GB/T 29416-2026Test method for the fire performance of external wall insulation systems applied to building facades (English PDF)
建筑外墙外保温系统的防火性能试验方法
Open the GB/T 29416-2026 preview as PDF
This is a limited preview
Buy now to download the full PDF (24 pages)
Issued by
SAMR; SAC
Level / Type
National · Recommended
Issue date
March 31, 2026
Implementation date
October 1, 2026
Scope
GB/T 29416-2026 is the English-translated version of 建筑外墙外保温系统的防火性能试验方法.
GB/T 29416-2026 is the Chinese national standard covering the large-scale facade fire test - a full external wall insulation system built on a test rig with a fire in the opening below it, which is the only way to know whether a system will carry a fire up the outside of a building. It replaces GB/T 29416-2012 and has been in force since 1 October 2026. It was issued on 31 March 2026 and takes effect on 1 October 2026, replacing GB/T 29416-2012. The document is under the responsibility of the National Fire and Rescue Administration. This page is published from the official record of the 2026 edition; the clause text of a standard this recent is not yet in circulation, and the figures, limits and tables it contains are those of the document itself, delivered in full with the English translation.
Document preview — GB/T 29416-2026
National Standard of the People's Republic of China
- ICS
- 13.220.50
- Classification
- C 82
- Replacing
- GB/T 29416-2012
Issued by: State Administration for Market Regulation; Standardization Administration of the PRC
Contents
- 1 Scope
- 4 Test Apparatus
- 4.6 Measurement System
- 4.6.2 Thermocouples
- 4.6.2.3 Internal thermocouples on horizontal alignment lines 2 and
- 5 Samples
- 5.2 Sample Dimensions and Installation
- 7 Test Procedure
- 7.4 Experimental Observation and Recording
Foreword
This document complies with the provisions of GB/T 1.1-2020 "Standardization Work Guidelines Part
1.Structure and Drafting Rules of Standardization Documents". Drafting. This document replaces GB/T 29416-2012 "Test Methods for Fire Resistance Performance of External Thermal Insulation Systems for Buildings", and is consistent with GB/T 29416- Compared to.2012, aside from structural adjustments and editorial changes, the main technical changes are as follows:
a) The term "horizontal alignment 3" and its definition have been added (see 3.4);
b) The term "collapsed area" and its definition have been added (see 3.8);
c) Increased requirements for the height of the indoor space for the construction of the test facility (see 4.1);
d) The heights of the main and secondary walls in the test setup were changed (see 4.2,.2012 edition of 4.2);
e) The distance between the combustion chamber opening and the sub-wall has been changed (see 4.3,.2012 edition of 4.3);
f) The requirements for the combustion heat source have been changed (see
4.4 and Annex A, 4.4, Annex A and Annex B of the.2012 edition);
g) The installation position of the thermocouple at horizontal level line 3 and the requirements for recording the thermocouple temperature at horizontal level line 3 have been added (see 4.6.2). 7.4.2);
h) The time interval for recording data in the data acquisition system has been changed (see 4.6.3,.2012 version 4.6.3);
i) The measurement accuracy of the wind speed measuring equipment has been changed (see 4.6.5,
4.6.6 in the.2012 version);
j) The requirement for the total thickness of the specimen has been removed (see
1 Scope
GB/T 29416-2026 is the Chinese national standard covering the large-scale facade fire test - a full external wall insulation system built on a test rig with a fire in the opening below it, which is the only way to know whether a system will carry a fire up the outside of a building. It replaces GB/T 29416-2012 and has been in force since 1 October 2026. It was issued on 31 March 2026 and takes effect on 1 October 2026, replacing GB/T 29416-2012. The document is under the responsibility of the National Fire and Rescue Administration. This page is published from the official record of the 2026 edition; the clause text of a standard this recent is not yet in circulation, and the figures, limits and tables it contains are those of the document itself, delivered in full with the English translation.
