Scope
GB/T 50102-2014 is the English-translated version of 工业循环水冷却设计规范.
GB/T 50102-2014 is the Chinese standard "Code for design of cooling for industrial recirculating water".
Its scope clause reads: This code is formulated with a view to implementing the technical and economic policies of the nation in design of facilities for cooling for industrial recirculating water and thus achieving advanced technology, safety and applicability, economic rationality, energy saving and environmental protection and guaranteed quality.
This code is applicable to process and structural design for open recirculating water cooling facilities.
The type selection of recirculating water cooling facilities shall be determined through technical and economic comparison according to the production process requirements for the quantity, temperature and quality of recirculating water, as well as operation mode of water supply system, etc., and in combination with the following factors: 1 Local natural conditions, such as hydrogeology, meteorology, topography and geology; 2 Supply of materials, equipment, electricity and make-up water; 3 Site layout and construction conditions; 4 The interaction between recirculating water cooling facilities and the surrounding environment; 5 Safety reliability of buildings (structures).
In addition to this code, the design of recirculating water cooling facilities shall also meet the requirements of the current relevant standards of the nation. Its clauses include general provisions; terms.
Found what you need?
Document preview — GB/T 50102-2014
National Standard of the People's Republic of China
- Classification
- P 59
- Replacing
- GB/T 50102-2003
Issued by: Ministry of Housing and Urban-Rural Development
Contents
- Foreword
- 1 General provisions
- 2 Terms
- 3 Cooling tower
- 3.1 General requirement
- 3.2 Natural draft cooling tower
- 3.3 Mechanical draft cooling tower
- 3.4 Basic requirements and materials of cooling tower structural design
- 3.5 Load and internal force calculation of natural draft cooling tower
- 3.6 Load and internal force calculation of mechanical draft cooling tower
- 3.7 Water spray device structure
- 3.8 Detailing Requirements
- 3.9 Cooling tower durability
- 4 Spray pond
- 4.1 Process design of spray pond
- 4.2 Structural design of spray pond
- 5 Water surface cooling
- 5.1 General requirement
- 5.2 Cooling pond
- 5.3 Channel cooling
- 5.4 Gulf cooling
- Appendix A Design temperature value of inner air of the ventilator for natural draft cooling tower
- Appendix B Equivalent static load calculation method of fan and motor for mechanical draft cooling tower
1 General provisions
1.0.1
This code is formulated with a view to implementing the technical and economic policies of the nation in design of facilities for cooling for industrial recirculating water and thus achieving advanced technology, safety and applicability, economic rationality, energy saving and environmental protection and guaranteed quality.
1.0.2
This code is applicable to process and structural design for open recirculating water cooling facilities.
1.0.3
The type selection of recirculating water cooling facilities shall be determined through technical and economic comparison according to the production process requirements for the quantity, temperature and quality of recirculating water, as well as operation mode of water supply system, etc., and in combination with the following factors:
1 Local natural conditions, such as hydrogeology, meteorology, topography and geology;
2 Supply of materials, equipment, electricity and make-up water;
3 Site layout and construction conditions;
4 The interaction between recirculating water cooling facilities and the surrounding environment;
5 Safety reliability of buildings (structures).
1.0.4
In addition to this code, the design of recirculating water cooling facilities shall also meet the requirements of the current relevant standards of the nation.
2 Terms
2.0.1 open recirculating water cooling facilities
cooling facilities where industrial recirculating cooling water (hereinafter referred to as recirculating water) is directly exposed to the atmosphere.
2.0.2 evaporation loss
loss of recirculating water due to vaporization of liquid surface.
2.0.3 drift and blow-out loss
loss of recirculating water due to entrainment of water droplets by airflow.
2.0.4 purge loss
loss of recirculating water due to discharge of a certain amount of water from the recirculating water system to maintain a certain concentration cycle of recirculating water.
2.0.5 rate of evaporation water loss
percentage of evaporation water loss amount of cooling facilities such as cooling towers, cooling pond and spray pond in recirculating water entering these cooling facilities.
2.0.6 rate of drift and blow-out water loss
percentage of the drift and blow-out water loss of cooling facilities such as cooling towers and spray pond in recirculating water entering these cooling facilities.
2.0.7 concentration cycle of recirculating water
ratio of the salt content of the recirculating water to the salt content of makeup water.
2.0.8 seawater salinity
ratio of total dissolved solid mass to seawater mass in g/kg.
2.0.9 air deflector
device for steering flow installed at air inlet of cooling tower.
2.0.10 super large-scale cooling tower
natural draft counter flow cooling tower with area of water drenching greater than or equal to 10000m2.
2.0.11 seawater cooling tower
wet cooling tower using seawater as recirculating water.
2.0.12 flue gas discharged cooling tower
natural draft cooling tower with flue gas discharge function.
2.0.13 velocity of flue gas at outlet pipe in cooling tower
average flow velocity of flue gas at outlet pipe in the tower.
2.0.14 outlet velocity of cooling tower
average flow velocity of mixed gas at cooling tower outlet.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 111 pages — is available in the English PDF.
Referenced standards
Cited by
- GB/T 44855-2024Management specification for water conservation of cooling towers
- GB/T 41985-2022230MeV~250MeV superconducting proton cyclotron
- HY/T 0187.5-2021Design Specification for Seawater Circulating Cooling System - Part 5: Circulating Water Field
- GB/T 23248-2020Code for design of seawater treatment for recirculating cooling seawater system
- GB/T 7941-2019Refrigeration test systems
- GB/T 35084-2018Guidelines for environmental protection at press shop
How to Download GB/T 50102-2014
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 10003-2026 — Biaxially oriented polypropylene (BOPP) film
GB/T 10004-2026 — Plastic/Plastic laminated films and pouches for packaging
GB/T 10007-2026 — Rigid cellular plastics - Determination of shear properties
Secure payment via Stripe
Payments accepted
GB/T 50102-2014
$800.00