GB/T 6909-2018Analysis of water used in boiler and cooling system—Determination of hardness (English PDF)

锅炉用水和冷却水分析方法 硬度的测定

Preview PDF

This is a limited preview

Buy now to download the full PDF (15 pages)

Need quotation for your management?

Get a formal quotation for GB/T 6909-2018 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

June 7, 2018

Implementation date

January 1, 2019

Scope

GB/T 6909-2018 is the English-translated version of 锅炉用水和冷却水分析方法 硬度的测定.

GB/T 6909-2018 is the Chinese national method for measuring the hardness of water used in boilers and cooling systems.

It gives three procedures: an EDTA titration with chrome black T indicator covering 0.01 mmol/L to 5 mmol/L, an acid chrome blue K titration covering 1 µmol/L to 100 µmol/L, and a potentiometric titration with an automatic titrator and calcium ion electrode covering 0.25 mmol/L to 10 mmol/L, all with Ca2+ and Mg2+ as the basic units.

Clause 1 extends it to natural water, cooling water, demineralized water and boiler feed water. It also fixes the masking of iron, aluminium, copper and manganese interference, the tolerance between parallel results, and the adjustment of the ammonia-ammonium chloride buffer.

It replaces GB/T 6909-2008, was issued on 7 June 2018 and has applied since 1 January 2019.

Found what you need?

Document preview — GB/T 6909-2018

National Standard of the People's Republic of China

ICS
71.040.40
Classification
G 76
Replacing
GB/T 6909-2008

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Foreword3
  • 1 Scope4
  • 2 Normative references4
  • 3 General4
  • 4 Volumetric method5
  • 5 Potentiometric titration method9
  • Annex A (normative) Adjustment of ammonia-ammonium chloride buffer solution11

1 Scope

This Standard specifies the determination method for hardness of water used in boiler and cooling system.

This Standard applies to the determination for hardness of water used in boiler and cooling system. The determination range of chrome black T method in this Standard is 0.01mmol/L~5mmol/L. When it exceeds 5mmol/L, the sampling volume can be appropriately reduced. Determine after dilution. The determination range of acid chrome blue K method is 1µmol/L~100µmol/L. The determination range of potentiometric titration is 0.25mmol/L~10mmol/L (both with Ca2+ and Mg2+ as basic units). This Standard is also applicable to the determination of the hardness of natural water, cooling water, demineralized water and boiler feed water.

2 Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

GB/T 601, Chemical reagent - Preparations of reference titration solutions

GB/T 603, Chemical reagent - Preparations of reagent solutions for use in test methods

GB/T 6682, Water for analytical laboratory use - Specification and test methods

3 General

The reagents used in this Standard, unless otherwise specified, shall be of analytically pure. The water used shall comply with the provisions of GB/T 6682. Of which, the determination of constant hardness shall meet the requirements of grade two water. The […]

4 Volumetric method

4.1.2.6 Disodium ethylenediaminetetraacetic acid standard titration solution I: c (EDTA) is about 0.05mol/L.

4.1.2.7 Disodium ethylenediaminetetraacetic acid standard titration solution II: c(EDTA) is 0.005mol/L. Accurately dilute 10 times with disodium edetate standard titration solution I. This solution is prepared when required.

4.1.2.8 Chrome black T indicator solution: 5g/L
4.1.3 Test steps

4.1.3.1 Use a pipette to measure 100mL of water sample. Place it in a 250mL Erlenmeyer flask. If the water sample is turbid, it shall be filtered with medium-speed quantitative filter paper before sampling. When the water sample is highly acidic or alkaline, it can be neutralized with sodium hydroxide solution or hydrochloric acid solution. The buffer solution is then added. When the iron in the water sample is greater than 2mg/L, the aluminum is greater than 2mg/L, the copper is greater than 0.01mg/L, and the manganese is greater than 0.1mg/L, it will interfere with the determination.

