GB/T 27698.2-2023Test methods for the performance of heat exchangers and heat exchange elements - Part 2: Heat exchangers (English PDF)

热交换器及传热元件性能测试方法 第2部分:热交换器

Preview PDF

This is a limited preview

Buy now to download the full PDF (19 pages)

Need quotation for your management?

Get a formal quotation for GB/T 27698.2-2023 in 30 minutes.

Issued by

State Administration for Market Regulation; Standardization Administration of China

Level / Type

National · Recommended

Issue date

August 6, 2023

Implementation date

August 6, 2023

Scope

GB/T 27698.2-2023 is the English-translated version of 热交换器及传热元件性能测试方法 第2部分:热交换器.

GB/T 27698.2-2023 is Part 2 of GB/T 27698 and describes how the thermal performance of a heat exchanger is measured.

It gives the product model and sample parameters to be declared, the test procedures, the processing of test data, the error and uncertainty treatment and the test report requirements, and it applies to tubular heat exchangers including shell-and-tube units, to plate heat exchangers including welded and brazed ones, and to spiral plate units.

Five tests are defined: liquid-liquid turbulent and low-flow-rate tests without phase change, vapour-liquid condensation, flow boiling and evaporation, and pool boiling.

Results are reported as curves of total heat transfer coefficient and pressure drop against flow rate, with Nusselt, Reynolds, Prandtl and Euler number relations.

It replaces GB/T 27698.2-2011, GB/T 27698.3-2011 and GB/T 27698.4-2011, was issued on 6 August 2023 and has applied since 6 August 2023.

Found what you need?

Document preview — GB/T 27698.2-2023

National Standard of the People's Republic of China

ICS
27.060.30
Classification
J 75
Replacing
GB/T 27698.2-2011

Issued by: State Administration for Market Regulation; Standardization Administration of China

Contents

  • Foreword3
  • Introduction6
  • 1 Scope7
  • 2 Normative references7
  • 3 Terms and definitions7
  • 4 Product model and sample parameters8
  • 4.1 Tubular heat exchangers8
  • 4.2 Plate heat exchangers9
  • 4.3 Spiral plate heat exchangers9
  • 5 Test procedure10
  • 5.1 Liquid-liquid turbulence performance test without phase change10
  • 5.2 Liquid-liquid low-flow rate performance test without phase change11
  • 5.3 Vapor-liquid condensation performance test12
  • 5.4 Vapor-liquid flow boiling and evaporation performance test12
  • 5.5 Pool boiling heat transfer performance test13
  • 6 Test data processing14
  • 6.1 Liquid-liquid performance test without phase change14
  • 6.2 Vapor-liquid condensation performance test14
  • 6.3 Vapor-liquid flow boiling and evaporation performance test15
  • 6.4 Pool boiling heat transfer performance test15
  • 7 Error and uncertainty15
  • 8 Test report16

1 Scope

This document describes the performance test procedures, test data processing and test report requirements for heat exchangers.

This document applies to the performance test of tubular heat exchangers (including shell and tube heat exchangers), plate heat exchangers (including welded plate heat exchangers and brazed plate heat exchangers), and spiral plate heat exchangers.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

GB/T 151, Heat exchanger

GB/T 27698.1, Test methods for the performance of heat exchangers and heat exchange elements - Part 1: General requirements

NB/T 47004.1, Plate heat exchangers - Part 1: Plate-and-frame heat exchangers

NB/T 47004.2, Plate heat exchangers - Part 2: Welded plate heat exchangers

NB/T 47045, Brazed plate heat exchangers

NB/T 47048, Spiral plate heat exchanger

3 Terms and definitions

For the purpose of this document, the following terms and definitions, as well as those given in GB/T 27698.1, apply.

3.1 Standard condition

The operating condition set to characterize the performance of the heat exchanger.

4 Product model and sample parameters

4.2 Plate heat exchangers

4.2.1 The number of plates in the plate heat exchanger sample shall be determined by considering the uniformity of fluid distribution within the measured flow rate range, and the number of plates installed shall not be less than 9.

4.2.2 When testing plate heat exchangers, the product model and the following parameters shall be clearly stated:

a) Plate corrugation form (corrugation angle, corrugation depth, corrugation spacing, mixing angle);

b) Plate geometric dimensions (length, width, corner hole diameter, longitudinal and transverse center distance);

c) Heat transfer area of a single plate;

d) Spacing between plates;

e) Flow channel cross-sectional area;

f) Plate thickness;

g) Plate material;

h) Number of plates;

i) Clamping dimensions;

j) Process combination;

k) Design temperature;

l) Design pressure.

The above structure and design data shall be determined in accordance with the requirements of GB/T 27698.1 and NB/T 47004.1, NB/T 47004.2 as well as NB/T 47045.

4.2.3 When the product model or any of the parameters a) ~ e) in 4.2.2 changes, the performance test shall be repeated.

4.3 Spiral plate heat exchangers

4.3.1 When testing spiral plate heat exchanger, the product model and the following parameters shall be clearly stated:

a) Layout and geometric dimensions of spacing columns;

b) Spacing between plates;

c) Equivalent diameter;

d) Flow cross-sectional area;

e) Flow channel length;

f) Heat transfer plate material;

g) Heat transfer plate thickness;

h) Heat transfer area (based on the neutral surface of the heat transfer plate);

i) Design temperature;

j) Design pressure.

