JB/T 9615.1-2000Test methods for interturn insulation of random-wound windings of low-voltage AC machines (English PDF)

交流低压电机散嵌绕组匝间绝缘试验方法

Preview PDF

This is a limited preview

Buy now to download the full PDF (15 pages)

Need quotation for your management?

Get a formal quotation for JB/T 9615.1-2000 in 30 minutes.

Issued by

MIIT

Level / Type

Industry · Recommended

Issue date

April 24, 2000

Implementation date

October 1, 2000

Scope

JB/T 9615.1-2000 is the English-translated version of 交流低压电机散嵌绕组匝间绝缘试验方法.

JB/T 9615.1-2000 is the Chinese standard "Test methods for interturn insulation of random-wound windings of low-voltage AC machines". Its scope clause reads: This Standard specifies the method of AC motor loose winding inter-turn insulation test.

This Standard applies to the 3-phase or single-phase of AC motor loose winding inter-turn insulation test of which the nominal voltage is not more than 1140 V. Its clauses include definitions; test instruments; test method; test identification; u2 v2 u1 and v1 sqrt; u2 v2 u1 and v1 ×; u2 v2 u1 and v1 ×; u v w sqrt; u v w ×; v w u sqrt u phase fault.

Found what you need?

Document preview — JB/T 9615.1-2000

National Standard of the People's Republic of China

Replacing
JB/Z 294-1987

Issued by: Ministry of Industry and Information Technology of the People's Republic of China

Contents

  • Foreword3
  • 1 Scope4
  • 2 Normative References4
  • 3 Definitions4
  • 4 Test instruments5
  • 5 Test method5
  • 6 Selection principle of test connection8
  • 7 Test identification9
  • 8 Automatic testing and automatic identification11
  • Annex A (Normative) Comparison method of impulse waveform13

1 Scope

This Standard specifies the method of AC motor loose winding inter-turn insulation test.

This Standard applies to the 3-phase or single-phase of AC motor loose winding inter-turn insulation test of which the nominal voltage is not more than 1140 V.

2 Normative References

The articles in the following standard are quoted by this Standard and become the articles of this Standard. At the time of publication, the edition indicated is valid. All standards are subject to revision. Parties who enter into an agreement based on this Standard are encouraged to investigate the possibility of applying the most recent edition of the standard indicated below.

JB/T 9615.2 Test limits of the interturn insulation on random wound winding for AC low-voltage machines

3 Definitions

For the purpose of this Standard, the following definitions apply.

3.1 Comparison method of impulse waveform

A method to test motor winding (or coil) turn-to-turn insulation by using impulse voltage test.

Use impulse voltage wave that possesses specified peak-value and front time; alternately (or simultaneously) and directly apply to the same-design test-object winding (or coil) AND reference-object winding (or coil); test whether the performance of motor winding (or coil) turn-to-turn insulation is good or not by judging the whether damped oscillation waveforms caused by impulse voltage are different. See annex A for details (normative annex).

3.2 Reference-object winding (or coil)

When using impulse waveform comparison method to test motor winding (or coil) turn-to-turn insulation, the motor winding (or coil) that is used to compare with test-object winding (or coil).

3.3 Test waveform difference

JB/T 9615.1-2000

When using impulse waveform comparison method to test motor winding (or coil) inter-turn insulation, and in test-object winding (or coil) and reference-object winding (or coil), the difference between both test waveforms that is caused by non-insulation failures such as turn-to-turn insulation failure, material and process fluctuation; it is usually expressed in percentage.

The test waveform difference caused by turn-to-turn insulation failure is usually called harmful difference.

The test waveform difference not caused by insulation failure is usually called non-harmful difference or allowable difference.

4 Test instruments

4.1

Two groups of impulse voltage wave outputted by the instruments shall be symmetrical (tolerance±3%).

It is allowable that the instrument outputs a single-impulse voltage wave OR converts a single-impulse voltage into double-impulse voltage waves for output.

4.2

Front time of the first impulse voltage wave outputted by instrument are 0.2 µs (tolerance µs) and 1.2 µs (tolerance±30%). 0.2 µs is recommended with priority.

Other front time can be outputted upon client's demand.

4.3

Maximum impulse voltage peak outputted by instrument shall meet the test limit value requirements on related test-object by JB/T 9615.2; tolerance is ±5% or ±3%, the recommended priority is ±3%.

