GB/T 30040.2-2013Leak detection systems—Part 2: Pressure and vacuum systems (English PDF)
双层罐渗漏检测系统 第2部分:压力和真空系统
This is a limited preview
Buy now to download the full PDF (17 pages)
Need quotation for your management?
Get a formal quotation for GB/T 30040.2-2013 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
December 17, 2013
Implementation date
September 1, 2014
Scope
GB/T 30040.2-2013 is the English-translated version of 双层罐渗漏检测系统 第2部分:压力和真空系统.
GB/T 30040.2-2013 is the second part of the Chinese series on leak detection systems for double-walled tanks and pipes, and it covers pressure and vacuum systems.
It defines the terms and symbols, describes how such a system works in the interstitial space between the two walls, and sets the requirements and the tests for the vacuum and pressure leak detectors, for the leak-proof liner and for the leak-proof jacket, together with the marking of the equipment; a normative annex gives the type test of the pressure relief valve.
Makers and installers of tanks for fuels and chemicals, and the bodies that inspect them, use it. Issued on 17 December 2013, it has applied since 1 September 2014.
Found what you need?
Document preview — GB/T 30040.2-2013
National Standard of the People's Republic of China
- ICS
- 23.020.01; 23.040.99; 29.260.20
- Classification
- G 93
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Preface
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 Symbols and
- 5 2 Overview
- 6 2 double gap
- 7 vacuum and pressure leak
- 8 Test
- 9 leakproof liner
- 10 leak-proof jacket
- 11 13 Flag
- Appendix A (normative) pressure relief valve type tests
- Appendix B (normative) drying filter design
- 4 vacuum leak detector test device characteristic curve Temperature Figure 5 -25 °C ~ 25 °C between the curve Temperature Figure 6 70 °C ~ 25 °C between the curve Vacuum leak detection test device 7 Sirens test required
- 8 test equipment required for the test cut-off valve 12 in FIG.
Foreword
GB/T 30040 "double-tank leak detection system" is divided into seven sections.
--- Part 1. General;
--- Part 2. Pressure and vacuum systems;
--- Part 3. Tank Liquid media systems;
--- Part 4. double or facilities used in anti-leakage gap liquid or vapor sensor systems;
--- Part 5. Tank level gauge leak detection systems;
--- Part 6. Monitoring Wells sensor display system;
--- Part 7. Double gap, anti-seepage lining and general requirements and test methods for anti-leakage jacket.
This section GB/T Part of 230,040.
This section drafted in accordance with GB/T 1.1-2009 given rules.
The technical content portion BSEN13160-2:2003 "leak detection systems - Part 2. Pressure and vacuum systems" (in English) Consistent.
7 Vacuum and pressure leak detectors
7.1 Overview
7.1.1 system of vacuum or pressure, including pressure changes caused by changes in temperature, should not exceed the tank, anti-seepage lining, leakproof Design parameters jacket or pipe. Among them, in accordance with Appendix A, under the conditions of pressure relief valve, the pressure can be more than double the gap allowed 90% of the maximum allowable pressure.
7.1.2 vacuum system vacuum pipe line leak detectors located and double gap between, each of which should be installed at a low condensate yield Collection device.
7.1.3 Leak detector system should be set calibration parameters (such as pressure switch threshold adjustment) and analog alarm system.
7.1.4 Leak communicating tube diameter and the gap between the double should be minimized.
a) the communication medium is air having an inner diameter of 6mm;
b) the communication medium is an inert gas having an inner diameter of 4mm.
7.1.5 Leak and double tank communicating pipe or double pipe between the gas flow when the flow rate of (85 ± 15) L/h, the total flow resistance should not exceed Too 1kPa. In the air as the media system, when the communication pipe length l is less than or equal to 50m, its inner diameter should be 6mm.
7.1.6 communication pipe leak detectors and double the gap between the labeling provisions should comply with the following colors.
--- Measuring tube. red;
--- Exhaust pipe or pressure pipe. white or colorless and transparent;
--- Exhaust pipe. green.
7.1.7 a vacuum leak can only be used a tank or a pipeline.
7.1.8 a pipeline can contain multiple duct portion, which double the gap should communicate with each section.
7.1.9 Leak in generating (85 ± 15) L/h gas flow rate should trigger an alarm, see Figure 1. Force change.
7.3 Vacuum leak detector
7.3.1 Overview
7.3.1.1 bilayer pressure should be maintained within the gap between subatmospheric negative pressure until a leak occurred before.