The above structure and design data shall be determined in accordance with the requirements of GB/T 27698.1 and NB/T 47048.

4.3.2 When the product model or any of the parameters a) ~ d) in 4.3.1 changes, the performance test shall be repeated.

5 Test procedure

5.1 Liquid-liquid turbulence performance test without phase change

5.1.1 Before testing, the reliability of the test sample, pipeline and measuring instruments shall be checked.

5.1.2 After starting operation, the gas in the test sample shall be exhausted in time, so that the test sample can be operated under the condition of being fully filled with test fluid and adjusted to the standard condition according to Table 1.

5.1.3 After running stably for 30 minutes under standard conditions, the following test requirements should be followed:

a) The fluid flow rate on both sides remains the same, the flow rate changes within the range of Table 1, and the change interval meets the requirements of Table 1;

b) The fluid on one side (hot side or cold side) is fixed at the flow rate under standard conditions; the flow rate of the fluid on the other side varies within the range of Table 1, and the variation interval meets the requirements of Table 1;

5.4 Vapor-liquid flow boiling and evaporation performance test

5.4.2 After starting operation, the non-condensable gas in the test sample shall be discharged in time and adjusted to the standard condition.

5.4.3 After running stably for 30 minutes under standard condition, the following test requirements should be followed:

a) Keep the steam temperature entering the pre-heater and the test sample inlet at 1 °C ~ 3 °C superheat, and the condensate temperature slightly lower than the saturation temperature corresponding to the outlet steam pressure, but within the range of 2 °C; obtain the steam flow rate by measuring the condensate;

b) The flow rate of the cold fluid varies within the range of Table 1, and the variation interval meets the requirements of Table 1;

c) The inlet dryness of the cold fluid of the test sample is adjusted by the pre-heater, and the minimum inlet dryness is 0;

d) The average dryness of the cold fluid of the test sample changes according to the use range, and the change interval increases with the increase of dryness;

e) When each test condition is stable for more than 5 minutes, carry out data collection simultaneously. During the condensate metering process, the condition remains relatively stable;

f) Repeat the measurement at each test point at least 3 times, with an interval of more than 5 minutes between each measurement; take the average value of the measurement results.

5.4.4 The test conditions can be determined through negotiation based on user requirements and equipment characteristics.

5.5 Pool boiling heat transfer performance test

5.5.1 Before testing, the reliability of the test sample, pipeline and measuring instruments shall be checked.

5.5.2 After running stably for 30 minutes, the test should be carried out according to the following test requirements:

a) Ensure that the liquid level of the cold fluid is higher than that of the test sample;

b) When each test condition is stable for more than 5 minutes and the relative error of thermal balance is no more than 5%, carry out data collection synchronously; the condition remains relatively stable during the condensate metering process;

c) Change the heat load at least 5 times during the test; collect at least 3 sets of data simultaneously at each test point.

5.5.3 The test conditions can be determined through negotiation based on user requirements and equipment characteristics.

6 Test data processing

6.1 Liquid-liquid performance test without phase change

6.1.1 Give the test curve of total heat transfer coefficient (k) and flow rate (u).

6.1.2 Summarize the criterion relation between the Nusselt number (Nu) and the Reynolds number (Re) as well as the Prandtl number (Pr).

6.1.3 In the same coordinate system, calculate the relationship curve between the total heat transfer coefficient (k) and the flow rate (u) when the reference temperatures of the cold/hot fluids are 20 °C/40 °C, 30 °C/50 °C, and 40 °C/60 °C respectively.

6.1.4 Provide the test curve of pressure drop (deltap) and flow rate (u).

6.1.5 Summarize the criterion relation between the Euler number (Eu) and the Reynolds number (Re).

6.1.6 In the same coordinate system, calculate the relationship curve between the pressure drop (deltap) and the flow rate (u) of the cold fluid when the reference temperatures are 20 °C, 30 °C and 40 °C, respectively.

6.1.7 In the same coordinate system, calculate the relationship curve between the pressure drop (deltap) and flow rate (u) of the hot fluid when the reference temperatures are 40 °C, 50 °C, and 60 °C, respectively.

6.1.8 Give the values of the total heat transfer coefficient (k) and pressure drop (deltap) at the flow rate under standard condition when the hot fluid reference temperature is 50 °C and the cold fluid reference temperature is 30 °C.

6.2 Vapor-liquid condensation performance test

6.2.1 Provide the test curve of the total heat transfer coefficient (k) and the liquid side flow rate (u) or Reynolds number (Re).

6.2.2 Summarize the relationship between the condensation convection heat transfer coefficient (alpha) and the flow rate (u) or the Reynolds number (Re).

6.2.3 Provide the test curve of the pressure drop (deltap) on both sides and the flow rate (u) or the Reynolds number (Re). […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 19 pages — is available in the English PDF.

Referenced standards

Similar standards

Editions of GB/T 27698.2

EditionTitleRevisionStatus
GB/T 27698.2-2023Test methods for the performance of heat exchangers and heat exchange elements - Part 2: Heat exchangersfirst revisionCurrent
GB/T 27698.2-2011Test method for the performance of heat exchangers and heat exchange elements - Part 2: Heat exchangersfirst issueSuperseded

This page sells the current edition, GB/T 27698.2-2023. Earlier editions are listed for reference only.

How to Download GB/T 27698.2-2023

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
19 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 27698.2-2023

$210.00