4.4

Impulse voltage peak outputted by instrument shall be continuously adjustable, with indication or pre-setting. Measurement accuracy is ±1.5% or ±1%, the recommended priority is ±1% and the adoption of digital peak voltmeter indication.

4.5

The instrument shall be able to clearly display and distinguish the waveform, waveform scanning frequency is adjustable.

4.6

The instrument can operate continuously and reliably.

4.7

The instrument shall be equipped with special test wire, reliable earth terminal, and necessary safety warning measure; the test conversion connection shall be convenient and reliable.

4.8

The instrument can be equipped with microcomputer interface, and with functions such as test waveform storage, comparison parameter setting, test waveform difference display, automatic identification and alarm. Instrument can be equipped with testing voltage conversion test device.

5 Test method

7 Test identification

The standard takes test waveform as the main identification evidence.

The automatic test waveform identification instrument which can compare and calculate the test waveform difference can be the supplementary method for automatic identification.

Display of fault waveform often accompanies with discharge sound, even with discharge spark and smell of O3; those signals can assist to identify fault type and location.

7.1 Normal waveform

If damped oscillation waveform displayed in two tests overlaps basically without significance difference (abbreviation as overlap), it is normal waveform, namely no fault for test-object winding turn-to-turn insulation, see annex A (normative annex).

7.2 Fault waveform

If abnormal waveform happens, there is fault for winding turn-to-turn insulation, see annex

A (normative annex).

7.3 Identification of 3-phase motor fault

Fault of 3-phase motor shall be identified separately by different wiring methods.

If one of two test waveforms displays differently, then single-phase winding has fault; if both test waveforms display differently, then it is necessary to conduct the 3rd test.

If the 3rd test waveform displays overlap, then single-phase winding has fault; if difference still exists, then fault exists in windings of 2 and above phases.

For 2nd and 3rd test, identification can be made by selecting any one wiring method.

7.3.1

See Table 1 for Phi (phase) connection fault identification example (see Figure 1 for wiring); others use the same analogy.

JB/T 9615.1-2000

Table 1 Phi (phase) connection fault identification example

S/N. Test times

Instrument terminal wiring Waveform display

Fault identification

H1 H2 L

1

1 U2 V2 U1 and V1 sqrt

2

U2 W 2 U1 and W 1 ×

W phase fault

V2 W 2 V1 and W 1 ×

2

1 U2 V2 U1 and V1 ×

2

U2 W 2 U1 and W 1 sqrt V phase fault

V2 W 2 V1 and W 1 sqrt U phase fault

3

1 U2 V2 U1 and V1 ×

2

U2 W 2 U1 and W 1 ×

Conduct 3rd test

V2 W 2 V1 and W 1 ×

3

V2 W 2 V1 and W 1

sqrt U phase fault

× Fault of 2-phase and above

U2 W 2 U1 and W 1

sqrt V phase fault

× Fault of 2-phase and above

Notes: sqrt - waveform displays overlap; × - waveform displays differently.

7.3.2

See Table 2 for Y (wiring) connection fault identification example (see Figure 2 for wiring); others use the same analogy.

Table 2 Y (wiring) connection fault identification example

S/N Test times

Instrument terminal wiring Waveform display

Fault identification

H1 H2 L

1

1 U V W sqrt

2

V W U ×

W phase fault

U W V ×

2

1 U V W ×

2 V W U sqrt U phase fault

U W V sqrt V phase fault

3

1 U V W ×

2

V W U ×

Conduct 3rd test

U W V ×

3

U W V

sqrt V phase fault

× Fault of 2-phase and above

V W U

sqrt U phase fault

× Fault of 2-phase and above

Notes: sqrt - waveform displays overlap; × - waveform displays differently.

7. 3.3 See Table 3 for delta(angle) connection fault identification example (see Figure 3 for wiring); others use the same analogy.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.

Referenced standards

Similar standards

Editions of JB/T 9615.1

EditionTitleRevisionStatus
JB/T 9615.1-2000Test methods for interturn insulation of random-wound windings of low-voltage AC machinescurrent editionCurrent
JB/Z 294-1987Test methods for interturn insulation of random-wound windings of low-voltage AC machinesprevious editionSuperseded

This page sells the current edition, JB/T 9615.1-2000. Earlier editions are listed for reference only.

How to Download JB/T 9615.1-2000

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Fast delivery

    After payment you'll receive an email confirmation. The English PDF is sent to the same address, usually within minutes and at the latest within 1 business day.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
15 pages
Fast delivery
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

JB/T 9615.1-2000

$150.00