NB/T 10614-2021General requirements for coordinated control of parallel operation for dynamic var compensator (English PDF)
动态无功补偿装置并列运行协调控制通用要求
This is a limited preview
Buy now to download the full PDF (22 pages)
Need quotation for your management?
Get a formal quotation for NB/T 10614-2021 in 30 minutes.
Issued by
NEA
Level / Type
Industry · Recommended
Issue date
April 26, 2021
Implementation date
July 26, 2021
Scope
NB/T 10614-2021 is the English-translated version of 动态无功补偿装置并列运行协调控制通用要求.
NB/T 10614-2021 is the Chinese energy industry standard for the coordinated control of two or more dynamic var compensators operating in parallel in new energy stations connected to grids of 10 kV and above.
It sets basic, functional and performance requirements, such as response and settling times, together with test requirements. Informative annexes describe coordinated control strategies, a communication protocol, a case study from a new energy station and an overview of how the technology has developed.
Coordinated control of several compensators in other settings may follow it by reference. Grid operators, station owners and equipment suppliers are its main users. It was issued on 26 April 2021 and has applied since 26 July 2021.
Found what you need?
Document preview — NB/T 10614-2021
National Standard of the People's Republic of China
- Classification
- K 04
Issued by: National Energy Administration of the People's Republic of China
Contents
- Preface
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
- 4 Basic requirements
- 5 Functional Requirements
- 6 Performance Requirements
- 7 Test requirements
- Appendix A (Informative) Coordinated Control Strategy of Dynamic Reactive Power Compensation Device
- Appendix B (Informative) Communication Protocol for Coordinated Control of Dynamic Reactive Power Compensation Device
- Appendix D (Informative) Overview of Coordinated Control Technology Development of Multiple Dynamic Reactive Power Compensation Devices in New Energy Stations Reference
Foreword
This document is in accordance with the provisions of GB/T 1.1-2020 "Guidelines for Standardization Work Part 1: Structure and Drafting Rules of Standardization Documents" drafted.
Certain contents of this document may be patented. The issuing agency of this document assumes no responsibility for identifying patents.
1 Scope
This document specifies the basic requirements, functional requirements, performance requirements, test requirements, etc. common enquiries.
This document is applicable to multiple sets (two sets or more) of dynamic reactive power in new energy stations connected to power systems with voltage levels of 10kV and above Coordinated control of compensation devices. Coordinated control of multiple sets of dynamic reactive power compensation devices in other scenarios can be implemented by reference.
2 Normative references
The contents of the following documents constitute essential provisions of this document through normative references in the text. Among them, dated citations documents, only the version corresponding to that date applies to this document; for undated references, the latest edition (including all amendments) applies to this document.
GB/T 18657.1-2002 Telecontrol Equipment and Systems Part 5: Transmission Protocol Part 1: Transmission Frame Format
3 Terms and Definitions
The following terms and definitions apply to this document.
3.1 Dynamic var compensator
A reactive power compensation device with dynamically adjustable impedance composed of capacitors (groups), reactors (groups), controllable switching devices and control devices. [Source: GB/T 32507-2016, 5.8]
3.2 Static var generator
Dynamic reactive power compensation device based on voltage source converter or current source converter. [Source: GB/T 32507-2016, 5.11]
3.3 Static var compensator
A stationary electrical device capable of absorbing controllable capacitive or inductive currents from a power system, thereby emitting or absorbing reactive power, system or device. [Source: GB/T 32507-2016, 5.9]
3.4 Response time
It starts from the change of the control target measurement value of the dynamic reactive power compensation device to exceed the set control target qualified range, until the dynamic reactive power compensation
The time required for the change of the actual output value of the compensation device to reach 90% of the difference between the device output target value and the initial value. As shown in Figure 1. [Source: NB/T 31099-2016, 3.9, with modifications]
3.5 Settling time
It starts from the change of the control target measurement value of the dynamic reactive power compensation device to exceed the set control target qualified range, until the dynamic reactive power compensation
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 22 pages — is available in the English PDF.
Referenced standards
Similar standards
How to Download NB/T 10614-2021
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Fast delivery
After payment you'll receive an email confirmation. The English PDF is sent to the same address, usually within minutes and at the latest within 1 business day.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 18657.1-2002 — Telecontrol equipment and systems -- Part 5: Transmission protocols -- Section 1: Transmission frame formats
NB/T 10186-2026 — Technical specification for power conversion equipment used in photovoltaic-storage systems
NB/T 11969-2026 — Guide for energy efficiency assessment of off-board conductive chargers for electric vehicles
NB/T 10614-2021
$390.00