GB/T 30137-2024Power quality - Voltage swell, voltage dips and short interruptions (English PDF)
电能质量 电压暂升、电压暂降与短时中断
Open the GB/T 30137-2024 preview as PDF
This is a limited preview
Buy now to download the full PDF (35 pages)
Issued by
State Administration for Market Regulation; Standardization Administration of the PRC
Level / Type
National · Recommended
Issue date
December 31, 2024
Implementation date
April 1, 2025
Scope
GB/T 30137-2024 is the English-translated version of 电能质量 电压暂升、电压暂降与短时中断.
China's national standard on voltage swells, voltage dips and short interruptions in the power system, and the current edition of GB/T 30137, replacing the 2013 edition. It specifies the indexes used to describe these events and the methods by which they are counted, detected, monitored and assessed, and it applies to 50 Hz AC power systems. The three events are the same phenomenon seen from different directions: a sudden departure of the root-mean-square voltage from its normal value, lasting from ten milliseconds to one minute and then returning. A swell is a rise to between 1.1 and 1.8 per unit, a dip a fall to between 0.1 and 0.9 per unit, and a short interruption a fall below 0.1 per unit. They are by far the most common power quality disturbance, and their economic weight is out of proportion to their duration: a dip lasting a tenth of a second can stop a semiconductor fabrication line, a paper machine or a continuous process plant, and the restart takes hours. Their cause is usually a fault somewhere on the network, which is cleared in a few cycles by protection, so the dip is felt across a wide area while the fault itself is remote and brief - which is why a dip cannot be eliminated at source and has to be characterised, measured and managed instead. The main change in the 2024 edition is that voltage swell is brought fully into scope alongside dips and interruptions, the terminology is aligned with GB/T 17626.30-2023, and phase-angle jump, hysteresis voltage, sliding reference voltage and the severity and energy indexes are defined and specified. Issued on 31 December 2024 and in force since 1 April 2025.
Document preview — GB/T 30137-2024
National Standard of the People's Republic of China
- ICS
- 29.020
- Classification
- K 04
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Statistics and indexes of voltage swells, voltage dips and
- 4.2 Indexes of voltage swells, voltage dips and short interruptions
- 5 Detection of voltage swells, voltage dips and short interruptions
- 5.1 Detection algorithm of r.m.s. voltage
- 5.2 Event detection
- 5.3 Method for selecting values of characteristic parameters
- 6 Monitoring of voltage swells, voltage dips and short interruptions
- 6.2 Technical requirements for monitoring instruments
- 6.2.1 Basic functions
- 7 Assessment of voltage swells, voltage dips and short interruptions
1 Scope
China's national standard on voltage swells, voltage dips and short interruptions in the power system, and the current edition of GB/T 30137, replacing the 2013 edition. It specifies the indexes used to describe these events and the methods by which they are counted, detected, monitored and assessed, and it applies to 50 Hz AC power systems. The three events are the same phenomenon seen from different directions: a sudden departure of the root-mean-square voltage from its normal value, lasting from ten milliseconds to one minute and then returning. A swell is a rise to between 1.1 and 1.8 per unit, a dip a fall to between 0.1 and 0.9 per unit, and a short interruption a fall below 0.1 per unit. They are by far the most common power quality disturbance, and their economic weight is out of proportion to their duration: a dip lasting a tenth of a second can stop a semiconductor fabrication line, a paper machine or a continuous process plant, and the restart takes hours. Their cause is usually a fault somewhere on the network, which is cleared in a few cycles by protection, so the dip is felt across a wide area while the fault itself is remote and brief - which is why a dip cannot be eliminated at source and has to be characterised, measured and managed instead. The main change in the 2024 edition is that voltage swell is brought fully into scope alongside dips and interruptions, the terminology is aligned with GB/T 17626.30-2023, and phase-angle jump, hysteresis voltage, sliding reference voltage and the severity and energy indexes are defined and specified. Issued on 31 December 2024 and in force since 1 April 2025.
This document specifies the indexes and statistical, test, monitoring and assessment methods for voltage swell, voltage dip and short interruption in the electric power system. This document is applicable to
50 Hz AC power systems.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
GB/T 19862, General requirements for monitoring equipments of power quality
GB/T 17626.30, Electromagnetic compatibility - Testing and measurement techniques - Part
30.Power quality measurement methods
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 voltage swell A phenomenon that the r.m.s. voltage at a certain point in the power system suddenly rises to
1.8 p.u. and returns to normal after a short period of 10 ms ~ 1 min.
3.2 magnitude of voltage swell The maximum value of the r.m.s. voltage during a voltage swell.
3.3 voltage dip; voltage sag A phenomenon that the r.m.s. voltage at a certain point in the power system suddenly drops to
0.1 p.u ~
0.9 p.u. and returns to normal after a short period of 10 ms ~ 1 min.
