GB/T 20702-2026 is the Chinese national standard covering measuring what concentration of a gaseous agent puts a fire out - the cup burner test that gives the extinguishing concentration from which every system design concentration is derived. It replaces GB/T 20702-2006 and has been in force since 1 October 2026, with the hanging gas extinguisher standard GB 47485-2026. It was issued on 31 March 2026 and takes effect on 1 October 2026, replacing GB/T 20702-2006. The document is under the responsibility of the National Fire and Rescue Administration. This page is published from the official record of the 2026 edition; the clause text of a standard this recent is not yet in circulation, and the figures, limits and tables it contains are those of the document itself, delivered in full with the English translation.

Document preview — GB/T 20702-2026

National Standard of the People's Republic of China

ICS
13.220.10
Classification
C 83
Replacing
GB/T 20702-2006

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • 1 Scope
  • 4 Test method for extinguishing concentration of gaseous fire extinguishing agents
  • 4.2 Test Apparatus
  • 4.4 Test Procedure
  • 4.4.3 Calculation Method for Extinguishing Agent Concentration
  • 5 Test method for inerting concentration of gaseous fire extinguishing agents

Foreword

This document complies with the provisions of GB/T 1.1-2020 "Standardization Work Guidelines Part

1.Structure and Drafting Rules of Standardization Documents". Drafting. This document replaces GB/T 20702-2006 "Test Methods for Extinguishing Performance of Gaseous Fire Extinguishing Agents". Compared with GB/T 20702-2006, except for... Aside from structural adjustments and editorial changes, the main technical changes are as follows:

a) A test apparatus for the delivery system suitable for testing the extinguishing concentration of high-boiling-point gaseous extinguishing agents has been added (see 4.2.3);

b) A list of recommended typical fuels has been added (see 4.3);

c) The air flow rate in the method for determining the extinguishing concentration of gaseous fire extinguishing agents using flammable liquids as fuel was modified [see 4.4.1c],.2006. Version A.4.4];

d) The test procedure for determining the extinguishing concentration of a gaseous extinguishing agent using flammable liquid as fuel, involving different airflow rates, has been removed (see [link to documentation]). (A.4.10~A.4.19,.2006 edition)

e) The test procedure involving heating the fuel in the method for determining the extinguishing concentration of a gaseous extinguishing agent using flammable liquid as fuel has been removed. (See A.4.22~A.4.23 in the.2006 edition);

f) The test steps for different flame heights in the method for determining the extinguishing concentration of gaseous fire extinguishing agents using combustible gas as fuel have been removed (see [link]). (A.5.11,.2006 edition)

g) Added requirements for relevant test conditions in the "Test Report" of the test method for the extinguishing concentration of gaseous fire extinguishing agents [see 4.5c)];

h) A test report for the inerting concentration test method of gaseous fire extinguishing agents has been added (see 5.4). Please note that some content in this document may involve patents. The issuing organization of this document assumes no responsibility for identifying patents. This document was proposed by the National Fire and Rescue Administration. This document is under the jurisdiction of the National Fire Protection Standardization Technical Committee (SAC/TC113). This document was drafted by: Tianjin Fire Research Institute of the Ministry of Emergency Management, Civil Aviation University of China, Shanghai Huiyou Precision Chemicals Co., Ltd., and Zhejiang... Hunan Provincial Chemical Research Institute Co., Ltd., Zhejiang Noah Fluorochemical Co., Ltd., China University of Mining and Technology (Beijing), State Grid Hunan Electric Power Co., Ltd. Disaster Reduction Center. The main drafters of this document are. Zhao Jing, Chen Peiyao, Wang Shuai, Zhuang Shuang, Zhang Beichen, Zhang Xiao, Liu Mingli, Ni Hang, Tao Yang, Zhou Biao, and Chen Baohui. The release history of this document and the document it replaces is as follows:

---This document was first published as GB/T 20702-2006;

---This is the first revision.

