GB/T 31142-2014Directives for selection and application of transfer switching equipment (English PDF)
转换开关电器(TSE)选择和使用导则
This is a limited preview
Buy now to download the full PDF (34 pages)
Need quotation for your management?
Get a formal quotation for GB/T 31142-2014 in 30 minutes.
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
September 3, 2014
Implementation date
April 1, 2015
Scope
GB/T 31142-2014 is the English-translated version of 转换开关电器(TSE)选择和使用导则.
GB/T 31142-2014 is the Chinese standard "Directives for selection and application of transfer switching equipment".
Its scope clause reads: This Standard specifies the product properties, technical parameters and structural types that should be paid attention to during the selection and application of transfer switching equipment (TSE), and the environmental conditions in use.
This Standard is applicable to the selection and application of the TSE with a nominal voltage of no more than AC 1,000V (1) or DC 1,500V. TSE is used in the transfer between two power supplies, so as to guarantee the continuous power supply to the loads.
During TSE transfer, it is allowed to conduct momentary interruption (2) to provide loads with power supply. TSE can also be used in the transfer between loads.
Its clauses include terms and definitions; symbols and abbreviations; service conditions of tse; requirements for atse's controller.
Found what you need?
Document preview — GB/T 31142-2014
National Standard of the People's Republic of China
- ICS
- 29.130.20
- Classification
- K 31
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- Foreword4
- Introduction5
- 1 Scope6
- 2 Normative references6
- 3 Terms and definitions7
- 4 Symbols and abbreviations15
- 5 Classification16
- 6 Major characteristics of TSE18
- 7 Service conditions of TSE23
- 8 Directives for selection and application of TSE25
- 9 Requirements for ATSE's controller37
- 10 Application of the TSE as load transfer41
- examples42
- supply system47
- Appendix C (Informative) Examples of the emergency load57
- environments on the transfer controllers59
- Appendix E (Informative) List of communication parameters62
- GB/T 14048.1163
- References67
1 Scope
This Standard specifies the product properties, technical parameters and structural types that should be paid attention to during the selection and application of transfer switching equipment (TSE), and the environmental conditions in use.
This Standard is applicable to the selection and application of the TSE with a nominal voltage of no more than AC 1,000V
(1) or DC 1,500V.
TSE is used in the transfer between two power supplies, so as to guarantee the continuous power supply to the loads. During TSE transfer, it is allowed to conduct momentary interruption
(2) to provide loads with power supply.
TSE can also be used in the transfer between loads.
2 Normative references
The following documents are essential to the application of this document. For dated references, only the editions with the dates indicated are applicable to this document. For undated references, only the latest editions (including all the amendments) are applicable to this document.
GB/T 2423.4-2008 Environmental testing for electric and electronic products
- Part 2: Test method - Test Db: Damp heat, cyclic ( 12h + 12h cycle) (IEC 60068-2-30:2005, IDT)
GB 10963.1-2005 Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installation - Part 1: Circuit-breakers for a.c. operation (IEC 60898-1:2002, IDT)
GB 14048.1-2012 Low-voltage switchgear and controlgear - Part 1: General rules (IEC 60947-1:2011, MOD)
(1)
The electrical appliances with the nominal voltage of AC 1,140V can refer to the implementation of this
Standard. The property requirements related to the electrical appliances shall be determined after consultation between manufacturer and user.
(2)
Except the closed transfer TSE.
GB 14048.3-2008 Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units (IEC 60947-3:2005, IDT)
GB 14048.4-2010 Low-voltage switchgear and controlgear - Part 4-1:
Contactors and motor-starters - Electromechanical contactors and motor- starters (including motor protector) (IEC 60947-4-1:2009 Ed.3.0, MOD)
GB/T 14048.11-2008 Low-voltage switchgear and controlgear - Part 6-1:
Multiple function equipment - Transfer switching equipment (IEC 60947-6-
1:2005, MOD)
GB/T 17626.13-2006 Electromagnetic compatibility (EMC) - Testing and measurement techniques - Harmonics and interharmonics including mains signalling at a.c. power port, low frequency immunity test (IEC 61000-4-
13:2002, IDT)
GB/T 20645 Specific environmental condition - Technical requirements of low-voltage apparatuses for plateau
GB/T 21208-2007 Low-voltage switchgear and controlgear - Controllers for drivers of stationary fire pumps (IEC/TS 62091:2003, MOD)
GB 50174-2008 Code for design of electronic information system room
3 Terms and definitions
The following terms and definitions are applicable to this document.
