GB/T 12242-2021Pressure relief devices - Performance test code (English PDF)
压力释放装置 性能试验方法
Open the GB/T 12242-2021 preview as PDF
This is a limited preview
Buy now to download the full PDF (38 pages)
Issued by
State Administration for Market Regulation; Standardization Administration of China
Level / Type
National · Recommended
Issue date
March 9, 2021
Implementation date
October 1, 2021
Scope
GB/T 12242-2021 is the English-translated version of 压力释放装置 性能试验方法.
GB/T 12242-2021 is the Chinese national standard on pressure relief devices - performance test code, in the field of environment and health protection, safety. The /T suffix marks it as a recommended standard: it is not compulsory by itself, but it becomes binding as soon as a contract, a tender or a customer specification calls it up - which in practice is how most foreign buyers meet it. It was issued on 9 March 2021 by the State Administration for Market Regulation; Standardization Administration of China, and has been in force since 1 October 2021. Classification: ICS 13.240, CCS J16. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
Document preview — GB/T 12242-2021
National Standard of the People's Republic of China
- ICS
- 13.240
- Classification
- J16
Issued by: State Administration for Market Regulation; Standardization Administration of China
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 General terms
- 3.2 Types of pressure relief devices
- 3.3 Characteristic dimensions of pressure relief device
- 3.4 Characteristic dimensions of non-reclosing pressure relief devices
- 3.5 Action and displacement characteristics of the pressure release device
- 4 General
- 5 Pressure release device action performance and displacement test
- 5.1 Test equipment and instruments
- 5.2 Measurement method
- 5.2.4 Flow measurement
- 5.2.7 Conditions under which correction can be carried out
- 5.3 Test installation requirements
- 5.4 Test procedure
- 5.5 Calculation of results
- 5.6 Test summary report
- 6 In-use test and constant pressure test on workbench
- 6.1 Measuring instruments and measuring methods
- 6.2 Test procedures in use
- 6.3 Constant pressure test procedure on the workbench
- 6.4 Seal test
- 6.5 Calculation of results
1 Scope
GB/T 12242-2021 is the Chinese national standard on pressure relief devices - performance test code, in the field of environment and health protection, safety. The /T suffix marks it as a recommended standard: it is not compulsory by itself, but it becomes binding as soon as a contract, a tender or a customer specification calls it up - which in practice is how most foreign buyers meet it. It was issued on 9 March 2021 by the State Administration for Market Regulation; Standardization Administration of China, and has been in force since 1 October 2021. Classification: ICS 13.240, CCS J16. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
This document specifies the test methods for the operating performance test (including mechanical characteristics), displacement and resistance coefficient of the pressure release device. This document is applicable to test procedures with various import and export conditions, and the test medium is steam and gas whose physical properties are known. (Air) or liquid (water); including reclosing and non reclosing pressure relief devices, as follows:
a) safety valve,
b) Bursting disc device,
c) Break/shear pin device,
d) Fusible plug device. When the parties involved in the test agree to accept the terms of this document, this document can also be applied to other pressure relief devices.
2 Normative references
The contents of the following documents constitute the indispensable clauses of this document through normative references in the text. Among them, dated quotations Only the version corresponding to that date is applicable to this document; for undated reference documents, the latest version (including all amendments) is applicable to This document.
GB/T 2624.1 Use a differential pressure device installed in a circular cross-section pipe to measure the flow of fluid in a full pipe. Part
3 Terms and definitions
The following terms and definitions defined in GB/T 12241 apply to this document.
3.1 General terms
3.1.1 Pressure relief device A device used to prevent the pressure of the internal medium from rising to exceed the predetermined maximum pressure when the pressure vessel is in an emergency or abnormal situation.
3.1.2 Pressure relief valve pressure relief valve; PRV A valve used to prevent the pressure of the internal medium from rising to exceed the predetermined maximum pressure when the pressure vessel is in an emergency or abnormal situation.
3.1.3 Field test fleldtesting In order to determine some or all of the working characteristics of the pressure relief device, the test of the pressure relief device installed on the system.