Before adding the indicator, 2mL of L-cysteine hydrochloride solution and 2mL of triethanolamine solution can be used for combined masking to eliminate the interference.

4.1.3.2 Add 5mL of ammonia-ammonium chloride buffer solution. Add two to three drops of chrome black T indicator.

NOTE: For water samples with high carbonate hardness, pre-dilute or add 80%~90% of the required EDTA standard solution before adding the buffer solution (recorded into the titration volume).

Otherwise, after the buffer solution is added, the carbonate is precipitated, and the end point is prolonged.

4.1.3.3 Under constant shaking, use disodium ethylenediaminetetraacetic acid standard titration solution I to titrate. When it is near the end point, titrate slowly. When the solution changes from red to pure blue, it is the end point. When the water sample hardness is less than 1mmol/L, disodium edetate standard titration solution II shall be used, or a microburette (device) shall be used.

4.1.3.4 Conduct the blank test at the same time.

4.1.4 Result calculation

The hardness is expressed in molar concentration c1. The value is expressed in millimoles per liter (mmol/L), calculated according to formula (1):

Where, V1 - The value of the volume of the standard titration solution of disodium edetate consumed by the titration of the water sample, in milliliters (mL);

V0 - The value of the volume of the disodium EDTA standard titration solution consumed by the blank test, in milliliters (mL); c - The exact value of the actual concentration of disodium EDTA standard titration solution, in moles per liter (mol/L);

V - The value of the volume of the water sample measured, in milliliters (mL) (V=100).

4.1.5 Tolerance

Take the arithmetic mean of the parallel determination results as the determination result. When the hardness is greater than 1mmol/L, the absolute difference between the two parallel determination results is not greater than 0.05mmol/L. When the hardness is less than or equal to 1mmol/L, the absolute difference between the two parallel determination results shall not be greater than 0.005mmol/L.

4.2 Acid chrome blue K method

4.2.1 Method summary

In an aqueous solution with a pH of about 10, acid chrome blue K is used as an indicator.

Titrate with ethylenediaminetetraacetic acid disodium salt (EDTA) standard titration solution to blue as the end point. Calculate the hardness value according to the volume of EDTA consumed.

When the content of iron, aluminum, copper and manganese in the water sample reaches a certain concentration, there will be interference to the determination. L- cysteine hydrochloride and triethanolamine can be added to jointly mask and eliminate the interference.

4.2.2 Reagents or materials

4.2.2.1 Water: GB/T 6682, grade one.

4.2.2.2 Borax buffer solution: Weigh 40g of borax (Na2B4O7·10H2O). Add 10g of sodium hydroxide. Dissolve in water and dilute to 1L. Store in plastic bottles.

4.2.2.3 Disodium ethylenediaminetetraacetic acid standard titration solution: c(EDTA) is about 0.005mol/L. Same as 4.1.2.7.

4.2.2.4 Acid chrome blue K indicator solution: 5g/L. Weigh 0.5g of acid chrome blue K (C16H9O12N2S3Na3) and 4.5g of hydroxylamine hydrochloride. Grind well in a mortar. Add 10mL of borax buffer solution. Dissolve in 40mL of water. Use 95% ethanol to dilute to 100mL. Store in brown bottles for later use. The storage time is one month. result. The absolute difference between the two parallel determination results is not more than 1.0µmol/L.

5 Potentiometric titration method

5.1 Method summary

Use automatic potentiometric titrator and calcium electrode to measure. Use disodium ethylenediaminetetraacetic acid (EDTA) standard titration solution to titrate calcium and magnesium ions. When the titration reaches a complete jump curve, the instrument automatically recognizes the stoichiometric point (that is, the jump point). Hardness is calculated from the volume of standard titration solution consumed at the jump point.

When the content of copper and manganese in the water sample reaches a certain concentration, there will be interference to the determination. L-cysteine hydrochloride and triethanolamine can be added to jointly mask and eliminate the interference.

