GB/Z 17799.6-2017Electromagnetic compatibility -- Generic standards -- Immunity for power station and substation environments (English PDF)
Also coversGBZ17799.6-2017
Open the GB/Z 17799.6-2017 preview as PDF
This is a limited preview
Buy now to download the full PDF
Issued by
General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China
Level / Type
National · Recommended
Issue date
July 12, 2017
Implementation date
February 1, 2018
Scope
GB/Z 17799.6-2017 (Electromagnetic compatibility -- Generic standards -- Immunity for power station and substation environments) is available as an English-translated PDF.
GB/Z 17799.6-2017 — This section applies to the power system power generation, transmission, distribution equipment and related communications systems with immunity requirements. Suitable places for the power system installation of power plants and substations. The immunity requirements given in this section apply to the electromagnetic phenomena of interest in the frequency range 0 Hz to 400 GHz. The tests involved Methods, test equipment and configuration to GB/T 17626 as the basis. The immunity requirements set forth in this standard apply to the specific needs of equipment and systems in implementing functions and fulfilling tasks to ensure that The actual electromagnetic environment, reliable operation, and given different functions of immunity test performance evaluation basis. This section gives different immunity test requirements for installation in power plants and substation equipment. Under special conditions, electromagnetic disturbance level May exceed the immunity test specified in this standard level, then in this case should take appropriate mitigation measures. High-voltage and high-power devices without electronic circuitry (primary system) are not covered by this standard. This section does not address the safety requirements of the equipment, such as shock protection, insulation and pressure test conducted prior to the immunity test. This section does not involve electromagnetic emission requirements. Electromagnetic emission requirements, please refer to other relevant standards (such as GB 7251.1, GB/T 18657.1 Wait). If there is no dedicated product and product class standard exists, the common standard is GB 17799.4.
Document preview — GB/Z 17799.6-2017
National Standard of the People's Republic of China
- ICS
- 33.100.20
- Classification
- L 06
Issued by: General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China, Standardization Administration of the People's Republic of China
Contents
- Foreword
- 1 Scope
- 2 Normative references
Foreword
The Common Criteria for Electromagnetic Compatibility now includes the following sections.
--- Common standard electromagnetic compatibility residential, commercial and light industrial environments immunity test;
--- EMC common standard industrial environment immunity test;
--- Electromagnetic compatibility common standard residential, commercial and light industrial environment in the launch;
--- EMC common standard industrial environment launch;
--- General electromagnetic compatibility standard indoor equipment high altitude electromagnetic pulse (HEMP) immunity;
--- EMC common standard power plant and substation environment immunity.
This section is "General Standard Electromagnetic Compatibility" Part 6, this section is the guiding technical documents.
This section drafted in accordance with GB/T 1.1-2009 given rules.
This section uses the redrafted Law Reference IEC /T S61000-6-5.2001 "Electromagnetic Compatibility Part 6-5. General Standard Power Plant
And substation environment immunity "compilation, and IEC /T S61000-6-5.2001 consistency is not equivalent.
This part of the IEC /T S61000-6-5.2001 technical differences and the reasons are as follows.
--- Shell port immunity test items increased pulsed magnetic field and damping oscillation magnetic field immunity test; low-voltage AC input/output power
Source port immunity test adds low frequency immunity test of AC power port harmonics, inter-harmonics and power network signals. The above increase
Canada's projects are currently the actual electromagnetic compatibility pilot project.
--- Pulsed magnetic field and damped Oscillatory magnetic field immunity test level to take five, according to GB/T 17626.9 and GB/T 17626.10 Medium
Harsh industrial environment requirements; AC power port harmonics, inter-harmonics and power network signal low frequency immunity test level
Level 2, according to GB/T 17626.13 in the public connection point (PCC) and the internal connection point (IPC) requirements.
This section made the following editorial changes.
--- Remove the IEC /T S61000-6-5.2001 English original introduction and introduction;
--- Adjust the IEC /T S61000-6-5.2001 in the chart and table location.
This part of the National Electromagnetic Compatibility Standardization Technical Committee (SAC/TC246) and focal point.
This section drafted unit. China Electric Power Research Institute, North China Electric Power University, State Grid Electric Power Research Institute, Beijing Sifang Automation Automation
Co., Ltd., Schneider Electric China Limited.
