GB/T 26216.1-2019DC current measuring device for HVDC transmission system—Part 1: Electronic DC current measuring device (English PDF)
高压直流输电系统直流电流测量装置 第1部分:电子式直流电流测量装置
This is a limited preview
Buy now to download the full PDF (15 pages)
Need quotation for your management?
Get a formal quotation for GB/T 26216.1-2019 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 10, 2019
Implementation date
July 1, 2020
Scope
GB/T 26216.1-2019 is the English-translated version of 高压直流输电系统直流电流测量装置 第1部分:电子式直流电流测量装置.
GB/T 26216.1-2019 covers electronic DC current measuring devices for HVDC transmission at voltage levels of ±1 100 kV and below.
It specifies the normal and special conditions of use, the ratings, the design and construction, the tests and the markings, and it applies to devices installed on DC pole busbars, at the midpoint of a double twelve-pulse converter valve group, on neutral busbars, on ground electrode leads and in the charging and bridge arm circuits of flexible DC systems.
The ratings it fixes are the rated primary DC current, overload and short-time current, rated primary voltage, maximum continuous operating voltage, insulation level, accuracy class and digital and analogue output.
Type, routine, field and special tests are all described. Part 1 of GB/T 26216, it replaces GB/T 26216.1-2010, was issued on 10 December 2019 and has applied since 1 July 2020.
Found what you need?
Document preview — GB/T 26216.1-2019
National Standard of the People's Republic of China
- ICS
- 29.180
- Classification
- K 41
- Replacing
- GB/T 26216.1-2010
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Normal and special conditions of use
- 5 Rating
- 5.1 Rated primary DC current (Ir)
- 5.2 Overload current
- 5.3 Short-time current rating
- 5.4 Rated primary voltage (Udr)
- 5.5 Maximum continuous operating voltage (Udm)
- 5.6 Insulation level
- 5.7 Accuracy level of the entire current measuring device
- 5.8 Digital output rating
- 5.9 Rated value of analog output
- 6 Design and structure
- 6.1 Sampling rate
- 6.2 Cut-off frequency (-3dB)
- 6.3 Maximum attenuation of fiber transmission
- 6.4 Electrical shielding
- 6.5 Anti-corrosion protection
- 6.6 Design Requirements for Digital Outputs
- 6.7 Shunt
- 6.8 Primary converter room
- 6.9 Optical fiber composite insulator
- 6.10 Junction Box
- 6.11 Merging Unit
- 7 Test
- 7.1 Test classification
- 7.2 General conditions of the test
- 7.3 Type test
- 7.4 Routine test
- 7.5 Field test
- 7.6 Special tests
- 8 signs
- 8.1 Terminal Markings
- 8.2 Nameplate logo
Foreword
GB/T 26216 `` DC Current Measurement Device for HVDC Transmission System '' is divided into two parts.
--- Part 1. Electronic DC current measuring device;
--- Part 2. Electromagnetic DC current measuring device. This part is the first part of GB/T 26216.
This section is drafted in accordance with the rules given in GB/T 1.1-2009.
This section replaces GB/T 26216.1-2010 "DC current measurement devices for high-voltage DC transmission systems. Part 1. Electronic DC Compared with GB/T 26216.1-2010, the main technical changes are as follows.
