GB/T 37012-2018Technical specification of earthing equipment for high-voltage direct current(HVDC) transmission using voltage sourced converters(VSC) (English PDF)
柔性直流输电接地设备技术规范
This is a limited preview
Buy now to download the full PDF (23 pages)
Need quotation for your management?
Get a formal quotation for GB/T 37012-2018 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 28, 2018
Implementation date
July 1, 2019
Scope
GB/T 37012-2018 is the English-translated version of 柔性直流输电接地设备技术规范.
GB/T 37012-2018 is the technical specification for the earthing equipment of HVDC transmission systems using voltage sourced converters, for symmetrical monopole modular multilevel systems rated up to ±500 kV DC.
It sets the normal and special conditions of use and then deals with four kinds of equipment: the neutral point earthing resistor of the connecting transformer, the DC side earthing resistor, the earthing device of the star-connected reactor and the earthing transformer.
For each it gives performance requirements, tests and marking, and it closes with packaging, transport and storage. Informative annexes show the wiring of earthing equipment in a symmetrical monopole system and a method for calculating the equivalent energy of a resistor.
It is used with the power transformer and insulation standards it cites. It was issued on 28 December 2018 and has applied since 1 July 2019.
Found what you need?
Document preview — GB/T 37012-2018
National Standard of the People's Republic of China
- ICS
- 29.240.01
- Classification
- F 21
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
- 4 Conditions of use
- 4.1 Normal use conditions
- 4.2 Special Conditions of Use
- 5 Connecting transformer neutral point grounding resistor
- 5.1 Performance Requirements
- 5.2 Test
- 5.3 Mark
- 6 DC side grounding resistor
- 6.1 Performance Requirements
- 6.2 Test
- 6.3 Mark
- 7 Star coupling reactor grounding equipment
- 7.1 Overview
- 7.2 Performance requirements
- 7.3 Test
- 7.4 Mark
- 8 Grounding transformer equipment
- 8.1 Overview
- 8.2 Performance requirements
- 8.3 Test
- 8.4 Mark
- 9 Packaging, transport and storage
- 9.1 Packing
- 9.2 Transportation and storage
- Appendix A (informative) Wiring method for grounding equipment of symmetrical single-pole topology flexible DC transmission system
- Appendix B (informative) Resistor equivalent energy calculation method
- Reference
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
1 Scope
This standard specifies the conditions for the use of flexible DC transmission grounding equipment, the neutral point grounding resistor of the connecting transformer, and the DC side grounding resistance. Performance requirements, test items and signs, packaging, transportation and other types of grounding equipment such as grounding devices for star-connected reactors and grounding transformers Store.
This standard applies to the grounding of symmetrical single-pole modular multi-level topological flexible DC transmission systems with DC voltage ±500kV and below. device.
2 Normative references
The following documents are indispensable for the application of this document. For dated references, only dated versions apply to this document. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 311.1-2012 Insulation coordination Part 1: Definitions, principles and rules
GB/T 1094.1-2013 Power transformers - Part 1: General
GB/T 1094.2-2013 Power transformers - Part 2: Temperature rises of liquid immersed transformers
GB/T 1094.3-2017 Power transformers - Part 3: Insulation level, insulation test and external insulation air gap
GB/T 1094.4-2005 Power transformers - Part 4: Lightning and operational impulse test for power transformers and reactors Guidelines
GB/T 1094.5-2008 Power transformers - Part 5: Ability to withstand shorts
GB/T 1094.6-2011 Power transformers - Part 6: Reactors
GB/T 1094.10-2003 Part 10: Determination of sound level
GB/T 1094.11-2007 Power transformers - Part 11: Dry transformers
GB/T 1094.18-2016 Power transformers - Part 18: Frequency response measurement
GB/T 2423.1-2008 Environmental testing of electric and electronic products - Part 2: Test methods Test A. Low temperature
GB 2536-2011 Unused mineral insulating oil for electrical fluid transformers and switches
GB/T 4109-2008 Insulating bushings with AC voltage higher than 1000V
GB/T 5273 high-voltage electrical terminal size standardization
GB/T 6451 oil-immersed power transformer technical parameters and requirements
GB/T 8287 (all parts) nominal voltage higher than 1000V system internal and outdoor post insulators
GB/T 10228 dry power transformer technical parameters and requirements
GB/T 16927.1-2011 High voltage test techniques - Part 1: General definitions and test requirements
GB/T 20840.1-2010 Transformers - Part 1: General technical requirements
GB/T 20840.3-2013 Part 3: Supplementary technical requirements for electromagnetic voltage transformers
GB/T 26218.1 Selection and sizing of high-voltage insulators for use under filth conditions Part 1: Definitions, information and general in principle
GB/T 30547-2014 High-voltage DC transmission system filter resistor
DL/T 722-2014 Guidelines for analysis and determination of dissolved gases in transformer oil
DL/T 1048 AC bar-strut composite insulator with a nominal voltage higher than 1000V - definition, test method and acceptance rules
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 23 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 1094.1-2013Power transformers-Part 1: General
- GB/T 1094.3-2017Power transformers -- Part 3: Insulation levels, dielectric tests and external clearances in air
- GB/T 1094.4-2005Power transformers -- Part 4: Guide to the lightning impulse and switching impulse testing -- Power transformers and reactors
- GB/T 1094.6-2011Power transformers -- Part 6: Reactors
- GB/T 1094.10-2003Power transformers - Part 10: Determination of sound levels
- GB/T 1094.11-2007Power transformers—Part 11: Dry-type transformers
GB/T 311.1-2012 · GB/T 1094.2-2013 · GB/T 1094.5-2008 · GB/T 8287 · GB/T 20840.3-2013 · DL/T 1048
Similar standards
How to Download GB/T 37012-2018
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
DL/T 722-2014 — Guide to the analysis and the diagnosis of gases dissolved in transformer oil
GB/T 10228-2023 — Technical parameters and requirements for dry-type power transformers
GB/T 1094.1-2013 — Power transformers-Part 1: General
Secure payment via Stripe