Valid

GB/T 19232-2019Fan coil unit (English PDF)

风机盘管机组

Preview PDF

This is a limited preview

Buy now to download the full PDF (60 pages)

Need quotation for your management?

Get a formal quotation for GB/T 19232-2019 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

August 30, 2019

Implementation date

July 1, 2020

Scope

GB/T 19232-2019 is the English-translated version of 风机盘管机组.

GB/T 19232-2019 is the Chinese national standard for fan coil units. It covers terms and definitions, classification and labelling, general requirements, requirements, test methods, inspection rules and the marking, packaging, transport and storage of the unit.

It applies to units fed with externally supplied chilled or hot water whose supply air volume does not exceed 3400 m³/h and whose external static pressure does not exceed 120 Pa.

Units are classified by structure, installation method, water connection side, external static pressure, application type, motor type and pipe system, each with its own code letter, and the three annexes give the test methods for air volume, for cooling and heating capacity and for noise.

It replaces GB/T 19232-2003, was issued on 30 August 2019 and has applied since 1 July 2020.

Found what you need?

Document preview — GB/T 19232-2019

National Standard of the People's Republic of China

ICS
91.140.30
Classification
P 48
Replacing
GB/T 19232-2003

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword3
  • 1 Scope5
  • 2 Normative References5
  • 3 Terms and Definitions6
  • 4 Classification and Labeling8
  • 5 General Requirements9
  • 6 Requirements24
  • 7 Test Methods26
  • 8 Inspection Rules35
  • 9 Marking, Packaging, Transportation, and Storage36
  • Appendix A (Normative) Test Method for Air Volume of Fan Coil Unit39
  • Appendix B (Normative) Test Methods for Cooling and Heating Capacity of Fan Coil Unit46
  • Appendix C (Normative) Noise Test Methods for Fan Coil Unit60

1 Scope

This Standard specifies the terms and definitions, classification and labeling, general requirements, requirements, test methods, inspection rules, marking, packaging, transportation and storage of fan coil unit (hereinafter referred to as "unit").

This Standard applies to unit that uses externally supplied chilled or hot water to cool, heat, or separately cool and heat rooms, with a supply air volume not exceeding 3400 m³/h and an external static pressure not exceeding 120 Pa. Unit with similar applications may also refer to this Standard.

2 Normative References

The following documents are essential to the application of this Document. For the dated documents, only the versions with the dates indicated are applicable to this Document; for the undated documents, only the latest version (including all the amendments) is applicable to this Document.

GB/T 191 Packaging - Pictorial marking for handling of goods

GB/T 1040.1 Plastics - Determination of tensile properties - Part 1: General principles

GB/T 2423.3 Environmental testing - Part 2: Testing method - Test Cab. Damp heat, steady state

GB/T 2518 Continuously hot-dip zinc-coated steel sheet and strip

GB/T 3198 Aluminum and aluminum alloy foils

GB/T 3880 Aluminum and aluminum alloy plates and strips for general industrial use

GB/T 5171.1-2014 Small power motors - Part 1: General technical requirements

GB/T 9068 Determination of sound power levels for noise emitted by heating, ventilating and air conditioning equipment - Engineering method

GB/T 11253 Cold-rolled sheets and strips of carbon structural steels

GB/T 12350 Safety requirements of small power motors

GB/T 15675 Continuously electrolytically zinc/zinc-nickel alloy coated steel sheet and strip

GB/T 17791 Seamless copper and copper alloys tube for air conditioner and refrigeration equipment

GB 50016-2014 Code for Fire Protection Design of Buildings

JG/T 21-1999 Test methods for determining the performance of air cooling and air heating coils

3 Terms and Definitions

For the purposes of this Document, the following terms and definitions apply.

3.1 Fan coil unit

The basic configuration of air handling equipment includes fans, coils, motors, condensate pans, etc. Depending on the usage requirements, additional accessories such as controllers, drainage and air-blocking devices, air filters and purification devices, air inlet and outlet ducts, and air inlet and outlet distributors can be configured.

3.2 Rated value

The basic performance values of the unit under the test conditions specified in the standard.

3.3 Nominal value

The values marked on the product nameplate and product sample.

3.4 Rated air volume flow rate

The volumetric air flow rate delivered by the unit per unit time under the test conditions specified in the standard.

NOTE: Unit is m³/h.

3.5 Rated cooling capacity

The total cooling capacity measured by the unit under the test conditions specified in the standard is the sum of sensible heat and latent heat.

NOTE: The unit is W or kW.

