JB/T 1612-1994Technical specifications for hydrostatic tests of boilers (English PDF)
锅炉水压试验技术条件
This is a limited preview
Buy now to download the full PDF (15 pages)
Need quotation for your management?
Get a formal quotation for JB/T 1612-1994 in 30 minutes.
Issued by
MIIT
Level / Type
Industry · Recommended
Issue date
December 9, 1994
Implementation date
June 1, 1995
Scope
JB/T 1612-1994 is the English-translated version of 锅炉水压试验技术条件.
JB/T 1612-1994 is the Chinese standard "Technical specifications for hydrostatic tests of boilers". Its scope clause reads: This standard specifies the methods for the hydraulic test of the entire boiler and all the single pressure components and parts.
This standard is applicable to the stationary boilers. Its clauses include subject contents and application scope; test equipments and instruments; test pressure.
Found what you need?
Document preview — JB/T 1612-1994
National Standard of the People's Republic of China
- Replacing
- JB 1612-1983
Issued by: Ministry of Industry and Information Technology of the People's Republic of China
Contents
- 1 Subject Contents and Application Scope
- 2 Normative References
- 3 Test Equipments and Instruments
- 4 Test Pressure
- 5 Operating Method
- 6 Acceptance Criteria
- 7 Quality Certificate
1 Subject Contents and Application Scope
This standard specifies the methods for the hydraulic test of the entire boiler and all the single pressure components and parts.
This standard is applicable to the stationary boilers.
2 Normative References
GB 9222 "Strength Calculation of Pressure Parts for Watertube Boilers"
JB 3622 "Strength Calculation of Pressure Parts for Shell Boilers"
3 Test Equipments and Instruments
3.1
Various holes (manhole, handhole and head-hole) opened in the pressure parts shall not be used with any temporary sealing devices, the closure plates at the tube joints shall have adequate strength and the welds on closure plates shall be tight reliably.
3.2
In the test, two pressure gages that are qualified through regular calibration shall be installed, and their measuring range shall be 1.5~3 times of the test pressure, which is recommended to be twice of the test pressure.
4 Test Pressure
4.1
The test pressure Ps1 adopted in the hydraulic test of entire hot water boilers (excluding cast iron boilers) shall be in accordance with Table 1, and the pressure P1 in Table 1 is the rated water-delivery pressure (also called as "allowable working pressure") of boilers.
4.2
The test pressure Ps2 adopted in the hydraulic test of entire cast iron boilers shall be in accordance with Table 2, and the pressure P1 in Table 2 is the rated water-delivery pressure (also called as "allowable working pressure") of boilers.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Cited by
- GB/T 30577-2014Specification of heat recovery steam generator for combined-cycle for gas-steam
- NB/T 51012-2014Regenerative oxidizer for coal mine ventilation air methane
- NB/T 34012-2013Technical Specification for the Water Cooled Vibrating Grate of Biomass Boiler
- NB/T 47030-2013Specification of High Frequency Resistance Welded Spiral Fin Tubes for Boiler
- NB/T 47031-2013Specification of Headers and Module for Spiral Fin Tubes
- GB/T 28057-2011Specification for oxygen converter heat recovery boiler
Similar standards
Editions of JB/T 1612
| Edition | Title | Revision | Status |
|---|---|---|---|
| JB/T 1612-1994 | Technical specifications for hydrostatic tests of boilers | current edition | Current |
| JB 1612-1983 | Technical specifications for hydrostatic tests of boilers | previous edition | Superseded |
This page sells the current edition, JB/T 1612-1994. Earlier editions are listed for reference only.
How to Download JB/T 1612-1994
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
JB/T 10062-2026 — Probes used in ultrasonic flaw detection - Testing methods for performance
JB/T 10096-2026 — Cases for power semiconductor devices - Selection guidance
JB/T 10097-2026 — Case for power semiconductor device
Secure payment via Stripe
Payments accepted
JB/T 1612-1994
$169.00