NB/T 42107-2017High-voltage direct current circuit-breaker (English PDF)
高压直流断路器
This is a limited preview
Buy now to download the full PDF (30 pages)
Need quotation for your management?
Get a formal quotation for NB/T 42107-2017 in 30 minutes.
Issued by
NEA
Level / Type
Industry · Recommended
Issue date
August 2, 2017
Implementation date
December 1, 2017
Scope
NB/T 42107-2017 is the English-translated version of 高压直流断路器.
NB/T 42107-2017 is the Chinese energy industry product standard for high-voltage DC circuit-breakers used in power systems of DC 6 kV and above.
It is written mainly for mechanical breakers, while power electronic and hybrid designs may also refer to it, and it extends to operating mechanisms and auxiliary equipment such as arresters, capacitors and reactors.
The standard defines normal and special service conditions and ratings including rated DC voltage, rated and short-circuit current, interrupting current, insulation level, power consumption and energy absorption.
Type tests cover insulation, main circuit resistance, temperature rise, EMC, mechanical operation, terminal static load, breaking of DC short-circuit current and seismic performance, followed by factory, special and field tests and rules for transport, installation, operation and maintenance. Issued on 2 August 2017, it has applied since 1 December 2017.
Found what you need?
Document preview — NB/T 42107-2017
National Standard of the People's Republic of China
Issued by: National Energy Administration of the People's Republic of China
Contents
- Foreword4
- Introduction5
- 1 Scope6
- 2 Normative references6
- 3 Terms and definitions7
- 4 Normal and special use conditions11
- 5 Rated value11
- 5.1 Rated DC voltage11
- 5.2 Rated current12
- 5.3 Rated short-circuit current12
- 5.4 Rated interrupting current12
- 5.5 Maximum continuous operating current12
- 5.6 Insulation level12
- 5.7 Number of mechanical operations13
- 5.8 Number of breakings of rated interrupting current13
- 5.9 Rated power consumption13
- 5.10 Rated energy absorption13
- 5.11 Rated auxiliary and control circuit power supply voltage14
- 6 Structure and performance requirements14
- 6.1 Overview14
- 6.2 General requirements14
- 6.3 Terminal mechanical load14
- 6.4 Creepage distance15
- 6.5 Auxiliary and control equipment15
- 6.6 Power operation15
- 6.7 Degree of protection of enclosure15
- 6.8 Nameplate15
- 6.9 Electromagnetic compatibility (EMC)16
- 7 Type test16
- 7.1 General16
- 7.2 Insulation test16
- 7.3 Measurement of main circuit resistance16
- 7.4 Temperature rise test16
- 7.5 Verification of degree of protection17
- 7.6 Sealing test17
- 7.7 Electromagnetic compatibility test (EMC)17
- 7.8 Mechanical operation test at ambient air temperature17
- 7.9 Terminal static load test17
- 7.10 Breaking test of DC circuit-breaker17
- 7.11 Seismic test19
- 8 Exit-factory test19
- 8.1 Overview19
- 8.2 Exit-factory test of the whole machine (when applicable)19
- 8.3 Measurement of main circuit resistance19
- 8.4 Design and appearance inspection19
- 9 Special test20
- 10 Field test20
- 11 Rules for transportation, storage, installation, operation, maintenance20
- 11.1 Overview20
- 11.2 Conditions for transportation, storage, installation20
- 11.3 Installation20
- 11.4 Operation20
- 11.5 Maintenance21
- 12 Safety22
- 13 Impact of the product on environment22
- Appendix A (Informative) Guidelines for the selection of DC circuit-breakers23
- Appendix B (Informative) Overload current of DC transmission system25
- Appendix C (Informative) DC circuit-breaker test circuit and test current waveform26
- References30
1 Scope
This standard applies to high-voltage DC circuit-breakers (hereinafter referred to as DC circuit-breakers) for DC 6 kV and above power systems. This standard is mainly for mechanical DC circuit-breakers. Power electronic and hybrid DC circuit-breakers can also refer to this standard.
This standard specifies the operating environment conditions, terms and definitions, ratings, technical requirements, type tests, exit-factory tests, special tests, field tests, etc. of DC circuit-breakers.
This standard also applies to the operating mechanism of DC circuit-breakers and their auxiliary equipment.
Note: This standard covers lightning arresters, capacitors, reactors and other devices used in DC circuit-breakers.
2 Normative references
The following documents are essential to the application of this document. For the dated documents, only the versions with the dates indicated are applicable to this document; for the undated documents, only the latest version (including all the amendments) is applicable to this standard.