3.4 short interruption A phenomenon that the r.m.s. voltage at a certain point in the power system suddenly drops to below
0.1 p.u. and returns to normal after a short period of 10 ms ~ 1 min.
3.5 threshold The voltage threshold value used to determine the start and end of a voltage swell, voltage dip or short interruption.
3.6 duration The time taken from the start to the end of a voltage swell, voltage dip or short interruption event.
3.7 phase-angle jump The sudden change in the relative position of the voltage and/or current waveform on the time axis before and after a voltage swell or voltage dip event occurs, expressed in degrees or radians.
3.8 frequency; occurrence frequency The number of voltage swells, voltage dips, or short interruptions that occur within a specified period of time.
3.9 r.m.s. voltage refreshed each half-cycle Urms(1/2) The measured value of r.m.s. voltage whose measurement data window is one cycle, starting from the zero crossing point of the fundamental wave and updated every half cycle.
4 Statistics and indexes of voltage swells, voltage dips and
short interruptions
4.1 Statistics of voltage swells, voltage dips and short interruptions The voltage swell, voltage dip and short interruption statistics table, which can intuitively reflect the occurrence of voltage swells, voltage dips and short interruptions at the monitoring point within a period of time, mainly counts the number of events with different magnitudes and durations. If voltage swell and voltage dip or short interruption occur simultaneously within 1 minute after the start of the event, they shall be counted in Table 1 and Table 2, respectively. Table 1 shows the number of voltage swell events corresponding to the corresponding magnitude and duration of voltage swell; Table 2 shows the number of voltage dips or short interruptions corresponding to the corresponding residual voltage and duration.
4.2 Indexes of voltage swells, voltage dips and short interruptions
4.2.2 Frequency index The frequency index reflects the frequency of voltage swells, voltage dips or short interruptions. Frequency statistics and evaluation can be carried out through monitoring or other means, and the general statistical cycle is 1 year. The event frequency of a node or the total event frequency of a regional power grid can be counted.
4.2.3 Severity index The severity index reflects the impact of voltage swells, voltage dips or short interruptions on equipment and users. The event severity index is calculated in combination with the equipment tolerance curve. The severity index Se of a single voltage swell event is defined as shown in Formula (3), and the severity index Se of a single voltage dip or short interruption event is defined as shown in Formula (4).
4.2.4 Indexes of voltage swell/dip The energy index reflects the degree of energy enhancement/loss caused by swell/dip events.
5.1 Detection algorithm of r.m.s. voltage
5.1.1 r.m.s. voltage refreshed each half-cycle [Urms(1/2)] The calculation method of Urms(1/2) is shown in Formula (6).
5.1.2 r.m.s. voltage refreshed each cycle [Urms(1)] The calculation method of Urms(1) is shown in Formula (7).
5.2 Event detection
5.2.1 Threshold setting The threshold for voltage swell is generally set at
1.1 p.u.; the threshold for voltage dip is generally set at
0.9 p.u.; the threshold for short interruption is generally set at
0.1 p.u.
5.2.2 Determination of voltage swell In a single-phase system, when Urms(1/2) or Urms(1) is higher than the swell threshold, the voltage swell event begins; when Urms(1/2) or Urms(1) is equal to or lower than the difference between the voltage swell threshold and the hysteresis voltage, the voltage swell ends. In a multi-phase system, when Urms(1/2) or Urms(1) of any phase is higher than the swell threshold, the voltage swell begins; when Urms(1/2) or Urms(1) of all phases is equal to or lower than the difference between the swell threshold and the hysteresis voltage, the voltage swell ends.
5.2.3 Determination of voltage dip In a single-phase system, when Urms(1/2) or Urms(1) is lower than the dip threshold, the voltage dip event begins; when Urms(1/2) or Urms(1) is equal to or higher than the sum of the dip threshold and the hysteresis voltage, the voltage dip ends. In a multi-phase system, when Urms(1/2) or Urms(1) of any phase is lower than the dip threshold, the voltage dip begins; when Urms(1/2) or Urms(1) of all phases is equal to or higher than the sum of the dip threshold and the hysteresis voltage, the voltage dip ends.
5.2.4 Determination of short interruption In a single-phase system, when Urms(1/2) or Urms(1) is lower than the short interruption threshold, the short interruption event begins; when Urms(1/2) or Urms(1) is equal to or higher than the sum of the short interruption threshold and the hysteresis voltage, the short interruption ends. In a multi-phase system, when Urms(1/2) or Urms(1) of any phase is lower than the short interruption threshold, the short interruption begins; when Urms(1/2) or Urms(1) of all phases is equal to or higher than the sum of the short interruption threshold and the hysteresis voltage, the short interruption ends.
