NB/T 11077-2023Technical specifications for high-voltage alternating-current fault current limiter based on current-limiting reactor (English PDF)
基于限流电抗器的高压交流故障电流限制器技术规范
Open the NB/T 11077-2023 preview as PDF
This is a limited preview
Buy now to download the full PDF (38 pages)
Issued by
NEA
Level / Type
Industry · Recommended
Issue date
February 6, 2023
Implementation date
August 6, 2023
Scope
NB/T 11077-2023 is the English-translated version of 基于限流电抗器的高压交流故障电流限制器技术规范.
NB/T 11077-2023 is the Chinese specification for the fault current limiter built from a current-limiting reactor, for AC systems of 3 kV and above at 50 Hz. It exists because of a problem that grows with the grid rather than with age: as more generation and more interconnection are added, the short-circuit current available at any given busbar rises, and eventually it exceeds what the switchgear installed there was rated to break. The conventional answers are all expensive - replace every breaker in the substation, split the busbar and lose the redundancy, or leave a permanent series reactor in circuit and pay for its losses and voltage drop for the life of the plant. The current-limiting reactor type limiter is the fourth answer: a limited purpose circuit breaker sits in parallel with the reactor and short-circuits it, so in normal operation the reactor is bypassed and the limiter is a low-impedance link. When a fault occurs the control device detects it, opens the parallel breaker at the end of the first large half-wave of fault current, and the reactor is inserted, taking the limiter to its high-impedance state and holding the current down to what the downstream switchgear can clear. Everything then hinges on speed, and this document defines it: the quick fault determination requirement is to establish the starting point, the rate of rise and the maximum value of the short-circuit current within 5 ms. The document names and defines the whole vocabulary of the technique - the C mode and CL mode, the C-CL and CL-C transitions, the limited purpose circuit breaker and the control device - and it is explicit about the limitation, that a limiter of this type may not limit the peak of the very first half-wave. It then sets the service conditions, the ratings, and the design and construction requirements including composition, structure, communications, power supply, protection current range, device components, main circuit resistance, temperature rise and the design of the insulating support structure. The type test clause covers insulation, surge current, continuous current, short-time and peak withstand current, the short-circuit current limiting test itself, harmonic distortion, current breaking, recovery, EMC, noise and seismic tests, together with verification of the limited purpose breaker, the circuit resistance measurement and the limiter starting test; routine tests and selection guidelines close the document. It was issued on 6 February 2023 by the National Energy Administration and took effect on 6 August 2023.
Document preview — NB/T 11077-2023
National Standard of the People's Republic of China
- ICS
- 29.130.10
- Classification
- K 43
Issued by: National Energy Administration of the PRC
Contents
- Foreword4
- 1 Scope1
- 2 Normative references1
- 3 Terms and definitions1
- 3.1 General terms and definitions1
- 3.2 Definitions relating to the CLR-FCL2
- 4 Service conditions6
- 5 Ratings7
- 6 Design and construction10
- 6.5 Mechanical load of terminals10
- 6.6 Auxiliary and control equipment10
- 6.7 Power operation10
- 6.8 Stored energy operation10
- 6.9 Cooling equipment10
- 6.10 Nameplate11
- 6.11 Position indication11
- 6.12 Degree of protection provided by the enclosure11
- 6.13 Creepage distance of outdoor insulators11
- 6.14 Gas and vacuum tightness11
- 6.15 Liquid tightness11
- 6.16 Fire hazard and flammability11
- 6.17 Electromagnetic compatibility (EMC)12
- 6.18 Corrosion12
- 6.19 FCL performance on loss of auxiliary equipment12
- 6.101 Composition12
- 6.102 Construction12
- 6.103 Communication requirements in the current-limiting reactor type limiter12
- 6.104 Power supply12
- 6.105 Protection current range12
- 6.106 Device components13
- 6.107 Main circuit resistance14
- 6.108 Temperature rise14
- 6.109 Design of the insulating support structure14
- 7 Type tests15
- 7.1 General15
- 7.2 Insulation tests16
- 7.3 Surge current test16
- 7.4 Continuous current test16
- 7.5 Short-time withstand current and peak withstand current tests16
- 7.6 Short-circuit current limiting test17
- 7.7 Harmonic distortion measurement18
- 7.8 Current breaking test18
- 7.9 Recovery test18
- 7.10 Electromagnetic compatibility test (EMC)18
- 7.11 Noise measurement18
- 7.12 Seismic test18
- 7.13 Tests for FCL specific technologies18
- 7.101 Verification of the short-circuit breaking performance of the limited purpose circuit breaker18
- 7.102 Measurement of the circuit resistance19
- 7.103 Additional tests on the auxiliary and control circuits19
- 7.104 Current limiter starting test19
- 7.105 Verification of the degree of protection19
- 8 Routine tests20
- 9 Selection guidelines22
Foreword
This document was issued on 6 February 2023 by the National Energy Administration of the PRC and takes effect on 6 August 2023.