GB/T 1094.6-2011 Power transformers - Part 6: Reactors
GB 1984-2014 High-voltage alternating-current circuit-breakers
GB/T 2900.20-2016 Electrotechnical terminology - High-voltage switchgear and controlgear
GB/T 11022-2011 Common specifications for high-voltage switchgear and controlgear standards
GB/T 13498-2017 Terminology for high-voltage direct current (HVDC) transmission
GB/T 13540 Seismic qualification for high voltage switchgear and controlgear
Note: Where there are special requirements for DC voltage, it shall be determined by negotiation between the supplier and the buyer.
5 Rated value
5.2 Rated current
It shall comply with the provisions of 4.5.1 of GB/T 11022-2011.
5.3 Rated short-circuit current
The DC current expected to be interrupted by the DC circuit-breaker is selected from the following values (kA). 2, 5, 8, 10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80, 100, 125.
Note: Where there are special requirements for current, it shall be determined by negotiation between the supplier and the buyer.
5.4 Rated interrupting current
The DC current interrupted by the DC circuit-breaker is selected from the following values (kA). 4, 5, 6.3, 8, 10, 12.5, 16, 20, 25, 31.5.
Note: Where there are special requirements for the current, it shall be determined by negotiation between the supplier and the buyer.
5.5 Maximum continuous operating current
The maximum continuous operating current is generally 1.05 ~ 1.25 times the rated current.
5.6 Insulation level
The rated insulation level of the DC circuit-breaker shall be selected from the values given in Table 1.
5.11 Rated auxiliary and control circuit power supply voltage
Complies with the provisions of 4.9 of GB/T 11022-2011.
6 Structure and performance requirements
6.1 Overview
In DC systems, DC circuit-breakers often use several parallel branches to complete the breaking task. Generally, DC circuit-breakers are composed of three parts.
a) Low-resistance on-state current conducting branch;
b) High-resistance current limiting and commutation branch during the breaking process;
c) Energy absorption branch.
For the mechanical, power electronic, hybrid DC circuit-breakers described in this standard, each has different topological structures and different technical characteristics.
The general topological structures of these three DC circuit-breakers are described in Appendix A.
6.2 General requirements
DC circuit-breakers shall be equipped with open and closed status indicators; their installation locations shall be clearly visible and reliable.
All components of DC circuit-breakers shall be corrosion-resistant or undergo corrosion-resistant treatment.
6.3 Terminal mechanical load
The mechanical load of the wiring terminals in DC circuit-breakers shall not be less than.
- Horizontal longitudinal. 2000 N;
- Horizontal transverse. 1500 N;
- Vertical. 1500 N.
Note 1. See 6.2.3 of GB/T 25309-2010.
Note 2. The wiring load under different voltage levels shall meet the requirements of actual working conditions.
6.4 Creepage distance
It shall be in accordance with actual engineering requirements.
6.5 Auxiliary and control equipment
Comply with the provisions of 5.4 of GB/T 11022-2011 and make the following supplement. For DC circuit-breakers using forced air cooling or water cooling, the relevant requirements of control equipment shall be considered.
6.6 Power operation
Comply with the provisions of 5.5 of GB/T 11022-2011.
6.7 Degree of protection of enclosure
Comply with the provisions of 5.13 of GB/T 11022-2011 and make the following supplement. The degree of protection of enclosure shall not be less than IP23.
6.8 Nameplate
The technical parameters on the nameplate shall at least include the following parameters.
- Rated DC voltage;
- Rated current;
- Rated power consumption.
- Rated short-circuit current (optional);
- Maximum continuous operating current;
- Rated lightning impulse withstand voltage;
- Rated DC withstand voltage;
- Rated interruption current;
7 Type test
7.5 Verification of degree of protection
Conform to the provisions of 6.7 of GB/T 11022-2011.
7.6 Sealing test
Conform to the provisions of 6.8 of GB/T 11022-2011 (when applicable).
7.7 Electromagnetic compatibility test (EMC)
Conform to the provisions of 6.9 of GB/T 11022-2011.
7.8 Mechanical operation test at ambient air temperature
Conform to the provisions of 6.101.2 of GB 1984-2014 and make the following supplement. Only mechanical operation test is carried out on mechanical disconnecting device.
7.9 Terminal static load test
The terminal force shall meet the requirements of 6.3. The test shall be carried out in accordance with the requirements of 6.101.6 of GB 1984-2014.
7.10 Breaking test of DC circuit-breaker
7.10.1 Overview
The purpose of this test is to verify whether the DC circuit-breaker has the ability to break the specified DC short-circuit current.
This test verifies that the DC circuit-breaker can successfully interrupt the DC current within the rated short-circuit current range, and that the interrupter can withstand the recovery voltage between the breaks. According to the actual project requirements, the test circuit shall be equivalent to the actual operating conditions of this type of DC circuit-breaker. The interruption test shall at least include the following requirements.
a) Recommended tests for products above 10 kV, see Table 2;
9 Special test
Performed in accordance with the agreement between the manufacturer and the user.
