Issued by
The General Administration of Quality Supervision, Inspection and Quarantine (AQSIQ) of The People's Republic
Level / Type
National · Mandatory
Issue date
December 3, 2012
Implementation date
March 3, 2013
Scope
JJF 1368-2012 (Program of Pattern Evaluation of Combustible - Gas Alarm Detectors) is available as an English-translated PDF.
JJF 1368-2012 is the Chinese standard "Program of Pattern Evaluation of Combustible - Gas Alarm Detectors". Its scope clause reads: This program of pattern evaluation applies to the combustible-gas alarm detectors (including combustible gas detector, hereinafter referred to as "detector") used in non-shaft operating environment and civil place.
Its clauses include general; technical data and experimental prototype submitted by; legal management requirements; measuring requirements; general technical requirements; lists of pattern evaluation items; test methods and condition for test items.
It was issued by the The General Administration of Quality Supervision, Inspection and Quarantine (AQSIQ) of The People's Republic on 2012-12-03 and took effect on 2013-03-03.
Found what you need?
Document preview — JJF 1368-2012
National Standard of the People's Republic of China
Issued by: The General Administration of Quality Supervision, Inspection and Quarantine (AQSIQ) of The People's Republic
Contents
- Introduction...4
- 1 Scope...5
- 2 Normative References...5
- 3 General...5
- 4 Technical Data and Experimental Prototype Submitted by Application Organization...6
- 4.1 Technical Data...6
- 4.2 Experimental Prototype...6
- 5 Legal Management Requirements...6
- 5.1 Requirements for Measurement Unit...6
- 5.2 Requirements for Accuracy (Maximum Permissible Error)...6
1 Scope
This program of pattern evaluation applies to the combustible-gas alarm detectors (including combustible gas detector, hereinafter referred to as "detector") used in non-shaft operating environment and civil place.
2 Normative References
JJG 693-2011 “Alarm Detectors of Combustible Gas"
GB 12358-2006 “Gas Monitors and Alarms for Workplace-General Technical
Requirements"
GB 15322-2003 “Combustible Gas Detector"
GB 16808-2008 “Combustible Gas Alarm Control Units"
GB/T 17626.2-2006 “Electromagnetic Compatibility (EMC) -- Testing and
Measurement Techniques -- Electrostatic Discharge Immunity Test"
GB/T 17626.3-2006 “Electromagnetic Compatibility-Testing and Measurement
Techniques-Radiated Radio-frequency Electromagnetic Field Immunity Test"
3 General
The detector is divided into catalytic combustion type, thermal conductivity type, semiconductor type and infrared absorption type - according to the test principle; divided into diffusion type and inhalation type - according to sampling type; divided into portable type and fixed type - according to usage mode. The detector mainly consists of detecting element, amplifying circuit, alarm system and displayer. It is used to monitor the concentration of combustible gas exist in the environment.
4 Technical Data and Experimental Prototype Submitted by
Application Organization
4.1 Technical Data
4.2 Experimental Prototype
The application organization shall provide the prototypes it produced and file an application for a single product or series products. In case of application for a single product, three prototypes shall be provided for non-fixed-type equipment; six prototypes, of which three prototypes shall be used for the long-term stability test, shall be provided for fixed-type equipment.
5 Legal Management Requirements
5.1 Requirements for Measurement Unit
The detector shall adopt the legal measurement units.
5.2 Requirements for Accuracy (Maximum Permissible Error)
The maximum permissible error of the detector shall comply with JJG 693-2011 "Alarm
Detectors of Combustible Gas".
5.3 Requirements for Legal Measurement Marking and Measuring Devices
Identification
The legal measurement marking and measuring device identification shall be indicated on the detector and easily seen - such as nameplate, panel and gauge-head and the marking.
Serial number and description must be distinguishable and firmly reliable.
5.4 Requirements for Installation Marking
The detector, whose accuracy will be affected by the improper installation, shall be provided with the installation instructions marking.
6 Measuring Requirements
The measuring requirements are detailed in Table 1.
7 General Technical Requirements
7.1 Appearance
7.2 Alarm Function and Alarm Operate Value
When the indication on the detector reaches the alarm set value, the detector shall produce sound and light alarm. When the detector produces the alarm signal, the detector with output control function shall start the output control function. When it is in under-voltage state, the battery-powered detector shall produce the sound or light index signal obviously which must be different from the alarm signal.
7.4 Adaptability of Supply Voltage
7.4.1 With the supply voltage being ±15% of the rated supply voltage, the indicated error on the AC powered detector shall be in accordance with those specified in Table 1.