3.1 Electrical supply system
3.1.1 Electrical supply system
The electrical supply system includes the power supply and the electrical circuits connected to the terminals for electrical equipment.
Note: It is allowed to refer to IEC 60364-5-56:2009.
3.1.2
Electrical supply system for safety services (emergency electrical supply system)
It refers to the electrical supply system used for maintaining the key component operation of the electrical equipment and installations, which is mainly:
- for the health and safety of human bodies or livestock; and/or […]
3.2.1 Transfer switching equipment; TSE
It refers to the electrical equipment composed of one or more pieces of switching equipment, which is used for breaking the load circuit from one power supply and connecting to another power supply afterwards.
3.2.2 Specific TSE
It refers to the integral TSE whose main part of the electrical appliance is specially designed for power supply transfer according to the requirements of
3.2.3 Derived TSE
It refers to the TSE whose main part of the electrical appliance meets the requirements of other product standards in GB 14048, for instance, TSE composed of two circuit-breakers or two switch-disconnectors or two contactors.
3.2.4 Manually operated transfer switching equipment; MTSE
It refers to the transfer switching equipment operated manually.
3.2.5 Remotely operated transfer switching equipment; RTSE
It refers to the transfer switching equipment operated remotely.
Note: RTSE can have the characteristic of manual operation.
3.2.6 Automatic transfer switching equipment; ATSE
It refers to the transfer switching equipment operated automatically.
Note: ATSE generally includes main part and controller.
3.2.7 Main part
It refers to the switching equipment used for transferring the load power supply in the main circuit, which is divided into specific main part and derived main part.
3.2.8 Controller
It refers to the electrical equipment that is used for detecting and monitoring the power supply status, and is able to automatically issue an action command to transfer the main part to the side of normal operating power supply when the power supply deviates from the configured normal status.
3.3 The main contact position of TSE
3.7.4 Electromagnetic compatibility; EMC
It refers to the capacity that the electrical equipment or system can work properly in its electromagnetic environment without constituting an unbearable electromagnetic disturbance to any matters in this environment.
Note: The electromagnetic environment can be divided into environments A and B.
Environment A: It is related to the sites/buildings in the low-voltage non-public power grid or industrial power grid, including the sites with higher disturbance source;
Environment B: It is related to the low-voltage public power grid, such as civil, commercial and light industrial sites/buildings and/or corresponding application environments, excluding the sites with higher disturbance source, such as arc welding machine.
4 Symbols and abbreviations
The following symbols and abbreviations are applicable to this document.
EMC Electromagnetic compatibility
I cm Rated short-circuit making capacity
I cs Rated service short-circuit breaking capacity
I cw Rated short-time withstand current
I e Rated working current
I p Maximum prospective peak current […]
6.2 Type of the electrical equipment
The following items shall be stipulated:
- level of the electrical equipment and transfer control mode: PC level or
CB level; ATSE or MTSE;
- number of poles;
- current category; and
- operating procedures and range.
The operating procedures are as follows:
a) Operations during the supply voltage loss
ATSE shall transfer the loads from common power supply to standby power supply within the scheduled time after the voltage interruption at any phase or all the phases to be monitored of the common power supply;
b) Operations during the under-voltage power supply
If ATSE is equipped with the device that can transfer the loads from common power supply to standby power supply when the main power supply's voltage decreases, the transfer shall be started within the specified voltage range;
c) Transfer based on the availability of the standby power supply voltage
If ATSE is equipped with the voltage monitoring circuit used for determining the availability of the standby power supply, TRANSFER within the specified range;
d) Transfer based on the availability of the voltage and frequency of the standby power supply
If ATSE is equipped with the voltage and frequency monitoring circuits used for determining the availability of the standby power supply, TRANSFER within the specified range;
7 Service conditions of TSE
7.1 Normal service conditions
7.1.1 Ambient air temperature
Normal ambient air temperature shall not be greater than +40°C. The lower limit shall be -5°C. The average temperature within 24h shall not be greater than
+35°C.
