standardization Administration of China
Level / Type
National · Mandatory
Issue date
June 7, 2018
Implementation date
January 1, 2019
Scope
GB 5135.7-2018 is the English-translated version of 自动喷水灭火系统 第7部分:水流指示器.
GB 5135.7-2018 is the Chinese national standard on automatic sprinkler systems - part 7: water flow indicators, in the field of environment and health protection, safety. It carries no /T suffix, which in the Chinese system means compliance is mandatory: a product or a practice within its scope has to meet it to be lawfully made, sold or carried out in China. It was issued on 7 June 2018 by the State Administration for Market Regulation; Standardization Administration of China, and has been in force since 1 January 2019. Classification: ICS 13.220.10, CCS C84. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
Document preview — GB 5135.7-2018
National Standard of the People's Republic of China
- ICS
- 13.220.10
- Classification
- C84
Issued by: State Administration for Market Regulation; Standardization Administration of China
Contents
- 1 Scope1
- 2 Normative references1
- 3 Terms and Definitions1
- 4 Category1
- 5 Model2
- 6 Requirements2
- 6.1 Appearance mark2
- 6.2 Specifications3
- 6.3 rated working pressure3
- 6.4 Connection3
- 6.5 blade3
- 6.6 Sealing assembly3
- 6.7 Signal output unit3
- 6.8 Sensitivity3
- 6.9 Work cycle3
- 6.10 Delay function3
- 6.11 Resistance to external impact4
- 6.12 Water impact resistance4
- 6.13 Hydraulic friction loss4
- 6.14 Overload performance4
- 6.15 Water pressure resistance4
- 6.16 Mechanical strength4
- 6.17 Withstand voltage capability and insulation resistance4
- 6.18 Corrosion resistance4
- 7 Test method4
- 7.1 Visual inspection4
- 7.2 Blade bending test5
- 7.3 Environmental testing of non-metallic materials5
- 7.4 Contact Contact Resistance Test5
- 7.5 Sensitivity test5
- 7.6 Working cycle test6
- 7.7 Delay function test6
- 7.8 External force impact test7
- 7.9 Water Impact Test7
- 7.10 Hydraulic friction test7
- 7.11 Overload test7
- 7.12 Water pressure test7
- 7.13 Mechanical strength test8
- 7.14 Withstand voltage and insulation resistance test8
- 7.15 Corrosion test9
- 8 Inspection rules9
- 8.1 Inspection Classification and Project9
- 8.2 Sampling method9
- 8.3 Test procedure10
- 8.4 Test result judgment 11 9 logo, instruction manual11
- 9.1 Mark11
- 9.2 Instruction Manual11
- 10 Packaging, transportation and storage11
- 10.1 Packing11
- 10.2 Transportation11
- 10.3 Storage11
Foreword
Chapters 6 and 8 of this section are mandatory and the rest are recommended. GB 5135 "Automatic Sprinkler System" is divided into the following sections.
--- Part 1. Sprinklers;
--- Part 2. Wet alarm valve, retarder, hydraulic alarm bell;
---Part 3. Water spray nozzles;
---Part 4. Dry alarm valve;
---Part 5. Rain alarm valve;
--- Part 6. General purpose valves;
--- Part 7. Water flow indicator;
--- Part 8. Accelerator;
---Part 9. Early suppression fast response (ESFR) nozzles;
---Part 10. Pressure switch;
--- Part 11. Grooved pipe joints;
--- Part 12. Expanding the coverage area sprinklers;
---Part 13. Water curtain nozzles;
1 Scope
GB 5135.7-2018 is the Chinese national standard on automatic sprinkler systems - part 7: water flow indicators, in the field of environment and health protection, safety. It carries no /T suffix, which in the Chinese system means compliance is mandatory: a product or a practice within its scope has to meet it to be lawfully made, sold or carried out in China. It was issued on 7 June 2018 by the State Administration for Market Regulation; Standardization Administration of China, and has been in force since 1 January 2019. Classification: ICS 13.220.10, CCS C84. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
This part of GB 5135 specifies the classification, model, requirements, test methods, inspection rules, and water flow indicator of the sprinkler system. Logo, instruction manual and packaging, transportation and storage. This section applies to the vane type water flow indicator in the sprinkler system. Other types of water flow indicators can be used as reference.
2 Normative references
The following documents are indispensable for the application of this document. For dated references, only dated versions apply to this article. Pieces. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 191 packaging storage and transportation icon
GB/T 1842 plastic polyethylene environmental stress cracking test method
GB 5135.11 Automatic sprinkler systems - Part 11. Grooved fittings
GB/T 7306 (all parts) 55° sealed pipe thread
GB/T 9112 Steel Pipe Flange Types and Parameters
GB/T 9969 General guidelines for the use of industrial products
GB/T 17241.6 integral cast iron flange
GB/T 25208 Fixed fire extinguishing system product environmental test method
3 Terms and definitions
The following terms and definitions apply to this document.
3.1 An alarm device used in an automatic sprinkler system to convert a water flow signal into an electrical signal.
3.2 The time from the start of the transmission component action caused by the flow of water to the time when the alarm signal is issued. 3.3 3.4
4 Classification
4.1 The flow indicator can be divided into.
a) time delay type;
b) No delay type.