7.3.1.2 Vacuum leak detector for double flat tank should be able to withstand the expected pressure leak occurs.
7.3.1.3 alarm should ensure its reliability in accordance with 7.3.2, if not ensure, in conformity with GB/T 30040.4 double gap in most Low vacuum leak detector in addition to outside, and then install a liquid sensor.
7.3.2 Reliability alert
7.3.2.1 As a reliable guarantee, the vapor space should be double the gap increases leakage of the liquid is reduced, see equation (3).
100000Pa-pPA 100000Pa-p x 100% (3)
7.3.2.2 Preset alarm pressure pAE double gap is based on penetration of liquid
(leakage has occurred) compared to the lowest point of the tank has risen To h1, see formula (4). g x rhoP g x rhoG (4)
7.3.2.3 should be based on the geometry of the tank, calculate the gap in the double injection of liquid leakage when the height h1 volume (in liters or metering), See GB/T 30040.7.
7.3.2.4 if the following conditions are considered reliable alarms, see equation (5).
V < According to GB/T 30040.7.
10 Leak-proof jacket
According to GB/T 30040.7.
11 Logo
According to GB/T 30040.1, in addition.
--- The maximum or minimum allowable pressure;
--- If you use a cut-off valve or a condenser, shall be marked with their rated pressure and composition of the shell material.
Appendix A (Normative)
Type test pressure relief valve A.1 Symbols and p0 the set pressure units. Pa (Pa)
Fe exhaust rate, unit. liter/hour (L/h)
And the exhaust gas pressure deltap p0 Fe rate differential, unit. Pa (Pa) pc termination pressure units. Pa (Pa) p0m measured set pressure units. Pa (Pa) pcm measured termination pressure units. Pa (Pa)
A.2 Test device
Test device consists of the following components.
a) Pressure test vessel with a volume of 1L, at least two nozzles connected to a pressure pump and a pressure relief valve;
b) the environment (simulation) box, the temperature can range from -25 °C ~ 70 °C changes, accuracy 2K;
c) For the temperature range of -40 °C ~ 40 °C test, its environment (simulation) oven temperature range should be -50 °C ~ 40 °C, Accuracy 2K;
d) a pressure pump or air compressor;
e) servo control valves, pressure sensors and pressure programmable controller with an accuracy of 0.5% of the specified set pressure;
f) not more than two times the specified range set a pressure measuring device (for example. pressure gauge);
g) gas flow meter accuracy for the range (at least 300L/h) 1%; h) sink.
A.3 Ready
Pressure relief valve should be installed as shown in Figure A.1. Test vessel and pressure relief valve should be connected to the environment (simulation) box.
A.4 Assessment
A.4.1 Test valve should be evaluated according to the following parameters given by the manufacturer.
--- Set pressure, p0;
--- Exhaust rate under pressure p0 deltap, Fe;
--- Termination pressure, pc;
--- Operating temperature range, namely the underground, anti-frost or outdoor installation.
A.4.2 If p0, p0 deltap and pc values measured before and after the durability test are given by the manufacturer in a difference of 5% or less, the test by. In addition, when the pressure is lower than the termination of pressure, without air through the valve.
A.7.7 durability test procedures according A.6 cycle 1 x 103 times.
A.7.8 environmental (analog) set oven temperature (20 ± 5) °C, and maintain.
A.7.9 A.5 performed according to parameter test procedure.
A.8 Test Results
In accordance with A.7.2 and A.7.9 record p0m, p0m deltap pcm and value, respectively, with the manufacturer of p0, p0 deltap and pc Compared to the value. If all measured values are within ± 5% of the value specified by the manufacturer, type approval is given. Otherwise, the test fails.
Appendix B (Normative) Dry filter design
B.1 Overview
Drying filter to a closed system is a prerequisite, according to a certain sized, so you do not replace within a year.