7.1.2 Altitude
The altitude of the installation location shall not be greater than 2,000m.
Note: When the clearance and creepage distance of the electronic equipment's terminal fail to conform to the provisions in Tables 13 and 15 of GB 14048.1-2012, VERIFY the dielectric property. In general, when the altitude of the ATSE controller's installation location exceeds 1,000m, it is suitable to take appropriate measures to satisfy the dielectric property of the adaptive altitude.
7.1.3 Installation environmental conditions
7.1.3.1 Humidity
When the highest temperature is +40°C, the relative humidity of the air shall not be greater than 50%. Higher relative humidity is allowable at lower temperature, for instance, the relative humidity can be up to 90% at 20°C.
Under normal environmental conditions, TSE shall have the ability of adapting to the humid environment.
Under this humidity condition, CONDUCT the cyclic damp heat test (Db) according to the requirements of GB/T 2423.4-2008 for detecting TSE's moisture resistance. The harsh classification of the test is generally as follows:
The high temperature is 40°C. The test cycle is 6 days and nights.
When installed and used in a humid basement or in the environment where there is water dripping from the pipelines with condensation on the top, TSE shall be installed in the cabinet whose degree of protection provided by enclosure is not less than IP31.
7.1.3.2 Pollution degree
Unless otherwise specified, industrial TSE shall be able to adapt to the environments of no less than the pollution degree 3.
8.1.5
The isolated electrical equipment is used for disconnecting the electrical
equipment and other switching equipment with power supplies during the circuit maintenance, so as to realize the safe maintenance of the electrical equipment or other switching equipment. The installation locations thereof shall conform to the provisions of relevant design codes. If using TSE as isolated electrical equipment as well, TSE's properties shall conform to the requirements of
Section 6.6.
TSE's overhaul and maintenance shall be taken into consideration. It is allowed to add isolated electrical equipment in the front of TSE. For the drawer-type
TSE with isolation function, it is unnecessary to provide additional isolated electrical equipment in the front of TSE.
8.2 TSE selection in accordance with the electrical supply system
8.2.1 Electrical supply system for safety services
Safety services involve personal and property safety. Therefore, electrical supply system for safety services shall provide automatic electrical supply. For instance, SELECT PC level ATSE.
8.2.2 Standby electrical supply system
In general, non-safety services will not cause secondary disasters to the off- time. Therefore, standby electrical supply system can provide either automatic electrical supply or non-automatic electrical supply. For instance, it is allowed to select ATSE or MTSE.
Note: For the ATSE used in standby electrical supply system, it is allowed to adopt the ATSE of B utilization category.
8.3 TSE selection in accordance with the installation location
8.3.1 TSE selection at the power location
TSE can be installed at different locations in the circuit system as required by the project (SEE Section 3.7.2). When TSE is at different installation locations, the requirements for its properties are different as well. For the TSE at the power location:
a) It is suitable to select three-position TSE.
b) TSE's overvoltage category shall be Class IV.
c) TSE's utilization category shall not be lower than AC-32 or DC-33.
d) TSE shall be convenient for maintenance.
e) Precautions during the selection of PC level TSE:
PC level TSE is mainly used for power transfer. When the circuit shorts out, it shall have the capacity of switching on and withstanding instead of breaking the short-circuit current. Therefore, short-circuit protective devices (SCPDs) shall be installed in front of the PC level TSE. PAY attention to the following issues during the selection of PC level TSE:
1) TSE's short-time withstand current (Icw) shall be greater than or equal to the circuit's prospective short-circuit current. The power-on time shall be greater than the short-time delay (such as frame-type circuit-breaker) or fusing time (such as fuse) of the protective device in the circuit.
