GB/T 24923-2010Technical specification for standard electric valve actuators (English PDF)
普通型阀门电动装置技术条件
This is a limited preview
Buy now to download the full PDF (17 pages)
Need quotation for your management?
Get a formal quotation for GB/T 24923-2010 in 30 minutes.
Issued by
General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC
Level / Type
National · Recommended
Issue date
August 9, 2010
Implementation date
December 31, 2010
Scope
GB/T 24923-2010 is the English-translated version of 普通型阀门电动装置技术条件.
China's national technical specification for standard electric valve actuators. It specifies the types and basic parameters, the technical requirements, the test methods, the inspection rules and the marking, packaging, transport and storage of electric valve actuators of ordinary, non-explosion-protected construction.
This is the companion to GB/T 24922 and covers the actuator as a machine, without the flameproof enclosure requirements - which is the great majority of them, since water treatment, power generation, district heating, HVAC and general industry have no hazardous area.
What is left when the explosion protection is removed is the part that determines whether the valve works, and it is more demanding than it looks.
An actuator has to develop a torque or thrust large enough to seat a valve and unseat it after it has been closed for months, and it must stop at exactly the right point: too little travel and the valve leaks, too much and the seat or the stem is destroyed.
That is done by limit switches - travel switches for position and torque switches for load - and the interaction between them is the heart of the device: a rising-stem valve is normally closed on torque and opened on travel, and getting that logic wrong breaks the valve on the first stroke.
The actuator must also fail safely and predictably, be operable by hand when the power is off, indicate its position locally and remotely, and survive being installed outdoors on a pipe and left for twenty years.
So the standard specifies the torque and thrust ratings and their classes, the switch arrangement and its adjustment, the manual override and its interlock, the duty rating and the motor thermal protection, the position indication and the control interface, the ingress protection and the environmental conditions. Issued on 9 August 2010 and in force since 31 December 2010.
Found what you need?
Document preview — GB/T 24923-2010
National Standard of the People's Republic of China
- ICS
- 23.060.99
- Classification
- J 16
Issued by: General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration of the PRC
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
Foreword
The standard proposed by China Machinery Industry Federation. The standard valve by the National Standardization Technical Committee (SAC/TC188) centralized. This standard is drafted by: Tianjin Baili Machinery Co., Ltd., Hefei General Machinery Research Institute, Yangzhou Electric Power Equipment Factory built, often State Power Station Auxiliary Equipment Factory Co., Ltd., China · Teflon Group Co., Ltd. Tianjin Ai Kete valve control Equipment Co., Ltd., Huangshan Liang industry Valve Co., Ltd. The main drafters of this standard. Wang Lei, Song Zhongrong, Liu Huaifu, Zhule Yao Jiang New Year, Li Jinshuo, Cao record type, item Megan, Chen Huaxiang, ZHAO. Common type valve electric device technology
1 Scope
China's national technical specification for standard electric valve actuators. It specifies the types and basic parameters, the technical requirements, the test methods, the inspection rules and the marking, packaging, transport and storage of electric valve actuators of ordinary, non-explosion-protected construction. This is the companion to GB/T 24922 and covers the actuator as a machine, without the flameproof enclosure requirements - which is the great majority of them, since water treatment, power generation, district heating, HVAC and general industry have no hazardous area. What is left when the explosion protection is removed is the part that determines whether the valve works, and it is more demanding than it looks. An actuator has to develop a torque or thrust large enough to seat a valve and unseat it after it has been closed for months, and it must stop at exactly the right point: too little travel and the valve leaks, too much and the seat or the stem is destroyed. That is done by limit switches - travel switches for position and torque switches for load - and the interaction between them is the heart of the device: a rising-stem valve is normally closed on torque and opened on travel, and getting that logic wrong breaks the valve on the first stroke. The actuator must also fail safely and predictably, be operable by hand when the power is off, indicate its position locally and remotely, and survive being installed outdoors on a pipe and left for twenty years. So the standard specifies the torque and thrust ratings and their classes, the switch arrangement and its adjustment, the manual override and its interlock, the duty rating and the motor thermal protection, the position indication and the control interface, the ingress protection and the environmental conditions. Issued on 9 August 2010 and in force since 31 December 2010.