4.2 The water flow indicator can be divided into.
f) Other styles. Table
1 Classification code Classification method structure type Flanged F Grooved G Clip type D Threaded L Saddle type M Other formula Q Delay function delay type Y no delay type omitted
5 Models
The model of the flow indicator is compiled as follows: ZSJZ Automatic sprinkler system water flow indicator Nominal diameter in millimeters (mm) Delay function code, see Table 1 Structural form code, see Table 1 Rated working pressure in MPa (MPa) Enterprise custom code Example 1. ZSJZ100-YF-
1.2 means the rated working pressure is 1.2MPa, with a time delay function, flanged structure, water flow indicator with a nominal diameter of 100mm. Example 2. ZSJZ100-M-1.2-A means that the company's custom code is A, the rated working pressure is 1.2MPa, no delay function, saddle structure, nominal diameter is 100mm Water flow indicator.
6.1 Appearance sign
6.1.1 The surface of the water flow indicator shall be smooth and smooth, free of processing defects and scratches, and the coating shall be uniform.
6.1.2 The water flow indicator shall be provided with a durability sign on the outer surface. The contents of the mark shall be clear and in accordance with the provisions of 9.1.
6.2 Specifications The water flow indicator nominal diameter series is 25mm, 32mm, 40mm, 50mm, 65mm, 80mm, 100mm, 125mm, 150mm,.200mm.
6.3 rated working pressure The rated operating pressure of the flow indicator shall not be less than
6.4 Connection
6.4.1 When the water flow indicator is flanged, the flange connection size, flange sealing surface type and size shall comply with GB/T 17241.6. Or GB/T 9112.
6.4.2 When the water flow indicator adopts the groove connection method, the groove size shall comply with the provisions of GB 5135.11.
6.4.3 When the water flow indicator is screwed, the connecting thread shall comply with the provisions of GB/T 7306.
6.5 Blade
6.5.1 When the water flow indicator uses metal material as the blade, the blade shall be made of a material whose corrosion resistance is not lower than that of austenitic stainless steel.
6.5.2 When the water flow indicator uses polyethylene as the blade, the blade shall be tested according to 7.3.2. After the test, the blade shall be free from cracking, etc. damage.
6.5.3 Water flow indicator blade The blade bending test shall be carried out according to the method specified in 7.2. After the test, the blade shall be free of fracture, permanent deformation, etc. damage.
6.6 Sealing assembly The sealing assembly used for water pressure sealing shall be subjected to the warm water aging test according to the method specified in 7.3.1. After the test, the sample shall be free from bonding, cracking, etc. For the phenomenon of normal work, the water pressure resistance of the water flow indicator shall comply with the provisions of 6.15.
6.7 Signal output unit The signal output component shall be provided with a terminal or output lead, the terminal identification shall be obvious, and the lead shall be color-coded. According to the provisions of
7.4 The contact contact resistance test is performed by the method, and the contact contact resistance of the signal output part should not be greater than 0.1 Omega.
6.8 Sensitivity The sensitivity test shall be carried out in accordance with the method specified in 7.5. The water flow indicator shall meet the following requirements.
a) When the flow rate is less than or equal to 15.0L/min, there should be no alarm signal output;
b) When the alarm signal is output, the flow rate should be greater than 15.0L/min and less than or equal to 37.5L/min;
c) When the flow rate is greater than or equal to 37.5L/min, the alarm signal shall be output, and the alarm signal shall not change with the increase of the flow rate;
d) The reset time ...
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 191Graphical symbols marking for handling and storage of packages
- GB 5135.11Automatic sprinkler systems - Part 11: Grooved pipe couplings and fittings
- GB/T 9969General principles for preparation of instructions for use of industrial products
- GB/T 25208Environmental test methods for fixed extinguishing systems
GB/T 1842 · GB/T 7306 · GB/T 9112 · GB/T 17241.6
Cited by
- GB 27898.3-2026Fixed water supply equipment used for fire-protection - Part 3: Pressure boosting and stabilizing type water supply equipment used for fire-protection
- GB 27898.5-2026Fixed water supply equipment used for fire-protection - Part 5: Dual power fixed water supply equipment used for fire-protection
- GB 27898.1-2011Fixed water supply equipment used for fire-protection - Part 1: Gas pressure fixed water supply equipment used for fire-protection
- GB 27898.3-2011Fixed water supply equipment used for fire-protection - Part 3: Pressure boosting and stabilizing type water supply equipment
Similar standards
Editions of GB 5135.7
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB 5135.7-2018 | Automatic sprinkler systems - Part 7: Water flow indicators | current edition | Current |
| GB 5135.7-2003 | Automatic sprinkler system-Part 7:Water flow indicator | previous edition | Superseded |
This page sells the current edition, GB 5135.7-2018. Earlier editions are listed for reference only.
How to Buy GB 5135.7-2018
- 1Add to cart. Click the "Buy GB 5135.7-2018" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 5135.11-2006 — Automatic sprinkler system-Part 11:grooved couplings and fittings
GB 5135.11-2025 — Automatic sprinkler systems - Part 11: Grooved pipe couplings and fittings
GB/T 18420.2-2009 — Biological toxicity for pollutants from marine petroleum exploration and exploitation - Part 2: Test method