3.1.4 In-service testing In order to determine some or all of the working characteristics of the pressure relief device, use system pressure or use an external pressure source (with or without auxiliary Lifting device) A test of a pressure relief device installed on the system that is protecting the system.
3.1.5 Displacement test flowcapacitytesting Determining the operating characteristics of the pressure relief device includes a test to measure the displacement.
3.1.6 Benchtesting A test on a pressurized system to determine the set pressure of the pressure relief device and the tightness of the closure.
3.2 Types of pressure relief devices
3.2.1 Reclosing pressure-Relieving devices Designed as a pressure release device that is driven by the inlet static pressure and re-closes after returning to normal working conditions.
Note. The structure types are spring direct load type, pilot type, power operation type.
3.2.2 Non-reclosing pressure relief device A pressure release device that remains open after an action can provide a means of manual reset.
Note. Non-reclosing pressure release devices include rupture discs, breaking pins, bending pins, shear pins, and fusible plugs.
3.2.2.1 Rupture disk device The function of a non-reclosing pressure release device driven by the static pressure difference between the inlet and outlet of the device is realized by the blasting of the pressure-bearing piece.
3.3 Characteristic dimensions of pressure relief device
3.3.1 Dischargearea The minimum cross-sectional area of the fluid passage when the valve is discharged.
3.3.2 Nozzlearea The minimum cross-sectional area of the flow path from the inlet end of the valve to the sealing surface of the closing member.
3.3.3 Nozzlediameter Corresponds to the diameter of the flow channel area.
3.3.4 Curtainarea When the valve flap rises above the valve seat, the cylindrical or conical discharge channel area is formed between the sealing surfaces.
Note. The area of the curtain is shown in Figure 1.
3.3.7 Seatangle The angle between the valve axis and the sealing surface.
Note. The bevel angle of the sealing surface of the flat sealing valve is 90°.
3.4 Characteristic dimensions of non-reclosing pressure relief devices
3.4.1 Net flow area netflowarea The area of the flow rate is determined after the non-reclosing pressure release device operates.
Note. The (minimum) net flow area of a rupture disc is the calculated net area after it is completely ruptured, and it has an appropriate tolerance, because some structural parts of the rupture disc May reduce its net circulation area.
3.5 Action and displacement characteristics of the pressure release device
3.5.1 Set pressure The inlet static pressure raised by the pressure release device, under which the device exhibits the definition of opening pressure, sudden jump pressure, and starting leakage pressure One of the action characteristics of force, burst pressure, and breaking pressure (for a specific device design, the applicable action characteristics are determined by the device manufacturer. set).
3.5.2 Overpressure The pressure increase exceeding the set pressure of the pressure release valve, at which the safety valve reaches the opening height specified by the manufacturer.
Note. The excess pressure is usually expressed as a percentage of the set pressure.
3.5.3 Re-seating pressure After the pressure release valve is discharged, the disc contacts the valve seat again, that is, the pressure when the opening height becomes zero.
3.5.4 Blowdown The difference between the set pressure and the return pressure.
Note. The opening and closing pressure difference is expressed as a percentage of the set pressure or in pressure units.
3.5.5 Discharge pressure Set pressure plus over pressure.
3.5.6 Rated discharge pressure flow-ratingpressure The inlet static pressure when measuring the displacement of the pressure release device.
3.5.7 Backpressure The static pressure generated at the outlet of the pressure relief device due to the presence of pressure in the exhaust system.
3.5.8 Built-upbackpressure The pressure generated at the outlet of the device as the medium flows through the pressure relief device into the discharge system.
3.5.9 Superimposedbackpressure The pressure that exists at the outlet of the pressure relief device immediately before it operates.
Note. The additional back pressure is caused by other pressure sources in the exhaust system.
3.5.10 Burst pressure When the bursting disc device operates, its inlet static pressure.
3.5.11 Specified burst pressure of bursting disc device specified burst pressure of a rupture disk device The inlet static pressure of the bursting disc device is increased, and the bursting disc is designed to burst at this pressure at a specified temperature.