3.6 Rated heating capacity

The total sensible heat output of the unit measured under the test conditions specified in the

4 Classification and Labeling

4.1 Classification

4.1.1 According to structural form, they can be divided into horizontal, vertical, cassette, and wall-mounted types, designated by "W", "L", "K", and "B", respectively.

4.1.2 According to installation method, they can be divided into surface-mounted and concealed-mounted types, designated by "M" and "A", respectively.

4.1.3 According to inlet and outlet water orientation, they can be divided into left-hand and right-hand types (facing the unit's air outlet, the supply and return water pipes are on the left and right sides respectively), designated by "Z" and "Y", respectively.

4.1.4 According to external static pressure, they can be divided into low static pressure type and high static pressure type. The code for low static pressure type is omitted; and the code for high static pressure type is "G + external static pressure value".

NOTE: For low static pressure units with accessories such as air outlets and filters, the default external static pressure is 0 Pa; for low static pressure units without accessories such as air outlets and filters, the default external static pressure is 12 Pa. High static pressure units are tested without air outlets and filters.

4.1.5 According to application type, they can be divided into general-purpose unit, dry fan coil unit, and heating fan coil unit. The code for general-purpose is omitted; the codes for dry fan coil unit and heating fan coil unit are "G" and "R", respectively.

4.1.6 According to motor type, they can be divided into AC motors and permanent magnet synchronous motors. The code for AC motors is omitted; the code for permanent magnet synchronous motors is "YC".

4.1.7 According to the type of pipe system, it can be divided into two-pipe system (one coil for a single water system, used for both cooling and heating) and four-pipe system (two coils for two separate water systems, one for cooling and one for heating). The code for two-pipe system is "2 (number of coil rows)"; and the code for four-pipe system is "4 (number of cold water coil rows + number of hot water coil rows)".

4.2 Labeling

EXAMPLE: A horizontal, concealed, left-hand water inlet, high static pressure 50Pa, AC motor, two-pipe system, three-row fan coil unit for general-purpose with a rated air volume flow rate of 680m³/h, labeled as FP-68WA-Z-2(3)-G50.

5 General Requirements

5.1 The unit shall be in accordance with the provisions of this standard and shall be manufactured according to the drawings and technical documents approved through the prescribed procedures.

5.2 The unit's structure shall meet the following requirements.

a) The length and slope of the condensate pan shall ensure unobstructed condensate drainage and that condensate from the unit drips into the pan;

b) The unit shall be equipped with an air venting device at a location that effectively removes trapped air from the coils;

c) For units with special functions (such as antibacterial, sterilization, purification, etc.), the components enabling these functions shall meet the requirements of relevant national regulations and standards;

d) Dry fan coil unit shall be equipped with a condensate pan;

e) Heating fan coil unit may not require insulation and may not be equipped with a condensate pan.

5.3 The unit's adjustment characteristics shall meet the following requirements.

a) AC motor units and permanent magnet synchronous motor units shall be able to adjust the air volume flow rate. When three air volume flow rate levels (high, medium, and low) are provided, the ratio of the three levels should be 1 : 0.75 : 0.5 of the rated air volume flow rate.

b) For permanent magnet synchronous motor units that do not have a default setting when leaving the factory, the highest level of air volume flow rate shall be used for testing.

5.4 The power supply for the unit shall be single-phase 220V, frequency 50Hz.

5.5 The unit materials shall meet the following requirements.

a) The materials used in the unit shall be free from rust and mildew, and the use of new materials that meet environmental protection requirements is encouraged;

b) The insulation materials of the unit shall comply with the provisions of 9.3.15 in GB 50016-2014; and the bonding shall be flat and firm;

c) The materials for the main parts of the unit shall be selected according to the requirements in Table 1; and the use of high-quality materials superior to those in Table 1 is encouraged;

d) When the unit uses cold-rolled steel plates for its panels and components, its inner and outer surfaces shall be effectively rust-proofed;

e) When the unit uses ferrous metal processed parts, the surfaces shall be hot-dip galvanized and effectively rust-proofed.

5.6 The rated values of the basic specifications of general-purpose units at high speeds shall meet the requirements of Tables 2 ~ 4, respectively. […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 60 pages — is available in the English PDF.

Referenced standards

Similar standards

Editions of GB/T 19232

EditionTitleRevisionStatus
GB/T 19232-2019Fan coil unitcurrent editionCurrent
GB/T 19232-2003Fan coil unitprevious editionSuperseded

This page sells the current edition, GB/T 19232-2019. Earlier editions are listed for reference only.

How to Download GB/T 19232-2019

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
60 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 19232-2019

$530.00