This document describes the test method for the fire resistance performance of building exterior wall insulation systems, and provides the test apparatus, specimens, conditioning procedures, and test process. The test includes an introduction, post-test inspection, test result determination, and test report. This document applies to fire performance testing of non-load-bearing external insulation systems installed on building exterior walls. This document does not apply to fire performance testing of breathable glass curtain wall external insulation systems installed on building exteriors.
4 Test Apparatus
4.1 General Requirements A fire performance testing device for external thermal insulation systems should generally consist of a base wall, a combustion chamber, a heat source, a collapse zone, and a measurement system. composition. The testing apparatus should be constructed in a building with sufficient space, the size of which should be adequate for the construction of the testing apparatus and the installation of the test specimens. Due to the needs of construction, testing operations, and testing safety requirements, the clearance height should not be less than 18m, and it should also be able to ensure the safe use of heat sources and samples during the test. Free combustion (experimental behavior was controlled by fuel, not ventilation). The testing apparatus should be durable and should not be deformed or damaged during the test, thus affecting the test results.
4.2 Base Wall The base wall of the experimental device consists of a main wall and a secondary wall, using autoclaved aerated concrete blocks with a dry density of not less than 600 kg/m^3. Straight masonry construction. The height of both the main wall and secondary walls shall not be less than 9700mm, and the thickness shall not be less than 300mm. The width of the main wall shall not be less than 2600mm, and the secondary wall... The wall width shall not be less than 1500mm, as shown in Figures 1a) and 1b). The main wall and the secondary wall form a 90° angle, as shown in Figure 1c).
4.3 Combustion Chamber The combustion chamber of the test apparatus is located at the bottom of the main wall, with its outer edge flush with the main wall surface. The opening size should be. height (2000±100) mm. Width (2000±100) mm. Internal dimensions. Height (2300±50) mm, Width (2000±50) mm, Depth (1000±50) mm. Combustion chamber opening. The distance from the opening to the outer surface of the external insulation system sample of the secondary wall should be (160~360) mm. The upper part of the opening should be protected with fire-resistant material.
4.4 Heat Source The heat source used in the test should be a wood stack heat source that conforms to the specifications in Appendix A.
4.5 Collapse Area The collapsed area of the test apparatus should be marked on the ground of the test apparatus (see Figure 2). The unit is millimeters.
4.6 Measurement System
4.6.1 Overview The measurement system consists of thermocouples, a data acquisition system, a camera, wind speed measuring equipment, and a timing device.
4.6.2 Thermocouples
4.6.2.1 General Provisions The thermocouple should be a type K armored thermocouple with an outer cable diameter D of (1.5±0.025) mm, conforming to GB/T 18404, for temperature measurement. The temperature range is (0~1000)°C, and the tolerance level is Class II. Thermocouples installed on the test apparatus are divided into external thermocouples and internal thermocouples. External thermocouples should be installed on horizontal alignment lines 1, 2, and
3.The measuring points of the external thermocouples should extend (50±5) mm beyond the outer surface of the external insulation system. The allowable deviation for the temperature measurement point location is ±10mm. Internal thermocouples should be installed on horizontal alignment lines 2 and
3.The temperature measuring points of the internal thermocouples should be arranged at the midpoint of the thickness of each structural layer of the insulation layer. At the core. When the insulation layer thickness is less than 10mm, thermocouples are not required. If the system contains cavities, the temperature measuring points of the internal thermocouples should be... They are positioned at the center of each cavity thickness. The allowable deviation for the temperature measurement point position is ±10mm.
4.6.2.2 External thermocouples on horizontal level line 1, horizontal level line 2, and horizontal level line
3 The installation method of the external thermocouples on horizontal level line 1, horizontal level line 2, and horizontal level line 3 is as follows:
---On the front of the main wall, thermocouples are installed on the vertical centerline of the combustion chamber opening and 500mm and 1000mm to each side of the centerline. Five temperature measuring points are set on each of the horizontal alignment lines 1, 2, and 3 (see Figure 1a);
---On the front of the secondary wall, thermocouples are installed at positions 150mm, 600mm, and 1050mm from the outer surface of the main wall's external insulation system. Three temperature measurement points are set on each of the horizontal alignment lines 1, 2, and 3 (see Figure 1b).