B.2 Symbols and p1 pPA 100000, unit. Pa (Pa) p2 pPE 100000, unit. Pa (Pa) p3 pAE 100000, unit. Pa (Pa) p4 pSV 100000, unit. Pa (Pa)
(PSV = pressure relief valve opening pressure of the relative value), unit. Pa (Pa) pm (p1 p2)/2 Average working pressure (absolute), unit. Pa (Pa)
T0 15 °C = 288K T1 T0 deltaT2 T2 T1 7.5K deltaT1 according to incremental (B.1) temperature unit. On [Kelvin] (K)
deltaT2 according to the incremental (B.2) temperature unit. On [Kelvin] (K) m1 at a temperature T1 and pressure p4 air quality m2 at a temperature T2 and pressure p4 air quality ma per kilogram of dried silica particles mass absorbed moisture, unit. g/kilogram (g/kg) msch dried silica particles gross weight, unit. kg/m 3 (kg/m3)
V0 extracted air volume (leak detector is discharged through the valve), unit. m 3 (m3)
Volume Vk double gap = 1m3 The maximum volume Vmax leak detector for double gap, unit. m 3 (m3)
VTF filter drier volume, unit. liter (L)
Conventional gas constant R (here, air) = 287J/(kgK)
Air flow rate QL leakage caused unit. m 3/year (m3/a)
The air flow rate Qs exceeds the pressure relief valve to open when the pressure caused by temperature changes, unit. m 3/year (m3/a)
Qgas total flow rate of air (Qs QL), unit. m 3/year (m3/a)
B.3 Dry filter air flow rate
B.3.1 Temperature Effect
Because of a gap in the double rise in temperature leads to a pressure increase of the reaction pressure relief valve, the pressure relief valve is equal to the amount of gas dried
NOTE filter exhaust air flow full amount again.
Referring to the output pressure in accordance with Equation (B.1) temperature increment derived as follows.
deltaT1 = T0 (p4/p1-1) (B.1)
Taking into account the average working pressure pm, according to the formula (B.2) derived deltaT2.
deltaT2 = T0 (p4/pm-1) (B.2)
Therefore, the temperature T1 can be calculated according to equation (B.3).
T1 = T0 deltaT2 (B.3)
Therefore, only the temperature is greater than from the time T0 to T1, the pressure relief valve will cause a reaction.
The average temperature increase leak detection medium exceeds T1 (dry air), then that takes into account the following temperature higher than the average temperature of the warm summer.
--- After 60 days the temperature rises 10K (greater than T1);
--- 60 days temperature 5K (greater than T1).
The average temperature increment mentioned before, if within the 120d reaches 7.5K, should also be taken into account.
B.3.2 Loss calculation
Calculate the air quality in accordance with the formula (B.4) and formula (B.5). m1 = (p1 x Vk)/(R x T1) (B.4) m2 = (p2 x Vk)/(R x T2) (B.5)
, The resulting air quality emissions according to formula (B.6) by the formula (B.5) minus formula (B.4).
T1- (B.6)
Thus, the formula (B.7) gives the emissions of.
V0 = deltam x R x T0/p0 = T0/p0 x Vk x T1- (B.7)
Double gap unit of measurement. cubic meter/cubic meter (m3/m3)
It shall be calculated by the following formula (B.8) according to the filter by drying air flow rate.
Qs = V0 x 120 (B.8)
B.3.3 Impact of leakage
Suppose leak detection system, there are 2.0L/d average leak rate that 0.73m3/a.
B.3.4 Results
According to the formula (B.9) obtained dried filter air flow should be.
Qgas = Qs QL (B.9)
Double gap volume by 1m3 dollars.
B.4 Filter drier volume calculation
For ease of calculation, temperature 30 °C, humidity of 80% air. Moisture in air at atmospheric pressure conditions fL = 25mL/m3 = 0.025kg/m3.
Install filter drier, so that air drawn according to equation (B.9) flow rate of drying to a residual moisture content of at least 10%. That is according to the following Formula (B.10) calculated in dry filled with dried silica particles filter year after the volume.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 17 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 30040.1Leak detection systems—Part 1: General principles
- GB/T 30040.4Leak detection systems - Part 4: Liquid and/or vapour sensor systems for use in leakage containments or interstitial spaces
- GB/T 30040.7Leak detection systems - Part 7: General requirements and test methods for interstitial spaces, leak protecting linings and leak protecting jacket
EN 764
Similar standards
How to Download GB/T 30040.2-2013
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 30040.1-2013 — Leak detection systems—Part 1: General principles
GB/T 30040.4-2013 — Leak detection systems - Part 4: Liquid and/or vapour sensor systems for use in leakage containments or interstitial spaces
GB/T 30040.7-2013 — Leak detection systems - Part 7: General requirements and test methods for interstitial spaces, leak protecting linings and leak protecting jacket
Secure payment via Stripe
Payments accepted
GB/T 30040.2-2013
$315.00