5.3 Method for selecting values of characteristic parameters
5.3.2 Voltage dip The characteristic parameters of voltage dip include residual voltage (Ures) or depth, duration, and phase-angle jump; the residual voltage is the lowest Urms value measured on any channel during the dip. The start time of the voltage dip shall be the end time of the Urms measurement data window triggering the event channel; the end time of the voltage dip shall be the end time of the Urms measurement data window terminating the event channel. Urms is determined by the sum of the threshold and the hysteresis voltage. The duration of a voltage dip is the time difference from the start to the end of the voltage dip.
6 Monitoring of voltage swells, voltage dips and short interruptions
6.1 Classification of monitoring instruments Monitoring instruments are divided into two categories according to their performance, which are defined as follows: Grade A performance - meeting the Grade A measurement method and uncertainty requirements in GB/T 17626.30, capable of accurately measuring the magnitude, duration, phase-angle jump and other characteristic parameters of voltage swell, voltage dip and short interruption. Each measurement channel can measure the r.m.s. voltage refreshed each half-cycle [Urms(1/2)]. This grade of instrument is suitable for occasions where precise measurements are required, such as standard compliance inspection, dispute resolution, power quality contract arbitration, etc. Grade S performance - meeting the Grade S measurement method and uncertainty requirements in GB/T 17626.30, and capable of measuring characteristic parameters such as the magnitude and duration of voltage swells, voltage dips and short interruptions. Each measurement channel can measure the r.m.s. voltage refreshed each half-cycle [Urms(1/2)] or the r.m.s. voltage refreshed each cycle [Urms(1)]. This grade of instrument is suitable for power quality survey statistics, troubleshooting and other applications that do not require high accuracy. An appropriate instrument performance grade shall be selected according to the specific application.
6.2.1 Basic functions
6.2.1.1 Monitoring function The instrument shall be able to perform real-time monitoring of voltage swell, voltage dip or short interruption events through voltage measurement, and obtain characteristic parameters such as magnitude of voltage swell, residual voltage, and duration.
6.2.1.2 Waveform recording function The event waveform record of the instrument shall be able to restore the process of voltage instantaneous waveform changes within the recording time period, and shall include waveforms of at least 5 cycles before the event and at least 20 cycles after the event. Instruments of Grade A performance have the function of recording event waveforms with a recording length of not less than 1 s, and instruments of Grade S performance have the function of recording event waveforms with a recording length of not less than
0.5 s.
6.2.1.3 Other functions The display, communication interface, authority management, parameter configuration, timing, storage and statistical functions of the instrument shall meet the requirements of GB/T 19862 and have the function of threshold setting.
6.2.2 Instrument accuracy The voltage magnitude measurement error of instruments of Grade A performance shall not exceed ±0.2% of the declared input voltage; the voltage magnitude measurement error of instruments of Grade A shall not exceed ±1.0% of the declared input voltage. The duration measurement error of instruments of Grade A performance shall not exceed ±1 cycle; the duration measurement error of instruments of Grade S performance shall not exceed ±2 cycles.
7 Assessment of voltage swells, voltage dips and short interruptions
7.1 General The assessment of voltage swell, voltage dip and short interruption is divided into single measuring point index and system index assessment. Determine the assessment object and scope based on the source and purpose of the assessment task; analyze the index results; form an assessment report. If necessary, corresponding improvement measures shall be suggested.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 35 pages — is available in the English PDF.
Referenced standards
Normative references
GB/T 17626.30
Cited by
- GB/T 19862-2025General requirements for monitoring equipment of power quality
- GB/T 46372-2025Guide for commissioning flywheel energy storage power stations
- GB/T 32507-2024Power quality - Terminology
- GB/T 42737-2023Code for commissioning of electrochemical energy storage station
- GB/Z 42722-2023Implementation guidelines for industrial power demand side management
Similar standards
Editions of GB/T 30137
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 30137-2013 | Power quality - Voltage dips and short interruptions | first issue | Superseded |
| GB/T 30137-2024 | Power quality - Voltage swell, voltage dips and short interruptions | first revision | Current |
This page sells the current edition, GB/T 30137-2024. Earlier editions are listed for reference only.
How to Buy GB/T 30137-2024
- 1Add to cart. Click the "Buy GB/T 30137-2024" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 19862-2025 — General requirements for monitoring equipment of power quality
GB/T 47310-2026 — Determination of total silicon, aluminium, iron, potassium, sodium, calcium, magnesium, manganese, phosphorus, titanium and sulfur in soil - Monochromatic excitation energy dispersive X-ray fluorescence spectrometry
GB/T 47321-2026 — Specification for the warning data exchange of the national emergency early warning dissemination system
Secure payment via Stripe
Payments accepted
GB/T 30137-2024
$425.00