It is a NB/T standard: recommended rather than compulsory, but it is the text a Chinese reviewer applies when assessing a submission.
It is classified under ICS 29.130.10, Chinese classification K 43.
This document was drafted in accordance with the rules given in GB/T 1.1-2020 Directives for standardization - Part 1: Rules for the structure and drafting of standardizing documents.
Please note that some of the content of this document may be the subject of patent rights. The issuing body of this document assumes no responsibility for identifying patents.
This document was proposed by, and is under the administration of, the energy industry standardization technical committee concerned.
This document is issued for the first time.
1 Scope
NB/T 11077-2023 is the Chinese specification for the fault current limiter built from a current-limiting reactor, for AC systems of 3 kV and above at 50 Hz. It exists because of a problem that grows with the grid rather than with age: as more generation and more interconnection are added, the short-circuit current available at any given busbar rises, and eventually it exceeds what the switchgear installed there was rated to break. The conventional answers are all expensive - replace every breaker in the substation, split the busbar and lose the redundancy, or leave a permanent series reactor in circuit and pay for its losses and voltage drop for the life of the plant. The current-limiting reactor type limiter is the fourth answer: a limited purpose circuit breaker sits in parallel with the reactor and short-circuits it, so in normal operation the reactor is bypassed and the limiter is a low-impedance link. When a fault occurs the control device detects it, opens the parallel breaker at the end of the first large half-wave of fault current, and the reactor is inserted, taking the limiter to its high-impedance state and holding the current down to what the downstream switchgear can clear. Everything then hinges on speed, and this document defines it: the quick fault determination requirement is to establish the starting point, the rate of rise and the maximum value of the short-circuit current within 5 ms. The document names and defines the whole vocabulary of the technique - the C mode and CL mode, the C-CL and CL-C transitions, the limited purpose circuit breaker and the control device - and it is explicit about the limitation, that a limiter of this type may not limit the peak of the very first half-wave. It then sets the service conditions, the ratings, and the design and construction requirements including composition, structure, communications, power supply, protection current range, device components, main circuit resistance, temperature rise and the design of the insulating support structure. The type test clause covers insulation, surge current, continuous current, short-time and peak withstand current, the short-circuit current limiting test itself, harmonic distortion, current breaking, recovery, EMC, noise and seismic tests, together with verification of the limited purpose breaker, the circuit resistance measurement and the limiter starting test; routine tests and selection guidelines close the document. It was issued on 6 February 2023 by the National Energy Administration and took effect on 6 August 2023.
This document specifies the service conditions, the ratings, the design and construction, the type tests, the routine tests and the selection guidelines for high-voltage alternating-current fault current limiters based on a current-limiting reactor.
This document applies to high-voltage alternating-current fault current limiters based on a current-limiting reactor that are designed for indoor or outdoor installation and operate in power systems of 3 kV and above at a frequency of 50 Hz. The individual components fitted in a current-limiting reactor type limiter are designed and tested in accordance with the provisions of their own standards.
This document does not apply to limiters that use a current-limiting reactor alone.
A limiter of this type may not limit the peak of the first half-wave of the fault current.
Note: a high-voltage alternating-current fault current limiter based on a current-limiting reactor is abbreviated to current-limiting reactor type limiter.
2 Normative references
The contents of the following documents constitute indispensable provisions of this document through normative reference in the text. For dated references, only the edition corresponding to that date applies to this document. For undated references, the latest edition, including all amendments, applies to this document.
GB/T 1094.1-2013 Power transformers - Part 1: General
GB/T 1094.6-2011 Power transformers - Part 6: Reactors
GB/T 1984-2014 High-voltage alternating current circuit-breakers
GB/T 2900.20-2016 Electrotechnical terminology - High-voltage switchgear and controlgear
GB/T 11022-2020 Common specifications for high-voltage alternating current switchgear and controlgear standards
GB/T 16927.1-2011 High-voltage test techniques - Part 1: General definitions and test requirements
DL/T 478-2013 General technical requirements for relay protection and automatic safety devices
NB/T 11076-2023 General technical specification for high-voltage alternating current fault current limiters
3 Terms and definitions
The terms and definitions given in GB/T 2900.20-2016, GB/T 11022-2020 and NB/T 11076-2023, together with the following, apply to this document.