2) When the manufacturer only gives the value of TSE's rated conditional short-circuit current (Iq), PAY attention to the type of the short-circuit protective device (SCPD) - circuit-breaker or fuse, and SCPD's model, rated values and characteristics. The selected short-circuit protective device in the circuit shall have consistent model or properties with the
SCPD assigned by the manufacturer. The rated conditional short-circuit current (I q) thereof shall be greater than or equal to the circuit's prospective short-circuit current. As long as TSE's let-through I
2 t is greater than SCPD's I
2 t, it is allowed to conduct SCPD exchange.
Note: During the transfer of PC level ATSE, it is likely to switch on the short-circuit current. This circuit shall be able to resist the short-circuit current impulses again. For the emergency electrical supply system, GIVE preference to PC level ATSE.
f) Precautions during the selection of CB level TSE:
CB level TSE is generally derived from circuit-breakers. When the circuits suffer from short circuit, overload and ground fault, the circuit-breakers shall be able to break the circuits for circuit and load protection. PAY attention to the following issues during the selection of CB level TSE:
1) TSE's rated service short-circuit breaking capacity (I cs) shall be greater than or equal to the circuit's prospective short-circuit current.
2) Short-time withstand current (I cw) shall be greater than or equal to the circuit's prospective short-circuit current.
3) During the selection of CB level ATSE, PAY attention to give consideration to both protective and transfer characteristics.
8.5.3 Utilization in coordination with the UPS
According to the provisions of GB 50174-2008, when UPS's two power supplies are mains supply and diesel generator, USE the transfer switching equipment with bypass function for the switchover between two power supplies. During the
ATSE maintenance, the switchover between two power supplies shall not be affected.
8.6 TSE selection in accordance with special functions
8.6.1 Bypass TSE
According to the requirements of the electrical supply systems or loads, it is allowed to select the TSE with special functions.
For the important loads with higher requirements for continuous and reliable electrical supply, SELECT the bypass TSE. When ATSE is disconnected with the circuit due to overhauls or faults, MTSE can continue to accomplish the transfer among the power supplies.
Bypass TSE has the following basic functions:
a) MTSE (bypass switch) shall be able to be connected in parallel with the ATSE.
Bypass power supplies shall be connected in parallel with the loads. The rated capacities of MTSE and ATSE shall be the same.
b) When ATSE is disconnected with the circuit, corresponding control circuit shall be safely isolated from the power supply, so as to ensure the personal safety during the ATSE maintenance and replacement.
c) MTSE and ATSE shall have working status indicating device, so as to clearly express the working status of the system.
d) Electrical and mechanical interlocking shall be installed between ATSE and
MTSE, so as to prevent the misoperation.
8.6.2 Instantaneous parallel TSE
TSE shall have two groups of moving contacts. Under certain conditions (such as same voltage, same frequency and same phase angle), the contacts operate according to the sequence of making first and breaking afterwards. CONDUCT instantaneous parallel to two power supplies, so as to transfer the important loads from one power supply to another without power outage.
8.8.2
ATSE shall conduct the test operating transfer for a few times (such as
3 to 5 times) periodically (such as within 3 months) under no-load condition, so as to ensure ATSE's normal operation in emergency state.
9 Requirements for ATSE's controller
9.1 Reliable operating capacity of the controller
ATSE's controller is the critical electrical equipment for ATSE's reliable operation. In order to ensure ATSE's reliable operation, the following requirements for its reliable operating capacity are put forward:
a) ATSE's controller operates continuously (24h working system).
b) The rated working voltage of the controller shall be consistent with that of the main circuit. The normal operating range shall be 85%Ue to 110%Ue. 85%Ue is lower limit. 110%Ue is upper limit.
Note 1: For the TNS and TT grounding systems, the controller's rated working voltage shall adopt the phase voltage (for instance, AC 230V for the power location / 220V for the load location); for the
TNC and IT grounding systems, the controller's rated working voltage shall adopt the linear voltage (for instance, AC 400V for the power location / 380V for the load location), or TAKE other measures to lead the neutral conductor to the ATSE.