4 General
4.1 The measurement deviation of the test in this document is specified as follows: For the displacement test, the deviation of the final displacement measurement should not exceed the measured value. ±2.0%; for the action performance test, the deviation of the pressure measurement should not exceed ±0.5% of the measured value; for the test in use and the setting on the workbench For pressure test, the deviation of pressure measurement should not exceed ±1.0% of the measured value.
4.2 For the tests specified in this document, the test device should have the pressure and sufficient capacity required by the tested pressure release device, and should meet The pressure release device or pressure release valve discharge pressure test needs, and the test duration should meet the required action under stable conditions The need for performance and displacement data. The test operating conditions shall be maintained in accordance with the requirements of the test procedure.
4.3 On-site installation or abnormal operating conditions may adversely affect the function of the pressure relief device. Evaluate the pressure relief device in The applicability and reliability under such conditions are outside the scope of this document.
4.4 If there is a big difference between the temperature of the medium used in the pressure release device test and the temperature the device is subjected to in actual use, the The functional characteristics in actual use, such as opening pressure, opening and closing pressure difference, and burst pressure, will be different from those obtained from the test. Consider these differences The content of making appropriate amendments to the pressure relief device under test conditions does not belong to the scope of this document.
4.5 This document provides recommended test procedures and test instruments. As long as other test procedures and test instruments can be proved to have at least the If the document requires equivalent accuracy and reliability, it can be used. If other procedures and instruments are to be used, the test should be obtained before the test Written consent of the parties concerned.
4.6 The test results shall be reported according to measurement and calculation. Only when the test fully complies with the mandatory requirements of this document can it be designated It is a test conducted in accordance with this document.
4.7 The parties involved in the test shall deal with the design and overpressure protection of the piping system and components, the safe discharge of the pressure release device during the test, and the general Special consideration is given to the high noise that accompanies the emission to ensure that the test device meets the minimum mandatory requirements.
4.8 The parties to the test shall reach an agreement on the following matters before conducting the test.
a) Test purpose;
b) Test site, test parties, test and test supervisors;
c) The benchmark condition of the test fluid under the rated discharge pressure;
d) Test methods, instruments and equipment used in the test (the calibration of the instrument should be in accordance with 5.1.2);
e) The number, diameter, type, condition, source, set pressure and expected displacement of the tested device;
f) Written test procedures, the procedures should include the observations and readings that should be recorded in order to meet the purpose of the test.
5.1 Test equipment and instruments
5.1.1 Test device The layout of the test device is shown in Figure 2~Figure 7 and Figure 9. To ensure its accuracy within the expected use range.
5.1.2.6 Steam calorimeter The steam calorimeter should be calibrated at the time of its installation and within the specified period. When the measurement result shows that the reading is obviously wrong At time or after reinstallation, calibration should be performed again.
5.1.2.7 Flowmeter combination The calibration of the flowmeter should include the actual pipes and all accessories on the upstream and downstream sides of the flowmeter. The connection between the container and the valve. The calibration should be completed before the execution of the formal test by the method of comparison, that is, the flow measurement value should be calibrated in advance. The value measured by the accurate flowmeter device is compared, and the latter's calibration is done with the aid of the original device or mechanism. About pre-calibration The agreement of the flow meter device should make the deviation of the final overall test result within ±2.0%. The calibration should be at the smallest, Performed at middle and maximum flow. For valves with different inlet connection forms, the connections should be made by laboratory personnel during manufacture or purchase. Calibration by the operator. In addition, the flow meter device should be recalibrated at least once every 5 years as described above. This recalibration should include the use of at least two Various sizes of connectors. Calibration records should be kept and audited by relevant parties. If a change is made to the equipment, it should be assessed that the change may affect the system. For the impact of system calibration, a new calibration should be performed when deemed necessary.
5.1.3 Adjustments in the test When collecting data, no adjustments should be made to the pressure release device. After any change or deviation of the test conditions, adequate Time allows the flow, temperature and pressure to stabilize before collecting data.
5.1.4 Test records and test results The test record should include all observations, measurements, meter readings and meter calibration records (when needed) of the test object. Original test record The records should be kept by the institution conducting the test. Copies of all test records should be submitted to all parties to the test. The correction and correction value should be loaded into the test record separately record. The test summary report shall be made in accordance with the provisions of 5.6.