--- "800" was changed to "1100", "flexible DC transmission system charging circuit and bridge arm circuit" was added to the typical layout position (see (Chapter 1, Chapter 1 of the 2010 edition);
--- Added "In the case of a digital interface, the electronic DC current measurement device is configured with a merge unit to complete this function." (See 3.2);
--- Modify the rated primary DC current value "600A, 3000A, 3125A, 4000A, 4500A" to "500A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A, 5000A, 6300A "(see 5.1, 5.1 of the 2010 version);
--- Modify "Rated Voltage" to "Rated Primary Voltage", where the values "408kV, 515kV, 680kV, 816kV" are modified "400kV, 500kV, 660kV, 800kV", and increase the value "1100kV" (see 5.4, 2010 version 5.4);
--- Increased the "maximum continuous operating voltage" (see 5.5);
--- The "rated DC voltage" in Table 1 was changed to "the highest continuous operating voltage", and the rated DC withstand voltage "1200" in the table was changed to "1224" and added "1122" and its corresponding value (see 5.6, 5.5 of the 2010 version);
--- Respecified the current error value in Table 2 (see 5.7, 5.9 in the 2010 version);
--- Modify "2D41H" to "3A98H (decimal 15000)" and "0CCCH" to "1388H (decimal 5000) (see 5.13, 5.11 of 2010) ";
--- Increased the "sampling rate" (see 6.1);
--- Deleted the "cut-off frequency" and moved it to Chapter 6 (see 6.2, 2010 version 5.7);
--- Adjusted the "maximum attenuation of fiber optic transmission" and moved it to Chapter 6 (see 6.3, 5.10 of the 2010 edition);
--- Removed the "nameplate logo" (see 6.3 of the 2010 version);
--- Deleted the "design requirements for analog voltage output" (see 6.5 of the 2010 version);
--- Added "Combination unit output signal transmission protocol is about TDM, GB/T 20840.8-2007, GB/T 20840.9-2017 may Select "(see 6.6);
--- Deleted "Insulator is composite type, optical fiber is enclosed in it.", "Probe box, composite insulator" was modified to "Optical fiber fusion box, optical Fiber composite insulators "(see 6.10, 6.9 of the 2010 edition);
--- Modify the content of the merging unit to "When the DC current measuring device outputs digital signals, the number of merging units is The number of secondary converters is configured. "(See 6.11, 6.11 of 2010);
--- Modified "error measurement" to "accuracy test" and added "n) temperature cycle test" (see 7.3.1, 7.3 of the 2010 edition);
--- Modify "Ur < 200" to "Udm < 300" and "Ur>=200" to "Udm>=300" (see 7.3.4, 7.3.3 of the 2010 version);
--- Modify "positive polarity DC voltage" to "negative polarity DC voltage" (see 7.3.6, 7.3.5 of the 2010 edition);
--- Added "For DC measurement devices using shunts, the product can be verified by applying a measurement voltage to a primary converter High current measurement performance, "(see 7.3.10);
--- Modify the rise time "400µs" of step response to "250µs" and add "< 100µs (for flexible DC transmission systems)" (See 7.3.11, 2010 version 5.8);
--- Deleted the "frequency response" and used its content as the criterion for the frequency response test (see 7.3.12, 2010 version 5.6);
--- Modify "0.75% (the benchmark is Ir)" to "3%" (see 7.3.12, 2010 version 5.6);
--- Modify "100A" to "5% Ir" (see 7.3.12, 7.3.11 of the 2010 version);
--- Modify d) "Partial discharge measurement" to "d) DC withstand voltage test and partial discharge measurement" (see 7.4.1, 2010 version 7.4);
--- "Partial discharge measurement" was modified to "DC withstand voltage test and partial discharge measurement" Partial discharge measurement. During the test, the pre-voltage was 1.225Ur, and the partial discharge amount did not exceed 50pC. The partial discharge measurement voltage was 1.5Ur/2, partial discharge does not exceed 20pC. Refer to GB/T 7354 for partial discharge measurement. "(See 7.4.5, 2010 edition 7.4.4);
--- Increased criteria for step response tests (see 7.4.6, 7.4.5 of the 2010 version);
--- "For electronic output current measuring devices with digital output, Routine test. "Amended to" can be applied to 0.1pu, 0.2pu, 1.0pu, 1.2pu DC at room temperature in accordance with 7.3.10 Flow to measure accuracy, meeting the requirements of 5.7. "(See 7.4.8, 7.4.7 of the 2010 edition);
--- Added "flags" (see Chapter 8);
--- Removed Appendix A of the 2010 edition.
1 Scope
This part of GB/T 26216 specifies the requirements for electronic DC current measurement devices for DC power transmission of voltage levels of ± 1100kV and below. Normal and special use conditions, ratings, design and construction, tests, etc.