This standard specifies the terms and definitions common type valve electric device, technical requirements, test methods, inspection rules, marking, packaging, transportation And storage. This standard applies to switching valve with an ordinary electric valve actuators (hereinafter referred to as electric apparatus).
2 Normative references
The following documents contain provisions which, through reference in this standard and become the standard terms. For dated references, subsequent Amendments (not including errata content) or revisions do not apply to this standard, however, encourage the parties to the agreement are based on research Whether the latest versions of these documents. For undated reference documents, the latest versions apply to this standard.
GB/T 3181-2008 standard paint colors
GB/T 3797-2005 Electric Control Equipment
GB 4208 housing protection (IP Code) ( GB 4208-2008, IEC 60529.2001, IDT)
GB/T 12222 multi-turn valve actuator connecting means ( GB/T 12222-2005, ISO 5210.1991, MOD)
GB/T 12223 part of the rotary valve drive connecting means ( GB/T 12223-2005, ISO 5211.2001, MOD) GB/T 21465 valve term
JB/T 2195-1998 YDF2 series of electric valve actuators with three-phase induction motor
JB/T 8862 valve electric device life test procedures
3 Terms and Definitions
GB/T 21465 and established the following terms and definitions apply to this standard.
3.1 Nominal torque nominaltorque Shows the identification electric actuator output torque size, for ease of electric equipment design, manufacture, use, distribution, use, and maintenance and unity Predetermined torque value, which is related to the value of the operating torque.
3.2 Nominal thrust nominalthrust Logo indicates that the output shaft of the electric device to drive the stem nut to produce axial force size, for ease of electric equipment design, manufacture, use, stream Through, use and maintenance of uniform provisions thrust value, which is related to the value of the work force.
3.3 Operating torque workingtorque Valves open and close the required torque, operating torque should not exceed the nominal torque.
3.4 Working thrust workingthrust Valve opening, closing thrust value needed for the work force should not exceed the nominal thrust.
3.5 Stall Torque blockingtorque Electric apparatus load is increasing, the torque value of the motor stall time.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 17 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 3181-2008Colour standard for paint film
- GB/T 3797-2005Electrical control assemblies
- GB/T 12222-2005Multi-turn valve actuator attachments
- GB/T 12223-2005Part-turn valve actuator attachments
- GB/T 21465Terminology for valves
- JB/T 2195-1998Specification for YDF2 series three-phase induction motor applying to electromotion device of valve
GB 4208-2008 · IEC 60529.2001 · ISO 5210.1991 · ISO 5211.2001
Cited by
- DL/T 1107-2019Basic specifications of automatic components for hydropower plant
- DL/T 2027-2019Guidelines for the ordering and acceptance of steam traps in thermal power plants
- JG/T 529-2018The headers and flexible multi-connected devices for hot and cold water distribution to air-conditioning terminals
- CJ/T 481-2016General specifications of ductile iron valves for water supply
- CJ/T 295-2015Grease-water separator for restaurant wastewater
- NB/T 42056-2015Fundamental technical requirements for inlet valves of small hydraulic turbine
Similar standards
GB/T 24922-2010|GB/T 12222-2005|GB/T 12223-2005|GB/T 4208-2017|GB 5226.1-2019|GB/T 22712-2021
How to Download GB/T 24923-2010
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 21465-2008 — Terminology for valves
GB/T 3181-2008 — Colour standard for paint film
JB/T 2195-1998 — YDF2 series three-phase asynchronous motors for electric valve actuators - Technical specifications
Secure payment via Stripe
Payments accepted
GB/T 24923-2010
$125.00