Note 2: The manufacturer is allowed to stipulate larger operating range.
c) TAKE effective isolating measures between strong and weak current of the controllers.
d) The anti-electromagnetic interference capacity of the controllers shall conform to the requirements specified in GB 14048.1-2012. The supplements are as follows:
1) The resistance to electrical fast transient bursts shall:
- ATSE at the power or distribution location: The test level of the power supplies is 4kV / 5kHz; the test level of the signals, I/O, data and control ports is 2kV / 5kHz.
- ATSE at the load location: The test level of the power supplies is 2kV /
5kHz; the test level of the signals, I/O, data and control ports is 1kV /
5kHz.
2) The resistance to harmonic interference shall conform to the requirements for the test level 3 in GB/T 17626.13-2006.
B.2 Selection of the generating units for the emergency power supply
B.2.1 General conditions
When using the generating units as emergency power supply, it is necessary to be clear about the following basic issues:
- capacity (loads to be withstood);
- fuels of the units; and
- installation of the units.
B.2.2 Capacity of the units
The capacity of the generating units is relevant to the loads to be connected.
BE clear about the properties and power of the loads requiring electrical supply as well as the electrical supply sequence. CALCULATE the capacity of the generating units afterwards.
The application of the generating units has impacts on the capacity calculation.
The rated values of the generating units are determined based on the working system of the unit operation. For the application with a relatively stable mains supply, where the generating units are only used in the emergency power supply, BE clear about the rated values in standby mode.
B.2.3 Fuels of the units
The fuels used by the generating units have direct impacts on the equipment selection and application, which might affect the reliability of the entire equipment's operation.
In order to obtain the highest reliability, generally SELECT diesel generating units in the emergency situations. Diesel generating units can provide the highest reliability. Since diesel generating units use specific fuel supply, this fuel supply does not rely on external fuel supply system. For instance, natural gas generating units are required to have external fuel supply system.
During the fuel selection, other items that shall also be paid attention to include:
a) When diesel generating units are used in cold environments, USE the fuels applicable to the winter so as to prevent the fuel system from being restricted, and thus to restrict the power output of the generating units. Therefore,
MAINTAIN the ambient temperature at 0°C at least or above. USE casing water heaters to maintain the operation. ENSURE that the generating units start up within 10s.
b) Diesel fuel decomposes as time goes by. Therefore, SELECT the diesel engine case with appropriate capacity.
c) If providing an on-site energy supply system (such as liquid propane) as standby fuel source, natural gas generating units can be selected as emergency power supply.
d) Compared with diesel generating units, natural gas generating units' control property to the frequency is relatively poor. Natural gas generating units are not applicable to the loads that are sensitive to the working frequency.
e) Diesel or natural gas generating units shall conform to the requirements of relevant national exhaust emission standards.
f) Due to the volatility of the gasoline and short storage life of the fuels, gasoline is not applicable to be used as the fuels of the emergency generating units.
B.2.4 Installation of the units
B.2.4.1 General requirements for the installation location
The selection of the installation locations of the generating units will have very important impacts on the reliability and installation costs of the units. In general, outdoor installation costs are lower. However, since the indoor installation can better control the ambient temperature and security of the indoor installation, the reliability of the outdoor installation is relatively low compared with that of the indoor installation. The general requirements for the installation location are as follows:
a) The design of all systems shall consider the impacts of the generating units' noise on the surrounding area.
b) In general, the locations of the electrical distribution equipment and automatic transfer switching equipment shall come close to the connected loads as far as possible. The selection of the generating units shall be in coordination with the emergency system.
c) For the accessories of the generating units, including the coolant heaters, battery chargers, etc., PROVIDE branch circuits.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 34 pages — is available in the English PDF.
Similar standards
How to Download GB/T 31142-2014
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Fast delivery
After payment you'll receive an email confirmation. The English PDF is sent to the same address, usually within minutes and at the latest within 1 business day.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 10003-2026 — Biaxially oriented polypropylene (BOPP) film
GB/T 10004-2026 — Plastic/Plastic laminated films and pouches for packaging
GB/T 10007-2026 — Rigid cellular plastics - Determination of shear properties
GB/T 31142-2014
$125.00