This section applies to electronic DC current measurement devices installed in DC power transmission systems with voltage levels of ± 1100kV and below.Typical Placement locations are DC pole busbars, midpoints of the double twelve pulsation converter valve group (if applicable) busbars, neutral busbars, ground electrode leads, flexible DC output Electric system charging circuit and bridge arm circuit.
2 Normative references
The following documents are essential for the application of this document. For dated references, only the dated version applies to this document. For undated references, the latest version (including all amendments) applies to this document.
GB/T 311.1-2012 Insulation coordination Part 1: Definitions, principles and rules
GB/T 2423.2 Environmental tests for electric and electronic products. Part 2. Test methods Test B. High temperature
GB/T 2423.3 Environmental test Part 2: Test method Test Cab. Constant humidity test
GB/T 2424.25 Environmental testing for electric and electronic products-Part 3: Test guidelines-Earthquake test methods
GB/T 2900.50 Electrical terminology General terminology for power generation, transmission and distribution
GB/T 2900.57 Electrical terminology for power generation, transmission and distribution operation
GB/T 2900.95 Electrical terminology transformers, voltage regulators and reactors
GB/T 7354 High Voltage Test Technology Partial Discharge Measurement
GB/T 11022-2011 Common technical requirements for high-voltage switchgear and control equipment standards
GB/T 16927.1 High voltage test technology-Part 1: General definition and test requirements
GB/T 20840.8-2007 Current transformers Part 8: Electronic current transformers
GB/T 20840.9-2017 Transformers Part 9: Digital Interface for Transformers
GB/T 22707 Artificial pollution test for high-voltage insulators for DC systems
3 Terms and definitions
GB/T 2900.50, GB/T 2900.57, GB/T 2900.95 and GB/T 20840.8-2007 as well as the following terms and definitions The meaning applies to this document. For ease of use, the following lists some of the terms and definitions in GB/T 20840.8-2007.
3.1 DC current measuring device
A device that provides a signal corresponding to the DC current of the primary circuit. The output signal is provided to measuring instruments, meters and protection or control equipment.
3.2 Electronic DC current measuring device
A DC current measuring device consisting of one or more current sensors connected to a transmission system and a secondary converter for transmission Proportional to the measured quantity, the schematic diagram is shown in Figure 1.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 2423.2Environmental testing for electric and electronic products - Part 2: Test methods - Tests B: Dry heat
- GB/T 2423.3Environmental testing - Part 2: Testing method - Test Cab: Damp heat, steady state
- GB/T 2424.25Environmental testing - Part 3: Test guidance - Seismic test methods
- GB/T 2900.50Electrotechnical terminology -- Generation, transmission and distribution of electricity -- General
- GB/T 2900.57Electrotechnical terminology -- Generation, transmission and distribution of electricity -- Operation
- GB/T 2900.95Electrotechnical terminology -- Transformers, voltage regulators and reactors
GB/T 311.1-2012
Cited by
- GB/T 42558.1-2023Seismic techniques of electrical equipment in converter station on plateau—Part 1:Directives for seismic test and evaluation
- GB/T 25308-2022DC filters for high voltage direct current transmission systems
- DL/T 1981.1-2019Unified power flow controller -- Part 1: function specifications
- DL/T 2004-2019DC current transformer use technical conditions
- GB/T 31487.3-2015Direct current de-icing devices -- Part 3: Tests
Similar standards
Editions of GB/T 26216.1
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 26216.1-2019 | DC current measuring device for HVDC transmission system—Part 1: Electronic DC current measuring device | current edition | Current |
| GB/T 26216.1-2010 | DC current measuring device for HVDC transmission system—Part 1: Electronic DC current measuring device | previous edition | Superseded |
This page sells the current edition, GB/T 26216.1-2019. Earlier editions are listed for reference only.
How to Download GB/T 26216.1-2019
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 16927.1-2011 — High-voltage test techniques -- Part 1: General definitions and test requirements
GB/T 20840.8-2007 — Instrument transformers -- Part 8: Electronic current transformers
GB/T 20840.9-2017 — Instrument transformers -- Part 9: Digital interface for instruments transformers