Scope
GB 37479-2019 is the English-translated version of 风管送风式空调机组能效限定值及能效等级.
GB 37479-2019 is the Chinese national standard on minimum allowable values of energy efficiency and energy efficiency grades for ducted air conditioners, in the field of energy and heat transfer engineering. It carries no /T suffix, which in the Chinese system means compliance is mandatory: a product or a practice within its scope has to meet it to be lawfully made, sold or carried out in China. It was issued on 4 April 2019 by the State Administration for Market Regulation; Standardization Administration of China, and has been in force since 1 November 2020. Classification: ICS 27.010, CCS F01. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the issuing body are taken from there. The clause text, the tables and the numeric limits are in the document itself, which is delivered complete in English translation.
Document preview — GB 37479-2019
National Standard of the People's Republic of China
- ICS
- 27.010
- Classification
- F01
Issued by: State Administration for Market Regulation; Standardization Administration of China
Contents
- Foreword ..........................................................................................................3
- 1 Scope ............................................................................................................4
- 2 Normative references ....................................................................................4
- 3 Terms and definitions.....................................................................................4
- 4 Energy efficiency grades ...............................................................................5
- 5 Technical requirements..................................................................................6
- 6 Test method ...................................................................................................7
Foreword
Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Ducted Air Conditioners
Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Ducted Air Conditioners 1 Scope
This Standard specifies the energy efficiency grades, technical requirements and test methods for ducted air conditioners. This Standard is applicable to ducted air-conditioning (heat pump) units and direct evaporation all fresh air handling units that use motor-driven compressors, and whose indoor unit static pressures are greater than
0 Pa (gauge pressure).
2 Normative references
The following documents are indispensable for the application of this document. For dated references, only the dated version applies to this document. For undated references, the latest edition (including all amendments) applies to this document.
GB/T 17758-2010, Unitary air conditioners
GB/T 18836, Ducted air-conditioning (heat pump) units
GB 21455, Minimum allowable values of the energy efficiency and energy efficiency grades for variable speed room air conditioners
GB/T 25128-2010, Direct evaporation all fresh air handling units
3 Terms and definitions
Terms and definitions determined by GB/T 18836, GB/T 25128-2010 and the following ones are applicable to this document.
5 Technical requirements 5.1 The minimum allowable values of ducted air-conditioning (heat pump) units and direct evaporation all fresh air handling units are the index values corresponding to grade-3 of the energy efficiency grades in Table 1.
5.2 Products which use electric auxiliary heating shall realize manual opening and closing of auxiliary heating system, and shall be installed with devices that show the working state of the electric auxiliary heating system in obvious position.
5.3 Under the condition when the outdoor-side dry bulb temperature of the product is larger than or equal to 0°C, the electric auxiliary heating shall not be automatically turned on.
5.4 The allowable difference shall meet the following requirements:
a) The marked value of energy efficiency of the product shall not be less than the specified index value corresponding to the rated energy efficiency grade, and it shall be within the value range corresponding to the rated energy efficiency grade.
b) The actual test value of energy efficiency of the product shall not be less than 95% of the marked value.
c) The marked nominal cooling capacity and actual test value of the product shall be within the nominal cooling capacity corresponding to the rated energy efficiency grade.
d) The calculated value of actual-measured power consumption of the product shall be less than or equal to 110% of the marked-value.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 11 pages — is available in the English PDF.
Referenced standards
Normative references
Similar standards
Editions of GB 37479
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB 37479-2019 | Minimum allowable values of energy efficiency and energy efficiency grades for ducted air conditioners | current edition | Current |
This page sells the current edition, GB 37479-2019. Earlier editions are listed for reference only.
How to Buy GB 37479-2019
- 1Add to cart. Click the "Buy GB 37479-2019" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 21455-2019 — Minimum allowable values of energy efficiency and energy efficiency grades for room air conditioners
GB/T 18836-2017 — Ducted air-conditioning (heat pump) units