1 Scope
This section applies to the power system power generation, transmission, distribution equipment and related communications systems with immunity requirements.
Suitable places for the power system installation of power plants and substations.
The immunity requirements given in this section apply to the electromagnetic phenomena of interest in the frequency range 0 Hz to 400 GHz. The tests involved
Methods, test equipment and configuration to GB/T 17626 as the basis.
The immunity requirements set forth in this standard apply to the specific needs of equipment and systems in implementing functions and fulfilling tasks to ensure that
The actual electromagnetic environment, reliable operation, and given different functions of immunity test performance evaluation basis.
This section gives different immunity test requirements for installation in power plants and substation equipment. Under special conditions, electromagnetic disturbance level
May exceed the immunity test specified in this standard level, then in this case should take appropriate mitigation measures.
High-voltage and high-power devices without electronic circuitry (primary system) are not covered by this standard.
This section does not address the safety requirements of the equipment, such as shock protection, insulation and pressure test conducted prior to the immunity test.
This section does not involve electromagnetic emission requirements. Electromagnetic emission requirements, please refer to other relevant standards (such as GB 7251.1, GB/T 18657.1
Wait). If there is no dedicated product and product class standard exists, the common standard is GB 17799.4.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version applies to this article
Pieces. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 4365 Electrotechnical terminology Electromagnetic compatibility (GB/T 4365-2003, IEC 60050 (161) .1990, IDT)
GB/T 7251.1 Low-voltage switchgear and controlgear - Part 1. Type test and part type test equipment
(GB 7251.1-2005, IEC 61439-1.1999, IDT)
GB/T 17618 Information technology equipment immunity limits and measurement methods (GB/T 17618-2015, CISPR24.2010, IDT)
GB/T 17626.1 electromagnetic compatibility test and measurement techniques Immunity Test Summary (GB/T 17626.1-2006,
IEC 61000-4-1.2000, IDT)
GB/T 17626.2 Electromagnetic compatibility test and measurement techniques Electrostatic discharge immunity test (GB/T 17626.2-2006,
IEC 61000-4-2.2001, IDT)
GB/T 17626.3 Electromagnetic compatibility test and measurement techniques RF electromagnetic radiation immunity test (GB/T 17626.3-
2006, IEC 61000-4-3.2002, IDT)
GB/T 17626.4 Electromagnetic compatibility test and measurement techniques Electrical fast transient burst immunity test (GB/T 17626.4-
2008, IEC 61000-4-4.2004, IDT)
GB/T 17626.5 electromagnetic compatibility test and measurement technology surge (impact) immunity test (GB/T 17626.5-2008,
IEC 61000-4-5.2005, IDT)
GB/T 17626.6 Electromagnetic compatibility-Testing and measurement techniques Immunity to conducted disturbances induced by radio-frequency fields (GB/T 17626.6-
2008, IEC 61000-4-6.2006, IDT)
GB/T 17626.8 Electromagnetic compatibility test and measurement techniques Frequency magnetic field immunity test (GB/T 17626.8-2006,
IEC 61000-4-8.2001, IDT)
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Normative references
GB/T 4365 · GB/T 4365-2003 · IEC 60050 · GB 7251.1-2005 · IEC 61439 · GB/T 17618 · GB/T 17618-2015 · GB/T 17626.1 · GB/T 17626.1-2006 · IEC 61000 · GB/T 17626.2 · GB/T 17626.2-2006 · GB/T 17626.3 · GB/T 17626.4 · GB/T 17626.5 · GB/T 17626.5-2008 · GB/T 17626.6 · GB/T 17626.8 · GB/T 17626.8-2006
How to Buy GB/Z 17799.6-2017
- 1Add to cart. Click the "Buy GB/Z 17799.6-2017" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 17626.11-2023 — Electromagnetic compatibility - Testing and measurement techniques - Part 11: Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase
GB/T 17626.12-2023 — Electromagnetic compatibility - Testing and measurement techniques - Part 12: Ring wave immunity test
GB/T 17626.18-2016 — Electromagnetic compatibility -- Testing and measurement techniques -- Damped oscillatory wave immunity test