5.2 Reagents or materials

5.2.1 Disodium ethylenediaminetetraacetic acid standard titration solution: c(EDTA) is about 0.05mol/L. When the hardness of the water sample is less than 1mmol/L, the standard titration solution of c(EDTA) 0.005mol/L is used.

5.2.2 Other reagents are the same as 4.1.2

5.3 Instruments and equipment

5.3.1 Automatic potentiometric titrator.

5.3.2 Calcium ion electrode.

5.4 Test steps

5.4.1 Take an appropriate amount of water sample in the measuring cup. If the water sample is turbid, it shall be filtered with medium-speed quantitative filter paper before sampling. Add 5mL of ammonia-ammonium chloride buffer solution. When the water sample is highly acidic or alkaline, it can be neutralized with sodium hydroxide solution or hydrochloric acid solution. It is then added with buffer solution. When the copper and manganese in the water sample are greater than 0.2mg/L, it will interfere with the determination. Before the determination, 2mL of L-cysteine hydrochloride solution and 2mL of triethanolamine solution can be used for joint masking to eliminate the interference.

5.4.2 Place the measuring cup on the titration stand. Insert the calcium ion electrode.

Turn on the instrument and the stirrer. Use disodium edetate standard titration solution to titrate. Stop the titration when the titration reaches a complete jump curve.

Annex A (normative) Adjustment of ammonia-ammonium chloride buffer solution

A.1 Method summary

Use chrome black T as indicator. To improve the sensitivity of endpoint indication, a certain amount of ethylenediaminetetraacetic acid (EDTA) disodium magnesium salt shall be added to the buffer solution. To avoid the unequal amount of EDTA and magnesium ions, and the hardness substances in the ammonia water used in the preparation, it is necessary to adjust the ammonia-ammonium chloride buffer solution after preparation, so as to avoid the hardness in the buffer solution or excessive EDTA, which will bring errors to the determination results.

A.2 Reagents or materials

A.2.1 Magnesium standard solution: 0.010mol/L. Weigh 0.6159g of magnesium sulfate heptahydrate (excellent pure). Dissolve it in water. Transfer it to a 250mL volumetric flask. Dilute to the scale mark. Shake well. Or use commercially available magnesium (Mg2+) standard solution to accurately dilute.

A.2.2 Disodium ethylenediaminetetraacetic acid standard titration solution: c(EDTA) is about 0.01mol/L.

A.2.3 Other reagents: Same as 4.1.2.

A.3 Test steps

A.3.1 Use a pipette to measure 10.00mL of the prepared ammonia-ammonium chloride buffer solution in the Erlenmeyer flask. Add 90mL of water. Add two to three drops of chrome black T indicator solution.

A.3.2 After adding the indicator solution, if the solution turns red, it indicates that there are hardness substances in the buffer solution. Use disodium edetate standard titration solution to titrate until it changes from red to pure blue. Then according to the consumption of disodium edetate standard titration solution and the amount of buffer solution to be adjusted, calculate the volume of disodium edetate standard titration solution to be added (for example, prepare 1000mL of buffer solution. 0.10mL of standard titration solution of disodium edetate is consumed during the test, then 9.90mL of the EDTA disodium standard titration solution needs to be added to the remaining 990mL of buffer solution).

A.3.3 After adding the indicator solution, if the solution turns blue, there may be two […]

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.

Referenced standards

Editions of GB/T 6909

EditionTitleRevisionStatus
GB/T 6909-2018Analysis of water used in boiler and cooling system—Determination of hardnesscurrent editionCurrent
GB/T 6909-2008Analysis of water used in boiler and cooling system—Determination of hardnessprevious editionSuperseded

This page sells the current edition, GB/T 6909-2018. Earlier editions are listed for reference only.

How to Download GB/T 6909-2018

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
15 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 6909-2018

$145.00