5.1.5 Measurement error Preliminary tests should be carried out to determine that the specified instruments and procedures can meet the error limits specified in
4.1 for the final displacement measurement. limit. An error analysis after the test should also be performed, unless all parties to the test agree and verify that the specified instruments and procedures including the discreteness of the data are based on The test specifications are used and executed to confirm that the error determined by the preliminary test is still valid after the test. The error determination should be determined by the shape of the test chamber Documented for review.
5.2 Measurement method
5.2.1 Atmospheric pressure measurement Atmospheric pressure should be measured with a barometer. When calculating including displacement, if the rated discharge pressure of the pressure relief device is equal to or higher than At 0.15MPa (gauge pressure), the average atmospheric pressure of the test area can meet the accuracy requirements of this document. On this occasion, the recorded The pressure can be average atmospheric pressure.
5.2.2 Temperature measurement The requirements for temperature measurement are as follows:
a) According to the operating conditions, temperature measurement can use glass tube liquid thermometer, bimetal thermometer, resistance thermometer or thermoelectric I. The glass tube liquid thermometer should be inserted into the sleeve, and the bimetal thermometer, resistance thermometer or thermocouple can be directly inserted into the tube In the channel, it can also be inserted into the casing. When the temperature is lower than 150°C, the temperature measuring device should be directly inserted into the pipeline without additional casing.
b) When taking any temperature measurement, the following measures should be taken. 1) Except for the measured medium, there should be no large heat transfer between the temperature measuring device and the outside world due to radiation or conduction. 2) The immediate vicinity of the insertion point and the exposed part of the temperature measuring device should be insulated. 3) The insertion depth of the small diameter pipe temperature measuring device should pass through the center line of the pipe; when the pipe diameter exceeds 300mm, the temperature measuring device The device should be inserted into the media stream at least 150mm deep. 4) On pipelines that transport compressible fluids, the temperature measuring device should be installed when the maximum medium flow rate does not exceed when performing flow measurement. 30m/s. If this is not possible, the temperature reading may need to be corrected to the appropriate static or full temperature. 5) The insertion position of the temperature measuring device should be such that the measured temperature represents the temperature of the flowing medium.
c) When using a glass tube mercury thermometer to measure temperature, the thermometer should have a graduated rod. When the measured temperature is the same as the ambient temperature When the difference is greater than 5°C and the mercury is partially exposed, the exposed rod should be corrected, or an exposed rod thermometer should be used.
d) When using a thermometer casing, the casing should be thin-walled and its diameter should be as small as possible. There should be no corrosion or debris on the outside of the casing. casing The inside should be filled with appropriate fluid, but mercury should not be used. If mercury is used, appropriate precautions should be taken.
e) If a thermocouple is used, it should have a soldered hot end, and it should be calibrated in the expected range of use together with its external wires. The thermocouple should be made of materials suitable for the measured temperature and medium. The electromotive force should be measured with a potentiometer or millivoltmeter. The cold junction of the thermocouple should be formed by using an ice bath (reference standard) or by installing a compensation circuit on the potentiometer.
5.2.3 Pressure measurement The requirements for pressure measurement are as follows:
a) The pressure measuring point should be arranged in the area where the flow is basically parallel to the pipe wall or container wall. When measuring a static pressure difference of less than 0.1MPa, A liquid pressure gauge can be used.
b) The pressure of the test vessel should be the static pressure measured through the pressure tap shown in Figure 2.
c) The back pressure should be the static pressure measured through the pressure tap shown in Figure 3, Figure 5 and Figure 6.
d) If there is a water level difference or other level difference between the pressure measurement point and the pressure gauge, the pressure reading should be appropriately corrected.
5.2.4 Flow measurement
5.2.4.1 The methods for measuring the displacement of the pressure release device are.
a) Subsonic inferred flowmeter, including orifice plate, flow nozzle and venturi tube;
b) Sound velocity inferred flowmeter, including plug flow nozzle;
c) Volume method or gravimetric method for directly collecting the discharge medium or its condensate.