4.6.2.3 Internal thermocouples on horizontal alignment lines 2 and
3 The installation method of the internal thermocouples on horizontal alignment lines 2 and 3 is as follows:
---Within the main wall external insulation system, thermocouples should be installed on the vertical centerline of the combustion chamber opening and 500mm on each side of the centerline. At a position of 1000mm, five temperature measuring points are set on each of the horizontal alignment lines 2 and 3 (see Figure 1a).
---Inside the secondary wall external insulation system, thermocouples are installed at distances of 150mm, 600mm, and 1050mm from the outer surface of the main wall external insulation system. At the position, three temperature measuring points are set on each of the horizontal alignment lines 2 and 3 [see Figure 1b].
4.6.3 Data Acquisition System The data acquisition system should record data at intervals no greater than 3 seconds.
4.6.4 Camera Two cameras with a continuous recording time of no less than 90 minutes were used to continuously record the entire experiment. The camera angles should cover the entire experiment. The overall height of the two walls of the test device should be determined. HD mode with a resolution of at least 1920×1080 is recommended for video recording.
4.6.5 Wind speed measurement equipment Wind speed can be measured using equipment such as an anemometers, with a measurement accuracy of not less than ±
0.1 m/s.
4.6.6 Timing device The measurement accuracy of the timing device shall not be less than 0.1s.
5 Samples
5.1 General Requirements The test specimens should include all components of the external insulation system, and their structure and thickness should fully reflect the actual engineering application, and should be in accordance with... The installation was carried out in accordance with the design requirements provided by the client who commissioned the test.
5.2 Sample Dimensions and Installation
5.2.1 Before sample installation, the base wall of the test apparatus shall be treated in accordance with the provisions of
4.2 or the design requirements provided by the client. Base It should be flat, clean, and free of oil, release agents, or other substances that may hinder adhesion.
5.2.2 The installation of the specimen should not obstruct the combustion chamber opening.
5.2.3 On the main wall of the test apparatus, the specimen installation width should not be less than 2400mm, with one side close to the specimen surface on the secondary wall; the installation height should be greater than... The specimen is positioned 7700 mm above the top of the combustion chamber opening. The specimen can be extended downwards to the ground on either side of the combustion chamber opening.
5.2.4 On the secondary wall of the test apparatus, the specimen installation width should not be less than 1200mm, with one side close to the specimen surface on the main wall; the installation height should be the same as... The samples on the main wall were installed at the same height.
5.2.5 At the corner where the main wall and the secondary wall meet, the test specimens shall be prepared according to the actual construction of the external insulation system or as required by the testing client. Install.
5.2.6 The edges of the specimen around the combustion chamber opening shall be protected in accordance with the actual application structure of the external insulation system or the requirements of the test commissioning party. When the external insulation system is constructed without any opening protection measures in practical applications, the edges of the sample around the combustion chamber opening should remain uniform. Unprotected state.
5.2.7 When the external insulation system includes horizontal structural joints in actual application, the structural joints shall be constructed in accordance with the actual requirements specified by the testing commissioning party. The joints should be spaced out, and at least one horizontal structural joint should be provided at (2400±50) mm above the combustion chamber opening.
5.2.8 When the external insulation system includes vertical structural joints in actual application, the structural joints shall be constructed in accordance with the actual requirements specified by the testing commissioning party. The design should be spaced out, and a vertical structural seam should be provided extending upwards from the centerline of the combustion chamber opening, with its position relative to the centerline. The allowable deviation is ±100mm.
5.2.9 When the external insulation system is designed with fire-resistant barriers in practical applications, the fire-resistant barriers on the test specimens shall meet the requirements of the testing client. The distance between the two isolation strips should reflect the actual installation situation.
5.2.10 When the external insulation system is constructed with a keel in practical applications, the installation position of the keel should avoid the horizontal alignment line 1 and the horizontal alignment line 2. The distance between the upper edge of line 2 and horizontal alignment line 3 and horizontal alignment line 1, horizontal alignment line 2 and horizontal alignment line 3 should not be less than 100mm.
