Scope
GB/T 19837-2019 is the English-translated version of 城镇给排水紫外线消毒设备.
GB/T 19837-2019 covers ultraviolet disinfection equipment for urban water supply and drainage works. It gives the classification and composition of the equipment, its requirements, the testing, the inspection rules and the rules for marking, packaging, transport and storage.
Equipment is tube type or channel type by use, and low pressure or medium pressure by lamp; channel equipment must carry at least the lamp modules and their bracket, the power distribution and system control centres, the water level control and the online dose monitoring.
It defines the UV lamp aging factor as the ratio of the lamp's output power at a given time to its output after 100 hours. It applies to drinking water, purified drinking water, municipal sewage effluent and reclaimed water.
It replaces GB/T 19837-2005, was issued on 10 December 2019 and has applied since 10 December 2019.
Found what you need?
Document preview — GB/T 19837-2019
National Standard of the People's Republic of China
- ICS
- 91.140.70
- Classification
- P 40
- Replacing
- GB/T 19837-2005
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Classification and composition
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
This standard replaces GB/T 19837-2005 "Urban UV disinfection equipment for water supply and drainage". This standard is in line with GB/T 19837-2005 In addition to editorial changes, the main technical content changes are as follows.
--- Revised "Scope" (see Chapter 1, Chapter 1 of the 2005 edition);
--- Modified "terms and definitions" (see Chapter 3, Chapter 3 of the 2005 edition);
--- Modified "classification and composition" (see Chapter 4, Chapter 4 of the 2005 edition);
--- Modified the "packaging" requirements (see 8.2.2, 8.2.3, 8.2.4, Chapter 1 of the 2005 edition);
--- Modified the "Test Method for UV Lamp Life and Aging Coefficient" (see Appendix A, Appendix A of the 2005 edition);
--- Modified the "Method for Detecting the Scaling Coefficient of Ultraviolet Lamp Sleeve" to stipulate by referring to Appendix B in GB/T 32091-2015 (see 6.3, (Appendix B of the 2005 edition);
--- Modified the ultraviolet effective dose and average dose detection methods, and explicitly adopted the quasi-parallel light detection method to quote
GB/T 32091 specifies Appendix E (see 6.5, Appendix C and Appendix D of the 2005 edition);
--- Deleted the "design requirements for ultraviolet disinfection equipment" (see Appendix E of the 2005 edition).
1 Scope
This standard specifies the classification and composition, requirements, testing and inspection, inspection rules, signs, packaging, Transportation and storage.
This standard applies to urban water supply and drainage such as drinking water, drinking water purification, urban sewage treatment plant effluent, and urban sewage recycling water. UV water disinfection equipment.
2 Normative references
The following documents are essential for the application of this document. For dated references, only the dated version applies to this document. For undated references, the latest version (including all amendments) applies to this document.
GB/T 191 Packaging, storage and transportation icon
GB/T 4208 enclosure protection grade (IP code)
GB/T 9969 General Instructions for Use of Industrial Products
GB/T 13384 General technical requirements for packaging of electromechanical products
GB 18918 Pollutant Discharge Standard for Urban Sewage Treatment Plants
GB/T 32091-2015 UV dose test method for UV water disinfection equipment
GB/T 32092 Terminology of ultraviolet disinfection technology
3 Terms and definitions
The terms and definitions defined in GB/T 32092 and the following apply to this document.
3.1 UV lamp aging factor
The ratio of the UV output power of the UV lamp at a certain time to the UV output power of the UV lamp after 100 hours of initial operation.
4 Classification and composition
4.1 Classification
Divided into tube-type ultraviolet disinfection equipment and channel-type ultraviolet disinfection equipment according to the use method; can be divided into low-pressure ultraviolet rays according to the type of lamp Disinfection equipment and medium pressure UV disinfection equipment.
4.2 Composition
4.2.1 Channel UV disinfection equipment shall include at least UV lamp module group, module bracket, power distribution center, system control center, and water level control System, UV dose online monitoring system.
4.2.2 The tubular UV disinfection equipment shall include at least UV reactor, power distribution center, system control center and UV dose online monitoring
4.2.3 The system control center shall include at least hardware and software for monitoring the ultraviolet dose, a central controller and a monitoring operation interface.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 191Graphical symbols marking for handling and storage of packages
- GB/T 4208Degrees of protection provided by enclosures (IP code)
- GB/T 9969General principles for preparation of instructions for use of industrial products
- GB/T 13384General specifications for packing of mechanical and electrical product
- GB 18918Discharge standard of pollutants for municipal wastewater treatment plant
- GB/T 32091-2015Ultraviolet equipment for water disinfection—Ultraviolet dose testing method
Cited by
- GB 28235-2020Hygienic requirements for ultraviolet appliance of disinfection
- JY/T 0593-2019Technical requirements and specifications on the drinking water equipment with membrane treatment for primary and middle schools
- CECS 375-2014Technical specification for integrated rotating biological contactor sewage treatment device
- GB/T 29153-2012Water reclamation and reuse facility
- HJ 2015-2012Technical guidelines on water pollution control engineering
- HJ 2522-2012Technical requirement for environmental protection products. Ultraviolet disinfection equipment
Similar standards
Editions of GB/T 19837
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 19837-2019 | Ultraviolet (UV) disinfection equipment for urban water and wastewater engineering | current edition | Current |
| GB/T 19837-2005 | Ultraviolet (UV) disinfection equipment for urban water and wastewater engineering | previous edition | Superseded |
This page sells the current edition, GB/T 19837-2019. Earlier editions are listed for reference only.
How to Download GB/T 19837-2019
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 18918-2002 — Discharge standard of pollutants for municipal wastewater treatment plant
GB/T 13384-2008 — General specifications for packing of mechanical and electrical product
GB/T 191-2025 — Graphical symbols marking for handling and storage of packages
Secure payment via Stripe
Payments accepted
GB/T 19837-2019
$145.00