5.2.4.2 The following methods shall be used to measure the displacement of the pressure release device as appropriate.
a) The steam flow rate when the back pressure is atmospheric pressure, using the method 5.2.4.1a) or 5.2.4.1c);
b) The steam flow rate when the back pressure is higher than the atmospheric pressure, use the method 5.2.4.1a);
c) The flow of air or gas when the back pressure is atmospheric pressure, using the method 5.2.4.1a) or 5.2.4.1b);
d) The flow of air or gas when the back pressure is higher than atmospheric pressure, using the method 5.2.4.1a);
e) The liquid flow rate when the back pressure is atmospheric pressure, using the method 5.2.4.1a) or 5.2.4.1c);
f) The liquid flow rate when the back pressure is higher than the atmospheric pressure, use the method 5.2.4.1a).
Note. During the test, the back pressure may be higher than the atmospheric pressure. Pay attention to the use of the sound velocity inferred flowmeter.
5.2.4.3 One-time measuring element.
a) The primary measuring element should be placed on the upstream side of the inlet of the pressure relief device under test. Installation requirements and meter location are shown in Figure 2.hole The ratio of the plate hole diameter to the pipe inner diameter should be between
5.2.7 Conditions under which correction can be carried out
5.2.7.1 Steam. The reference condition is dry saturated steam. In the test, the steam condition at the inlet of the pressure release device should be that the steam dryness is not small At 98% or overheating is not more than 10°C.
5.2.7.2 Water. The reference condition is 18°C~24°C. The temperature range of the water at the inlet of the pressure release device in the test should be 5°C~50°C.
5.2.7.3 Air and other gases. the reference condition is 13°C~24°C. Air or other gas at the inlet of the pressure release device during the test The temperature range should be -18°C~93°C.
5.2.7.4 If the test condition is not within the range of 5.2.7.1~5.2.7.3, the correction from the actual test condition to the reference condition cannot be carried out. The actual test pressure should not be corrected.
5.2.8 Medium composition A medium with well-defined physical properties should be used as the test medium. If there is any doubt about the physical properties of the fluid, physical experiments or chemical Learn to analyze to determine.
5.3 Test installation requirements
5.3.1 The pressure release device under test shall use connecting accessories (flange type, thread type or welding type, etc.). The acceptable internal cross-sectional shape is shown in Figure 8) Install directly on the test vessel. As long as it does not affect the accuracy of the test results, other connection accessories can also be used; no matter which one is used To connect in any way, it should be ensured that the inner diameter of the connection accessory test vessel interface is greater than the inner diameter of the pressure release device under test.
5.3.2 For the test where the back pressure before discharge is atmospheric pressure, the test arrangement should be such that the medium is directly discharged from the pressure release device to the atmosphere or the condenser (see Figure 2, Figure 3 and Figure 4). When using a discharge pipe, the pipe size should be at least equal to the outlet size of the pressure relief device. Support for discharge pipe Should be independent of the pressure relief device, its support method should not affect the action of the pressure relief device. Measures should be taken to ensure the pressure relief device And the discharge pipeline is strong enough to withstand the combined force generated by the discharge.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 38 pages — is available in the English PDF.
Referenced standards
Similar standards
Editions of GB/T 12242
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 12242-2021 | Pressure relief devices - Performance test code | current edition | Current |
| GB/T 12242-2005 | Performance test code - Pressure relief devices | previous edition | Superseded |
This page sells the current edition, GB/T 12242-2021. Earlier editions are listed for reference only.
How to Buy GB/T 12242-2021
- 1Add to cart. Click the "Buy GB/T 12242-2021" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 12243-2021 — Spring loaded safety valves
GB/T 47310-2026 — Determination of total silicon, aluminium, iron, potassium, sodium, calcium, magnesium, manganese, phosphorus, titanium and sulfur in soil - Monochromatic excitation energy dispersive X-ray fluorescence spectrometry
GB/T 47321-2026 — Specification for the warning data exchange of the national emergency early warning dissemination system
Secure payment via Stripe
Payments accepted
GB/T 12242-2021
$860.00