GB/T 37141.1-2022Guide to UV imaging detection of electrical equipments in high altitude regions—Part 1: Substations (English PDF)
高海拔地区电气设备紫外线成像检测导则 第1部分:变电站
This is a limited preview
Buy now to download the full PDF (20 pages)
Need quotation for your management?
Get a formal quotation for GB/T 37141.1-2022 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
October 14, 2022
Implementation date
May 1, 2023
Scope
GB/T 37141.1-2022 is the English-translated version of 高海拔地区电气设备紫外线成像检测导则 第1部分:变电站.
GB/T 37141.1-2022 is Part 1 of the Chinese national guide to ultraviolet imaging inspection of electrical equipment at high altitude, and covers substations. Solar-blind ultraviolet imagers are used on AC equipment of 1000 V and above in substations and converter stations at altitudes of 1000 m to 5000 m, to find corona and arc discharge.
It sets out the detection conditions and steps, the altitude correction of the photon count, how discharge type and cause are judged, defect classification and handling, the inspection interval and data management.
It defines photon number, mean photon number, gain and detection distance, and its annexes give the test report form, the distance correction constants C1 and C2 and typical discharge types.
It cites GB 26860, DL/T 345 and DL/T 664. It was issued on 14 October 2022 and has applied since 1 May 2023.
Found what you need?
Document preview — GB/T 37141.1-2022
National Standard of the People's Republic of China
- ICS
- 29.240.10
- Classification
- F 23
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Preface
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
- 4 Detection condition
- 5 Detection principle
- 6 Detection step
- 7 Altitude Correction
- 8 Discharge type and cause judgment
- 9 Defect classification and handling
- 10 detection cycle
- 11 Data Management
- Appendix A (informative) UV test report for live equipment
- Appendix B (Informative) Values of UV Photon Distance Correction Constants C1 and C2
- Appendix C (informative) Discharge parameters and characteristic quantities
- Appendix D (Informative) Correction of Photon Numbers for Different Ultraviolet Imaging Equipment
- Appendix E (Informative) Typical discharge types of substations, evaluation methods of equipment discharge status, diagnosis of discharge types and causes
- Reference
Foreword
This document is in accordance with the provisions of GB/T 1.1-2020 "Guidelines for Standardization Work Part 1: Structure and Drafting Rules for Standardization Documents" drafting.
This document is part 1 of GB/T 37141 "Guidelines for Ultraviolet Imaging Testing of Electrical Equipment in High Altitude Areas". GB/T 37141 has The following parts have been published.
--- Part 1: Substation;
--- Part 2: Transmission lines.
Introduction
This document is compiled based on the research results of discharge ultraviolet detection conducted by relevant units on the substation site and in the laboratory.
The methods and criteria presented in this document are derived from observed examples in field and laboratory tests. Taking into account the environmental parameters and instrument models, Due to differences in versions, different models and batches of ultraviolet imagers may not observe completely consistent discharge phenomena in the same environment.
Since substations and transmission lines are different in terms of equipment, defect types, and importance levels, etc., the detection strips for ultraviolet detection in substations There are some differences from transmission lines in terms of components, detection methods, defect classification and processing, and detection cycle.
GB/T 37141 is divided into two parts, including.
--- Part 1: Substation. The purpose is to provide high-altitude substation corona and arc ultraviolet imaging detection, defect evaluation, etc. method and basis.
--- Part 2: Transmission lines. The purpose is to provide corona and arc ultraviolet imaging detection and defect evaluation for transmission lines in high altitude areas Provide methods and basis.
1 Scope
This document provides the application of solar-blind ultraviolet imaging equipment to detect the corona of 1000V and above AC electrical equipment in substations (converter stations). And arc discharge detection conditions, detection methods, altitude correction of ultraviolet photon number, discharge type and cause judgment, defect classification and treatment, detection Measurement cycle and data management.
This document is applicable to the operation of 1000V and above AC electrical equipment in substations (converter stations) at an altitude of 1000m~5000m Detection of corona and arc discharge.
2 Normative references
The contents of the following documents constitute the essential provisions of this document through normative references in the text. Among them, dated references For documents, only the version corresponding to the date is applicable to this document; for undated reference documents, the latest version (including all amendments) is applicable to this document.
GB 26860 Electrical Safety Work Regulations for Electric Parts of Power Plants and Substations
DL/T 345 Guidelines for the application of ultraviolet diagnostic technology for live equipment
DL/T 664 Application specification for infrared diagnosis of live equipment
3 Terms and Definitions
DL/T 345 and DL/T 664 defined and the following terms and definitions apply to this document.
3.1 Photon number
The number of photons detected by the UV imaging device reflecting the intensity of the discharge.
3.2 Mean photon number
The average value of the number of photons (3.1) detected over a specified period of time.
3.3 Gain
The ratio by which a UV imaging device amplifies the detected photon signal.
3.4 Detection distance
The linear distance between the detected part and the lens of the ultraviolet imaging device.
3.5 Inspection detection
Preliminary determination of corona and arc discharge generation, position and intensity of electrical equipment by means of inspection with ultraviolet imaging equipment process.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 20 pages — is available in the English PDF.
Referenced standards
Similar standards
How to Download GB/T 37141.1-2022
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
DL/T 345-2019 — Application guidelines of UV diagnostic technology for live electrical equipment
GB 26860-2011 — Safety code of electric power industry - Electric part of power plants and transformer substations
GB/T 37141.2-2018 — Guide to UV imaging detection of electrical equipments in high altitude regions—Part 2: Transmission lines
Secure payment via Stripe