5.3 Basic performance characteristics of the specimen Before conducting fire resistance tests according to this document, the basic performance characteristics of the specimens shall be determined in accordance with the following provisions.
a) Test the combustion performance of the specimens according to GB 8624;
b) Test the apparent density of the insulation material used in the test specimens according to GB/T 6343;
7 Test Procedure
7.1 Environmental Conditions The ambient temperature at the start of the test should be within the range of (20±15)°C, and the air velocity at the horizontal level 2 of the test apparatus should not exceed [a certain value]. 2m/s.
7.2 Data Acquisition Data acquisition and video recording should be performed for no less than 5 minutes before ignition of the heat source. If any horizontal alignment line or any level is not observed before ignition... If a thermocouple with two or more temperature measuring points shows abnormal data, the test should be stopped. Measure and record the external heat at ignition level 1. The temperature of the thermocouple is taken as the average temperature, which is the initial temperature (T0).
7.3 Ignite the heat source Five minutes after the start of data acquisition, the heat source of the wood stack was ignited in accordance with the provisions of Appendix A.
7.4 Experimental Observation and Recording
7.4.1 After the heat source is ignited, the temperature of the external thermocouples on horizontal level line 1 should be measured and recorded. When the recorded temperature of any thermocouple is higher than the specified value, the temperature of the thermocouples should be recorded. The time when the initial temperature (T0) is.200°C and the duration reaches 30s is the start time of the experiment (ts).
7.4.2 During the test, the time when the combustion state of the sample and the stability of the system change should be observed and recorded. Combustion states include.
a) Complete combustion;
b) Continuously visible flame condition;
c) External flame spread, i.e., the temperature of any external thermocouple on horizontal level line 1, horizontal level line 2, or horizontal level line 3;
d) The internal flame propagation status, i.e., the temperature of any internal thermocouple on horizontal level line 2 and horizontal level line 3;
e) Condition of burning debris. System stability includes the occurrence of phenomena such as damage, peeling, and collapse of the entire or part of the sample, and the time it takes for these phenomena to occur.
7.5 Test Time The test duration should be 60 minutes. The heat source typically burns out within 30 minutes.
7.6 Early termination of the experiment The test should be terminated under the following conditions.
a) Safety risks to personnel and equipment arise;
b) The flame height of the external insulation system sample reached the horizontal level line 3, and the flame height lasted for 10 seconds.
8.Post-test inspection Within 24 hours after the test, while the testing apparatus has cooled naturally, the condition of the specimens should be inspected, including cracking, melting, deformation, and other defects. Layering and other phenomena may occur, but areas blackened or faded by smoke should not be considered. Depending on the inspection needs, some coverings on the sample may be removed. The following should be done. Records.
a) If smoldering is present, after 24 hours of testing, inspect the areas of the specimen damaged by smoldering in both the vertical and horizontal directions;
b) The extent of flame propagation on the sample surface in both vertical and horizontal directions;
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 24 pages — is available in the English PDF.
Editions of GB/T 29416
| Edition | Title | Revision | Status |
|---|---|---|---|
| GB/T 29416-2026 | Test method for the fire performance of external wall insulation systems applied to building facades | current edition | Current |
| GB/T 29416-2012 | Test method for the fire performance of external wall insulation systems applied to building facades | previous edition | In force until 1 October 2026 |
This page sells the current edition, GB/T 29416-2026. Earlier editions are listed for reference only.
How to Buy GB/T 29416-2026
- 1Add to cart. Click the "Buy GB/T 29416-2026" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 47310-2026 — Determination of total silicon, aluminium, iron, potassium, sodium, calcium, magnesium, manganese, phosphorus, titanium and sulfur in soil - Monochromatic excitation energy dispersive X-ray fluorescence spectrometry
GB/T 47321-2026 — Specification for the warning data exchange of the national emergency early warning dissemination system
GB/T 47293-2026 — Determination of available mercury in soil
Secure payment via Stripe
Payments accepted
GB/T 29416-2026
$305.00