GB/T 24835-2018Regulation of operation and maintenance for 1100kV gas-insulated metal-enclosed switchgear (English PDF)

1100kV气体绝缘金属封闭开关设备运行维护规程

Preview PDF

This is a limited preview

Buy now to download the full PDF (15 pages)

Need quotation for your management?

Get a formal quotation for GB/T 24835-2018 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

December 28, 2018

Implementation date

July 1, 2019

Scope

GB/T 24835-2018 is the English-translated version of 1100kV气体绝缘金属封闭开关设备运行维护规程.

GB/T 24835-2018 sets out how 1100 kV gas-insulated metal-enclosed switchgear (GIS), including hybrid HGIS, is operated and maintained in service.

It starts from safety during operation: protection of the GIS room, oxygen content and SF6 gas concentration monitoring with alarms, gas masks and protective clothing at the entrances, fire protection, sealed cable openings and forced ventilation with outlets near the floor.

It then gives the technical requirements for routine operation and maintenance, quality supervision of the SF6 gas, and the technical requirements for disassembly and repair, including the tests to be carried out after repair.

Substation operators, maintenance crews and utilities running UHV AC stations use it. It was issued on 28 December 2018 and has applied since 1 July 2019.

Found what you need?

Document preview — GB/T 24835-2018

National Standard of the People's Republic of China

ICS
29.240
Classification
K 43

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword
  • 1 Scope
  • 2 Normative references
  • 3 Safety requirements for operation and maintenance
  • 4 Technical requirements for operation and maintenance
  • 5 Quality Supervision of SF6 Gas
  • 6 Technical requirements for disassembly and repair

Foreword

This standard was drafted in accordance with the rules given in GB/T 1.1-2009.

This standard replaces GB /Z 24835-2009 "1000kV gas insulated metal-enclosed switchgear operation and maintenance procedures", and The main changes compared with GB /Z 24835-2009 are as follows.

--- Removed "terms and definitions" (see Chapter 3 of the 2009 edition);

--- Removed the "auxiliary system (air compressor system for pneumatic mechanisms)" (see 7.4.6 of the 2009 edition);

--- Removed the general flow chart of GIS decomposition and maintenance (see 7.7 of 2009 edition);

--- Removed the "Decomposition Check" (see 7.8 of the 2009 edition);

--- Removed the precautions for the use of gas recovery units (see 7.9 of the 2009 edition);

--- Removed the precautions for storage of gas cylinders (see 7.10 of the 2009 edition);

--- Remove the precautions for the use of adsorbents (see 7.11 of the 2009 edition);

--- Deleted the organization notes after disassembly and repair (see 7.12 of 2009 edition);

--- Removed the "Selection and Test of Grease and Sealant" (see 7.13 in 2009);

--- Removed the "Technical Requirements for Sealing and Disassembling" (see 7.14 in 2009);

--- Removed "spare parts and special tools" (see Chapter 9 of the 2009 edition);

--- Removed the "positioning and detection methods for discharge faults" (see Appendix A of the 2009 edition);

--- Revised the basis for the disassembly and repair of the circuit breaker (see 6.1.1, 4.4.4.1 of the 2009 edition);

---Modified the dismantling and maintenance project of the circuit breaker in GIS, and deleted the "pneumatic operating mechanism" (see 6.2.1.2, 7.4.1.2 of 2009 edition);

--- Revise the technical requirements for physical examination and repair, and incorporate the "test" (see the 8th edition of 2009) into the "experiment after disassembly and repair" (see 6.7).

1 Scope

This standard specifies the project, content and technology of 1100kV gas insulated metal-enclosed switchgear (hereinafter referred to as GIS) operation and maintenance. Claim.

This standard applies to rated voltage 1100kV AC GIS (including HGIS).

2 Normative references

The following documents are indispensable for the application of this document. For dated references, only dated versions apply to this document. For undated references, the latest edition (including all amendments) applies to this document.

GB/T 5832.1 Determination of trace moisture - Part 1. Electrolysis

GB/T 5832.2 Determination of trace moisture - Part 2. Dew point method

GB/T 11023 High-voltage switchgear sulphur hexafluoride gas seal test guide

GB/T 12022 industrial sulfur hexafluoride

GB/T 24846-2018 1000kV AC electrical equipment preventive test procedures

Guide for on-site withstand voltage and insulation test of DL/T 555 gas-insulated metal-enclosed switchgear

3 Safety requirements for operation and maintenance

3.1 Safety technical measures during GIS operation

3.1.1 Security protection of GIS room

The security protection of the GIS room is as follows.

a) According to GB 8958GIS, the oxygen content in indoor air should be greater than 19.5% or the concentration of SF6 gas should not exceed 1000 µL/L. (or 6g/m³);

b) The GIS indoor should be equipped with an automatic detection and alarm device for air oxygen content or SF6 gas concentration;

c) Protective equipment such as gas masks, protective clothing and plastic gloves should be provided at the entrance and exit of the GIS room;

d) The GIS room shall be equipped with special fire protection facilities in accordance with the relevant provisions of fire protection;

e) All access holes in the GIS room shall be sealed with fireproof materials;

f) The GIS room should be equipped with adequate ventilation and exhaust devices;

g) When entering the GIS indoor cable trench or low recess, the oxygen content or SF6 gas concentration should be measured, and the safety can be confirmed before entering;

h) In order to prevent accidents in single-person operations, access to these areas requires supervision.

3.1.2 Ventilation technical requirements for GIS room

The GIS room should be equipped with a powerful ventilation device, and the air outlet should be placed at the bottom of the room.

The GIS room where the operators frequently enter and exit, each class should be ventilated at least once (15min); for indoor places where the staff does not frequently enter and exit, Check the ventilation facilities regularly.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.

Referenced standards

Similar standards

How to Download GB/T 24835-2018

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
15 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 24835-2018

$205.00