7.5 Requirements for Secure Environment
7.5.1 Insulation resistance (not applicable to the battery-powered detector)
At the normal test conditions, the insulation resistance of the detector shall not be less than 100 Mohm; after the damp heat test, the insulation resistance of the detector shall not be less than 1Mohm.
7.6 Requirements for Climatic Environment
7.6.1 High-temperature test
With the detector being in the normal monitoring state (the test temperature of 55 °C or
70 for outdoor use)°C, the test shall last 2h.
7.6.3 Constant damp heat test
With the detector being in the normal monitoring state (40, 93%), the test °C shall last continuous 2h. During the test, the detector shall be able to work normally. Upon the test duration is reached, the indicated error shall not exceed ±10%FS. After the test, the detector shall be free from coating damage or corrosion.
7.7 Requirements for Mechanical Environment
7.8 Requirements for Electromagnetic Compatibility
7.8.1 Radio-frequency electromagnetic field radiation immunity test
Field strength. 10V/m; frequency range. 80MHz~1000MHz. During the test, the detector shall be able to work normally; after the test, the indicated error shall be in accordance with those specified in Table 1.
7.8.2 Electrostatic discharge immunity test
Discharge voltage. 8kV; discharge times. 10.During the test, the detector shall be able to work normally; after the test, the indicated error shall be in accordance with those specified in
Table 1.
8 Lists of Pattern Evaluation Items
The pattern evaluation items of the detector are detailed in Table 3.
9 Test Methods and Condition for Test Items
9.1 Measuring Requirements
9.1.1 Indicated error
9.1.1.1 Test purposes
To test whether the indicated error of the detector complies with Table 1 under the test conditions.
9.1.1.5 Data processing
The indicated error at all points deltac is calculated according to Formula (1) and the maximum absolute value of deltac is the indicated error.
9.1.2 Repeatability
9.1.2.1 Test purposes
To test whether the repeatability of the detector complies with Table 1 under the test conditions.
9.1.2.2 Test conditions
Same as 9.1.1.2.
9.1.2.3 Test equipment
Same as 9.1.1.3.
9.1.2.4 Test procedure
With stable preheating, provide the gas reference material at a concentration about 40% of full span and record the stable indication ci on the detector, and remove the gas reference material. Conduct six such operations at the identical condition.
9.1.3 Response time
9.1.3.1 Test purposes
To test whether the response time of the detector complies with Table 1 under the test conditions.
9.1.3.2 Test conditions
Same as 9.1.1.2.
9.2.9 Constant damp heat test
9.2.9.1 Test purposes
To test whether the detector operates in accordance with 7.6.3 under the constant damp heat environment.
9.2.9.2 Test conditions
Temperature. 40 ±2°C °C;
Relative humidity. 93%±3%;
Duration. 2h.
9.2.12.3 Test equipment
a) In conformity with the requirements of Chapter 6 in GB/T 17626.3-2006;
b) Same as 9.1.1.3.
9.2.12.4 Test procedure
Make the test according to the requirements of Chapter 8 in GB/T 17626.3-2006.During the test, observe and record operating state of the detector; after the test, make the test according to 9.1.1.4.
9.2.13.6 Qualification criteria
It is qualified if the result is in accordance with those specified in 7.8.2.
9.2.14 Electrical fast transient/burst immunity test (only for AC powered detector)
9.2.14.1 Test purposes
To test whether the electrical fast transient/burst immunity of the detector complies with
7.8.3 under the test conditions.
9.2.14.2 Test conditions
Same as 9.1.1.2.
9.2.14.3 Test equipment
a) In conformity with the requirements of Chapter 6 in GB/T 17626.4-2008.
b) Same as 9.1.1.3.
9.2.14.4 Test procedure
Make the test according to the requirements of Chapter 8 in GB/T 17626.4-2008.During the test, observe and record operating state of the detector; after the test, make the test according to 9.1.1.4.
9.2.14.5 Data processing
Same as 9.1.1.5.
9.2.14.6 Qualification criteria
It is qualified if the result is in accordance with those specified in 7.8.3.
......
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 6 pages — is available in the English PDF.
Referenced standards
Normative references
- GB 12358-2006Gas detection and alarm instruments for workplace - General technical requirements
- GB 16808-2008Combustible gas alarm control units
- GB/T 17626.2-2006Electromagnetic compatibility -- Testing and measurement techniques -- Electrostatic discharge immunity test
- GB/T 17626.3-2006Electromagnetic compatibility - Testing and measurement techniques - Part 3: Radiated, radio-frequency, electromagnetic field immunity test
JJG 693-2011 · GB 15322-2003
How to Download JJF 1368-2012
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards