GB 14287.9-2026Electrical fire monitoring system - Part 9: Insulation monitoring device of electrical fire (English PDF)

电气火灾监控系统 第9部分:探测绝缘性能式电气火灾监控探测器

Open the GB 14287.9-2026 preview as PDF

Preview — first pages of GB 14287.9-2026 (full document: 24 pages)

This is a limited preview

Buy now to download the full PDF (24 pages)

Issued by

SAMR; SAC

Level / Type

National · Mandatory

Issue date

January 28, 2026

Implementation date

February 1, 2027

Scope

GB 14287.9-2026 is the English-translated version of 电气火灾监控系统 第9部分:探测绝缘性能式电气火灾监控探测器.

Part 9 of GB 14287 is a new part covering the insulation monitoring detector, which measures the insulation resistance of a live circuit continuously rather than inferring a problem from the leakage current it produces. The standard sets the classification, the general requirements and appearance, the performance of the main components, the basic, fault alarm, monitoring alarm and communication functions, then the electrical requirements - insulation resistance, leakage current, dielectric strength, electromagnetic compatibility and tolerance of voltage fluctuation - and the mechanical and climatic endurance, with twenty-one test methods, the inspection rules, the marking and two normative annexes. Issued on 28 January 2026, in force from 1 February 2027; first edition. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the edition it replaces are taken from there. The clause text, the tables and the numeric limits are not reproduced on this page - they are in the document itself, which is delivered in full in English translation.

Document preview — GB 14287.9-2026

National Standard of the People's Republic of China

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • 1.Scope1
  • 2 Normative References1
  • 3.Terms and Definitions1
  • 4.Classification2
  • 5 Requirements2
  • 5.1 General Requirements2
  • 5.2 Appearance2
  • 5.3 Performance of Major Components2
  • 5.4 Basic Functions3
  • 5.5 Fault Alarm Function4
  • 5.6 Monitoring and alarm functions4
  • 5.7 Communication Functions4
  • 5.8 Insulation resistance4
  • 5.9 Leakage Current4
  • 5.10 Electrical strength4
  • 5.11 Electromagnetic Compatibility5
  • 5.12 Voltage fluctuation6
  • 5.13 Mechanical environmental tolerance6
  • 5.14 Climate and Environmental Tolerance6
  • 5.15 Instruction Manual6
  • 6.1 General Requirements6
  • 6.2 Appearance and major component inspection8
  • 6.3 Basic Function Test9
  • 6.4 Fault Alarm Function Test12
  • 6.5 Monitoring and Alarm Function Test12
  • 6.6 Communication Function Test12
  • 6.7 Insulation resistance test12
  • 6.8 Leakage Current Test12
  • 6.9 Electrical strength test13
  • 6.10 Radio Frequency Electromagnetic Field Radiation Immunity Test13
  • 6.11 Conducted Interference Immunity Test Based on Radio Frequency Field Induction13
  • 6.12 Electrostatic Discharge Immunity Test14
  • 6.13 Electrical Fast Transient/Bulk Immunity Test14
  • 6.14 Surge (Impulse) Immunity Test14
  • 6.15 Immunity test for voltage sags, short interruptions and voltage variations14
  • 6.16 Power Frequency Magnetic Field Immunity Test15
  • 6.17 Voltage Fluctuation Test15
  • 6.18 Vibration (Sine) (Running) Test15
  • 6.19 Crash Test16
  • 6.20 Low Temperature (Operation) Test16
  • 6.21 Constant Humidity and Heat (Operation) Test16
  • 7.Inspection Rule16
  • 7.1 Factory Inspection16
  • 7.2 Type Testing17
  • 8.Markings and Packaging17
  • 8.1 Product Marking17
  • 8.2 Quality Inspection Mark17
  • 18 Appendix B (Normative) Detector Housing Combustion Performance 19 B.1 Requirement 19 B.2 Experiment 19 B.3 requires20

Foreword

This document complies with the provisions of GB/T 1.1-2020 "Standardization Work Guidelines Part

1.Structure and Drafting Rules of Standardization Documents". Drafting. This document is Part 9 of GB 14287 "Electrical Fire Monitoring Systems". GB 14287 has the following parts published.

1.Electrical Fire Monitoring Equipment;

2.Residual Current Type Electrical Fire Monitoring Detector;

3.Temperature-measuring electrical fire monitoring detectors;

4.Fault Arc Detectors;

5.Measurement of Pyrolytic Particle Electrical Fire Monitoring Detectors;

6.Harmonic Suppression Electrical Fire Monitoring Devices;

7.Electrical Fire-Resistant Current-Limiting Protective Devices;

9.Electrical fire monitoring detectors that detect insulation performance. Please note that some content in this document may involve patents. The issuing organization of this document assumes no responsibility for identifying patents. This document was proposed and is under the jurisdiction of the State Fire and Rescue Administration.

With rapid socio-economic development and increasing demand for electricity from residents, total electricity consumption has continued to grow, leading to a continuous increase in the complexity of electrical systems. Electrical fires are occurring frequently, causing significant property damage and casualties. Preventing electrical fires and reducing casualties and property losses are crucial. To prevent property damage, building an electrical fire monitoring system and identifying potential hazards in advance through monitoring and early warning mechanisms has become a core requirement for fire safety assurance. Electrical fire monitoring systems differ from fire detection and alarm systems in that they focus on the early identification of potential electrical faults and anomalies through dynamic monitoring. Detection and early warning intervention can break the accident chain that leads to electrical faults evolving into fires. With the evolution of electrical fire monitoring and detection technology, domestic research and industrial institutions have developed technologies suitable for IT grounding systems and based on power distribution systems. Electrical fire monitoring products that integrate insulation performance detection serve as key components of electrical fire monitoring systems, supporting practical electrical fire prevention and control. Due to the needs of technological development and application, it is urgent to formulate this document to improve the technical approach for identifying electrical fire hazards in the GB 14287 standard system. Comprehensive coverage. This document standardizes the technical requirements and testing methods for electrical fire monitoring detectors that detect insulation performance, guiding industry players in their work. Product design, production, inspection, and engineering applications enhance the accuracy and reliability of hazard identification in electrical fire monitoring systems, contributing to international trade and technology. It provides a technological benchmark for communication and industry-collaborative innovation. GB 14287 "Electrical Fire Monitoring Systems" is the fundamental standard guiding the production, inspection, and use of electrical fire monitoring systems in my country. It is planned to consist of nine parts.

1.Electrical Fire Monitoring Equipment. The purpose is to standardize the general technical requirements for electrical fire monitoring equipment products and improve production efficiency. Product quality.

2.Residual Current Type Electrical Fire Monitoring Detectors. The purpose is to standardize residual current type electrical fire monitoring detectors. General technical requirements for products, to improve product quality.

3.Temperature-Sensing Electrical Fire Monitoring Detectors. The purpose is to standardize the use of temperature-sensing electrical fire monitoring detectors. Use technical requirements to improve product quality.

1 Scope

Part 9 of GB 14287 is a new part covering the insulation monitoring detector, which measures the insulation resistance of a live circuit continuously rather than inferring a problem from the leakage current it produces. The standard sets the classification, the general requirements and appearance, the performance of the main components, the basic, fault alarm, monitoring alarm and communication functions, then the electrical requirements - insulation resistance, leakage current, dielectric strength, electromagnetic compatibility and tolerance of voltage fluctuation - and the mechanical and climatic endurance, with twenty-one test methods, the inspection rules, the marking and two normative annexes. Issued on 28 January 2026, in force from 1 February 2027; first edition. This page is published from the official record of the standard held by the Chinese standards administration: the identification, the dates, the classification and the edition it replaces are taken from there. The clause text, the tables and the numeric limits are not reproduced on this page - they are in the document itself, which is delivered in full in English translation.

This document defines the terminology for electrical fire monitoring detectors that detect insulation performance, and specifies their classification, requirements, inspection rules, and markings. The packaging describes the corresponding test methods. This document applies to electrical fire monitoring detectors (hereinafter referred to as "detectors") used in electrical fire monitoring systems to detect insulation performance. Product design, manufacturing, and inspection.

2 Normative references

The contents of the following documents, through normative references within the text, constitute essential provisions of this document. Dated citations are not included. For references to documents, only the version corresponding to that date applies to this document; for undated references, the latest version (including all amendments) applies. This document.

GB/T 9969 General Rules for Instructions for Use of Industrial Products

GB 12978 Inspection Rules for Fire Protection Electronic Products

GB 14287 (all parts) Electrical fire monitoring systems

GB/T 16838 Environmental testing methods and severity levels for fire protection electronic products

GB/T 17626.2 Electromagnetic compatibility testing and measurement techniques - Electrostatic discharge immunity test

GB/T 17626.3 Electromagnetic compatibility testing and measurement techniques - Part

3 Terms and Definitions

The following terms and definitions apply to this document.

3.1 In AC and DC power distribution systems with ungrounded neutral points or high-resistance grounded power supplies, active injection into the monitored power distribution system is employed. The measurement signal detects the resistive insulation resistance value of the power distribution system to ground, or the resistive insulation resistance value of the power distribution system/load to other equipotential reference points. The detector.

Note. AC power distribution systems and DC power distribution systems with ungrounded neutral points and high-resistance grounding are hereinafter referred to as "IT systems".

3.1.1 A detector that independently detects the insulation performance of the monitored system and issues audible and visual monitoring alarm signals.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 24 pages — is available in the English PDF.

Referenced standards

Editions of GB 14287.9

EditionTitleRevisionStatus
GB 14287.9-2026Electrical fire monitoring system - Part 9: Insulation monitoring device of electrical firecurrent editionCurrent

This page sells the current edition, GB 14287.9-2026. Earlier editions are listed for reference only.

How to Buy GB 14287.9-2026

  1. 1Add to cart. Click the "Buy GB 14287.9-2026" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
24 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB 14287.9-2026

$425.00

$360.00for partners