3.1 General terms and definitions
3.1.1 fault current limiter, FCL
A device that, by increasing its resistance and/or its reactance so as to change from the non current-limiting mode to the current-limiting mode, limits the expected peak and/or root-mean-square value of the fault current in an alternating current system to the required value or below it. Note 1: the change of resistance and/or reactance may be achieved by a change of the conductance or of the magnetic flux of the device, or by a combination of the two. Note 2: some types of high-voltage alternating-current fault current limiter have fault clearing capability. [NB/T 11076-2023, definition 3.1.1, modified]
3.1.2 current-limiting reactor
A reactor connected in series in a power system in order to limit the fault current of the system. [GB/T 1094.6-2011, definition 3.1.2]
3.1.3 high-voltage alternating-current fault current limiter based on current-limiting reactor, CLR-FCL
A fault current limiter composed of a limited purpose circuit breaker connected in parallel with a current-limiting reactor, together with the associated control devices. Note 1: this term is abbreviated to current-limiting reactor type limiter. Note 2: the reactor referred to in this term is a current-limiting reactor that is inserted for a short time in the current-limiting mode. [NB/T 11076-2023, definition 3.1.2, modified]
3.1.4 limited purpose circuit breaker
A circuit breaker used to change the CLR-FCL between the non current-limiting mode and the current-limiting mode, and capable of interrupting at the end of the first large half-wave of the short-circuit fault current. [NB/T 11076-2023, definition 3.1.8, modified]
3.1.5 non current-limiting mode, C mode
The non current-limiting mode of the current-limiting reactor type limiter. Note: in this state the CLR-FCL is in the low impedance condition. [NB/T 11076-2023, definition 3.1.14, modified]
3.1.6 current-limiting mode, CL mode
The current-limiting mode of the current-limiting reactor type limiter. Note: in this state the CLR-FCL is in the high impedance condition. [NB/T 11076-2023, definition 3.1.15, modified]
3.1.7 C-CL transition
The transition from the C mode to the CL mode. [NB/T 11076-2023, definition 3.1.16]
3.1.8 CL-C transition
The transition from the CL mode to the C mode. [NB/T 11076-2023, definition 3.1.17]
3.1.9 control device
The device associated with the current-limiting reactor type limiter that carries out the detection and identification of the fault current, that is fault determination, together with the control, protection and regulation functions of the limited purpose circuit breaker.
3.2 Definitions relating to the CLR-FCL
3.2.1 short-circuit current
The overcurrent caused by a short circuit resulting from a fault or from an incorrect connection in a circuit. [GB/T 2900.20-2016, definition 3.7]
3.2.2 quick fault determination
The capability, from the instant a short-circuit fault occurs in the system, of completing within 5 ms the determination of the starting point, the rate of rise and the maximum value of the short-circuit current.
Remaining clauses in the full document
- 4 Service conditions
- 5 Ratings
- 6 Design and construction
- 7 Type tests
- 8 Routine tests
- 9 Selection guidelines
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 38 pages — is available in the English PDF.
Referenced standards
Normative references
GB/T 1094.1-2013 Power transformers - Part 1: General · GB/T 1094.6-2011 Power transformers - Part 6: Reactors · GB/T 1984-2014 High-voltage alternating current circuit-breakers · GB/T 2900.20-2016 Electrotechnical terminology - High-voltage switchgear and controlgear · GB/T 11022-2020 Common specifications for high-voltage alternating current switchgear and controlgear standards · GB/T 16927.1-2011 High-voltage test techniques - Part 1: General definitions and test requirements · DL/T 478-2013 General technical requirements for relay protection and automatic safety devices · NB/T 11076-2023 General technical specification for high-voltage alternating current fault current limiters
Similar standards
NB/T 11076-2023|GB/T 1984-2014|GB/T 11022-2020|GB/T 1094.6-2011|DL/T 478-2013
How to Buy NB/T 11077-2023
- 1Add to cart. Click the "Buy NB/T 11077-2023" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
NB/T 10077-2024 — Code for design of rock-filled concrete dams
NB/T 11488-2024 — General specification for power conversion system of flow battery energy storage system
NB/T 11512-2024 — Code for chimney design of fossil-fired power plant
Secure payment via Stripe
Payments accepted
NB/T 11077-2023
$620.00