Valid

GB 5135.5-2018Automatic sprinkler systems - Part 5: Deluge alarm valves (English PDF)

自动喷水灭火系统 第5部分:雨淋报警阀

Open the GB 5135.5-2018 preview as PDF

Preview — first pages of GB 5135.5-2018 (full document: 19 pages)

This is a limited preview

Buy now to download the full PDF (19 pages)

Issued by

General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC

Level / Type

National · Mandatory

Issue date

June 7, 2018

Implementation date

January 1, 2019

Scope

GB 5135.5-2018 is the English-translated version of 自动喷水灭火系统 第5部分:雨淋报警阀.

Part 5 of China's mandatory series on automatic sprinkler systems, covering the deluge alarm valve - the valve that holds water out of a deluge or pre-action system and opens on command to admit it to every open head at once. It is the component on which those systems entirely depend: in a deluge system the heads are open and nothing but this valve stands between the water and the protected space, so a valve that leaks floods a room that is not on fire and a valve that fails to open leaves the system inert. This part specifies the terms and definitions, the classification and code, the model designation, the requirements, the test methods, the inspection rules, the marking and instructions, and the packaging, transport and storage of deluge alarm valves. The requirements cover the strength and tightness of the valve body under system pressure held indefinitely; the opening on command, with the response time and the reliability of the release, whether the trip is hydraulic, pneumatic, electrical or manual - and the requirement that a manual release always exist and always work; the flow the valve must pass once open, since a deluge system demands the full design flow immediately rather than the gradual demand of a wet system; the resetting; the alarm the valve must give when it operates; and the durability over long periods held closed, which is the state the valve is in for its whole life. The associated trim, the priming arrangements and the drain are treated as part of the product, because a deluge valve is only as reliable as the small pipework hung on it. Issued on 7 June 2018 and in force since 1 January 2019, it replaces GB 5135.5-2003.

Document preview — GB 5135.5-2018

National Standard of the People's Republic of China

ICS
13.220.10
Classification
C 84
Replacing
GB 5135.5-2003

Issued by: General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC

Contents

  • 1 Scope1
  • 2 Normative references1
  • 3 Terms and Definitions1
  • 4 Classification and code2
  • 5 Model2
  • 6 Requirements3
  • 6.1 Appearance, logo3
  • 6.2 Specifications3
  • 6.3 rated working pressure3
  • 6.4 Material corrosion resistance3
  • 6.5 Body and bonnet3
  • 6.6 Parts3
  • 6.7 Clearance (applicable to pusher type rain alarm valve)4
  • 6.8 Connection method4
  • 6.9 Rigid non-metallic parts4
  • 6.10 Rubber seals4
  • 6.11 Solenoid valve5
  • 6.12 Body strength5
  • 6.13 Leakage and deformation5
  • 6.14 Hydraulic friction5
  • 6.15 Function5
  • 6.16 Anti-reset (except for temperature-sensitive deluge valves)6
  • 6.17 Fire resistance6
  • 7 Test method6
  • 7.1 Appearance inspection6
  • 7.2 Working cycle test6
  • 7.3 Air aging test for rigid non-metallic parts7
  • 7.4 Warm water aging test for rigid non-metallic parts7
  • 7.5 Rubber seal test7
  • 7.6 Solenoid valve test7
  • 7.7 Valve body strength test7
  • 7.8 Leakage and deformation test8
  • 7.9 Hydraulic friction test8
  • 7.10 Functional Test8
  • 7.11 Anti-reset test9
  • 7.12 Fire Test10
  • 8 Inspection rules11
  • 8.1 Inspection classification11
  • 8.2 Group Batch11
  • 8.3 Sampling11
  • 8.4 Inspection procedures11
  • 8.5 Test result determination 12 9 logo, instruction manual13
  • 9.1 Mark13
  • 9.2 User Manual14
  • 14 Appendix A (Normative Appendix) Hydraulic Friction Test Method15

Foreword

Chapters 6 and 8 of this section are mandatory and the rest are recommended. GB 5135 "Automatic Sprinkler System" is divided into the following sections.

--- Part 1. Sprinklers;

--- Part 2. Wet alarm valve, retarder, hydraulic alarm bell;

---Part 3. Water spray nozzles;

---Part 4. Dry alarm valve;

---Part 5. Rain alarm valve;

--- Part 6. General purpose valves;

--- Part 7. Water flow indicator;

--- Part 8. Accelerator;

---Part 9. Early suppression fast response (ESFR) nozzles;

---Part 10. Pressure switch;

--- Part 11. Grooved pipe joints;

--- Part 12. Expanding the coverage area sprinklers;

---Part 13. Water curtain nozzles;

1 Scope

Part 5 of China's mandatory series on automatic sprinkler systems, covering the deluge alarm valve - the valve that holds water out of a deluge or pre-action system and opens on command to admit it to every open head at once. It is the component on which those systems entirely depend: in a deluge system the heads are open and nothing but this valve stands between the water and the protected space, so a valve that leaks floods a room that is not on fire and a valve that fails to open leaves the system inert. This part specifies the terms and definitions, the classification and code, the model designation, the requirements, the test methods, the inspection rules, the marking and instructions, and the packaging, transport and storage of deluge alarm valves. The requirements cover the strength and tightness of the valve body under system pressure held indefinitely; the opening on command, with the response time and the reliability of the release, whether the trip is hydraulic, pneumatic, electrical or manual - and the requirement that a manual release always exist and always work; the flow the valve must pass once open, since a deluge system demands the full design flow immediately rather than the gradual demand of a wet system; the resetting; the alarm the valve must give when it operates; and the durability over long periods held closed, which is the state the valve is in for its whole life. The associated trim, the priming arrangements and the drain are treated as part of the product, because a deluge valve is only as reliable as the small pipework hung on it. Issued on 7 June 2018 and in force since 1 January 2019, it replaces GB 5135.5-2003.