10 Field test
The purpose of the field test is to check whether the DC circuit-breaker and its auxiliary equipment are not damaged due to transportation and storage, and to verify the overall performance of the assembled DC circuit-breaker.
The field test includes the inspection and testing of the DC circuit-breaker components and the DC circuit-breaker as a whole. Each component is implemented in accordance with its own standards.
The test methods and requirements are negotiated by the supplier and the buyer.
11 Rules for transportation, storage, installation, operation, maintenance
11.1 Overview
Comply with the provisions of Chapter 10 of GB/T 11022-2011.
11.2 Conditions for transportation, storage, installation
Comply with the provisions of 10.1 of GB/T 11022-2011.
11.3 Installation
Comply with the provisions of 10.2.1 ~ 10.2.4 of GB/T 11022-2011.
11.4 Operation
The instructions provided by the manufacturer shall include the following information.
- General description of the equipment, with particular attention to its characteristics and technical description of operation, so that the user fully understands the main principles involved;
- Description of the safety performance of the equipment;
- Description of the actions taken to operate, isolate, ground, maintain, test the equipment related to operation.
11.5 Maintenance
11.5.1 Overview
The effectiveness of maintenance depends mainly on the content of the instructions written by the manufacturer and the extent to which the user implements the instructions.
11.5.2 Recommendations for manufacturers
The manufacturer shall provide a maintenance manual that includes the following information.
- Scope and frequency of maintenance.
- Detailed description of maintenance work;
- A complete set of drawings of switchgear and controlgear details that are critical to maintenance, with clear markings of general assembly, subassembly, important parts on the drawings;
- Limit values and allowable deviations; if there are deviations, make necessary corrections;
- Specifications of auxiliary maintenance materials, including warnings for known incompatible materials;
- List of special tools, lifting and maintenance equipment.
- Test items after maintenance;
- Recommended spare parts (description, code, quantity) and storage recommendations;
- Estimates of effective planned maintenance time;
- At the end of the operating life of the equipment, how to deal with the equipment, including environmental requirements.
11.5.3 Recommendations for users
If the user wishes to perform maintenance by himself, his staff shall have a detailed understanding of the corresponding switchgear and controlgear.
Appendix A (Informative) Guidelines for the selection of DC circuit-breakers
A.1 Overview
This Appendix applies to DC circuit-breakers for DC transmission with voltage levels of 6 kV and above. The recommended values of the rated parameters of DC circuit-breakers are as shown in Chapter 5 of this standard.
In order to make the DC circuit-breaker suitable for the specified operating task, it shall be selected according to the various rated values required by the load conditions and fault conditions.
A.2 Selection of DC circuit-breaker ratings
A.2.1 Selection of rated DC voltage
The rated DC voltage of the DC circuit-breaker can be selected from 5.1.
A.2.2 Selection of rated current
The rated operating current of the DC circuit-breaker is determined by the rated current of the DC project.
The rated current of the DC circuit-breaker can be selected from 5.2.
A.3 Selection of DC circuit-breaker type
The typical schemes of DC circuit-breakers are. mechanical, power electronic, hybrid.
a) Mechanical DC circuit-breakers are generally composed of breaking device (CB), commutation capacitor (C), commutation reactor (L), commutation switch (G), lightning arrester (MOV), as shown in the dotted box in Figure A.1;
b) Power electronic DC circuit-breakers are generally composed of power electronic components (S) and lightning arrester (MOV), as shown in the dotted box in Figure A.2;
c) Hybrid DC circuit-breakers are generally composed of fast mechanical disconnector (FD), auxiliary DC switch (FS), main DC switch (MS), lightning arrester (MOV), among which the main DC switch and auxiliary DC switch are both power electronic components. As shown in the dotted box in Figure A.3.
DB1 and DB2 in Figures A.1, A.2, A.3 are auxiliary isolation devices used to interrupt residual current. […]
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 30 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 1094.6-2011Power transformers -- Part 6: Reactors
- GB 1984-2014High-voltage alternating-current circuit-breakers
- GB/T 2900.20-2016Electrotechnical terminology -- High-voltage switchgear and controlgear
- GB/T 11022-2011Common specifications for high-voltage alternating-current switchgear and controlgear standards
- GB/T 13498-2017Terminology for high-voltage direct current (HVDC) transmission
- GB/T 13540Seismic qualification for high voltage switchgear and controlgear
Similar standards
How to Download NB/T 42107-2017
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 1984-2014 — High-voltage alternating-current circuit-breakers
GB/T 1094.6-2011 — Power transformers -- Part 6: Reactors
GB/T 11022-2011 — Common specifications for high-voltage switchgear and controlgear standards
Secure payment via Stripe
Payments accepted
NB/T 42107-2017
$285.00