This part of GB 5135 specifies the terms and definitions, classification and code, model, requirements, test methods, inspection rules, Logo, instruction manual and packaging, transportation and storage. This section applies to the rain alarm valve used in the sprinkler system.

2 Normative references

The following documents are indispensable for the application of this document. For dated references, only dated versions apply to this article. Pieces. For undated references, the latest edition (including all amendments) applies to this document.

GB/T 3287 malleable cast iron pipe joint

GB 5135.1 Automatic sprinkler systems - Part 1. Sprinklers

GB 5135.6 Automatic sprinkler systems - Part 6. General purpose valves

GB 5135.11 Automatic sprinkler systems - Part 11. Grooved fittings

GB/T 9112 Steel Pipe Flange Types and Parameters

GB/T 9969 General guidelines for the use of industrial products

GB/T 17241.6 integral cast iron flange

GB/T 21873-2008 Specification for interface seals for rubber seals, drains and sewers

3 Terms and definitions

The following terms and definitions apply to this document.

3.1 Opened by electric, mechanical, pneumatic or other means, so that water can automatically flow into the water spray system in one direction and simultaneously alarm Kind of control valve.

3.2 The valve assembly of the rain alarm valve installed in the pipeline system is in the closed position, and the water supply side of the valve is filled with pressure-stabilized water, without water The state that flows out from the side of the rain alarm valve system.

3.3 A locking mechanism that prevents the flap assembly from returning to its closed position after actuation.

3.4 The operating point of the rain alarm valve to allow water to enter the sprinkler system is indicated by the system side, the water supply side or the auxiliary pressure. 3.5

3.6 The alarm valve is automatically opened.

3.7 Dynamic, pneumatic or mechanical starting methods allow the piston chamber or diaphragm cavity to be depressurized.

3.8 The valve is opened by the electric, pneumatic or mechanical starting method to make the water supply side pressure water enter the piston cavity or the diaphragm cavity through the pressure bearing area difference. carry out. 3.9 3.10

3.11 A portion of the valve separates the surface of the air and/or water seal assembly. When the valve is in the servo state, the chamber pressure is normal atmospheric pressure.

4 Classification and code

4.1 Rain alarm valve can be divided into.

a) Pusher type, codenamed "G";

b) diaphragm type, codenamed "M";

c) Piston type, codenamed "S";

d) butterfly valve type, codenamed "D";

e) Warm type, codenamed "W".

4.2 Rain alarm valve can be divided into. according to the starting mode.

a) Pressurized, codenamed "J";

b) Decompression type, code omitted.

5 Models

The model of the rain alarm valve is in turn the product code, structure form code, nominal diameter, rated working pressure, start mode code and type. The feature code is composed of parts such as the following. ZSF Automatic sprinkler system rain shower alarm valve Structural form code, see 4.1 Nominal diameter in millimeters (mm) Rated working pressure in MPa (MPa) Startup mode code, see 4.2 Type feature code (enterprise custom, can be omitted) Example 1. ZSFG100-1.2C1 means C1 type, decompression start, rated working pressure 1.2MPa, nominal diameter 100mm, push rod type rain shower alarm valve. Example 2. ZSFS150-1.6JXSW stands for XSW type, pressurized start, rated working pressure 1.6MPa, nominal diameter 150mm, piston type rain shower alarm valve.

6.1 Appearance, logo

6.1.1 The rain alarm valve should be smooth and smooth, free of processing defects and scratches, uniform coating and beautiful color.

6.1.2 The rain alarm valve shall be provided with a durability sign on the outer surface. The content of the mark shall be clear and in accordance with the provisions of 9.1.

6.2 Specifications Raindrop alarm valve inlet and outlet nominal diameter is 25mm, 32mm, 40mm, 50mm, 65mm, 80mm, 100mm, 125mm, 150mm,.200mm, 250mm, 300mm. The diameter of the seat ring can be smaller than the nominal diameter.

6.3 rated working pressure The rated working pressure of the rain alarm valve should not be lower than 1.2MPa.

6.4 Material corrosion resistance

6.4.1 The valve body and bonnet shall be made of materials with corrosion resistance not lower than that of cast iron. The corrosion resistance of the seat material shall not be lower than that of bronze.

6.4.2 If the seat of the diaphragm type rain shower alarm valve is made of material with lower corrosion resistance than bronze, the surface of the seat should be treated with anti-corrosion treatment, and The test shall be carried out in accordance with the provisions of

7.4 and shall comply with the provisions of

6.15 after the test.

6.4.3 Metal parts requiring rotation or sliding shall be made of corrosion-resistant materials such as bronze, nickel-copper alloy, brass, austenitic stainless steel. If ...

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 19 pages — is available in the English PDF.

Referenced standards

Similar standards

How to Buy GB 5135.5-2018

  1. 1Add to cart. Click the "Buy GB 5135.5-2018" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.