Gaseous fire extinguishing agents are widely used for fire protection in electrical equipment, data centers, and cultural relic archives. Extinguishing concentration and inerting concentration are also important considerations. It is a key indicator for evaluating the fire extinguishing performance of gaseous fire extinguishing agents and provides a design basis for the engineering application of gaseous fire extinguishing agents. This document provides a test method for determining the fire extinguishing performance of gaseous fire extinguishing agents under laboratory conditions. This method has applications in scientific research and engineering. Widely used in the formulation of construction standards, the measured extinguishing concentration or inerting concentration reflects the extinguishing effect of the gaseous extinguishing agent under test conditions. The minimum critical value for inerting effect, and the test results, provide important data support for the selection and engineering design of gaseous fire extinguishing agents. In practical engineering applications... In practice, multiple factors such as the configuration of the fire extinguishing system, environmental conditions, and safety level must be considered to ensure continuous and effective protection. Test methods for the extinguishing performance of gaseous fire extinguishing agents Warning

---The testing process may involve chemical exposure, high pressure risk, explosion risk, and fire risk. Personnel should take appropriate safety precautions. Protective measures.

1 Scope

GB/T 20702-2026 is the Chinese national standard covering measuring what concentration of a gaseous agent puts a fire out - the cup burner test that gives the extinguishing concentration from which every system design concentration is derived. It replaces GB/T 20702-2006 and has been in force since 1 October 2026, with the hanging gas extinguisher standard GB 47485-2026. It was issued on 31 March 2026 and takes effect on 1 October 2026, replacing GB/T 20702-2006. The document is under the responsibility of the National Fire and Rescue Administration. This page is published from the official record of the 2026 edition; the clause text of a standard this recent is not yet in circulation, and the figures, limits and tables it contains are those of the document itself, delivered in full with the English translation.

This document describes the experimental principle, apparatus, materials, procedures, and test report for determining the extinguishing concentration of gaseous fire extinguishing agents using the cup combustion method. The experimental principle, apparatus, materials, procedures, and test report for determining the inerting concentration of gaseous fire extinguishing agents using the inerting ball method. This document applies to the determination of extinguishing concentration and inerting concentration of gaseous fire extinguishing agents. It can be used as a reference for the determination of the extinguishing performance of other gaseous media.

4 Test method for extinguishing concentration of gaseous fire extinguishing agents

4.1 Experimental Principle At the center of the coaxial airflow, fuel combustion in the cylindrical storage tank (cup) forms a diffused flame, which is gradually added into the air. For gaseous fire extinguishing agents, record the concentration at which the fire was extinguished when it spread.

4.2 Test Apparatus

4.2.1 General Requirements The extinguishing agent concentration testing device is a cup burner. The cup burner should conform to the structure shown in Figure 1, and the combustion cup should conform to the structure shown in Figure 2. Structure. Unless otherwise specified, the dimensional error of the indicated dimensions shall not exceed ±5%.

4.2.2 Components The test setup includes the following.

---Combustion cup. Should be cylindrical, open at the top, made of glass, quartz, or stainless steel, with an outer diameter of (30±1) mm and a wall thickness of 1 mm. 2mm; top edge chamfered at 45°, fuel temperature measuring device installed 2mm~5mm below the top; gaseous fuel fire extinguishing The top of the device should be designed to ensure uniform gas flow (e.g., by filling it with refractory material).

---Chimney. Should be a vertical circular pipe, made of glass or quartz, with an inner diameter of (85±2) mm, a wall thickness of 2 mm~5 mm, and a height of... (535±5)mm.

---Gas collection tube. Air and extinguishing agent are collected in the gas collection tube to form a single mixed flow that is then sent into the diffuser.

---Diffuser. Installed at the bottom of the chimney, it is used to introduce a mixed airflow of air and extinguishing agent, and to ensure that the mixed airflow passes evenly through the chimney. The temperature of the air and extinguishing agent mixture inside the diffuser should be (25±10)°C, measured using a calibrated temperature sensor.

---Fuel supply. Liquid fuel shall be delivered to the cup at a constant and adjustable level; gaseous fuel shall be delivered to the cup at a constant flow rate.

---Air supply. A device for supplying air to the air collection pipe. The flow rate is adjustable, and the air flow rate should be measured using a calibrated device.

---Extinguishing agent supply. A device for delivering extinguishing agent to the gas collection pipe. The flow rate is adjustable, and the extinguishing agent flow rate should be measured using a calibrated device.

---Delivery system. A representative and measurable extinguishing agent sample should be delivered to the cup burner in gaseous form.

4.2.3 Delivery system suitable for testing the extinguishing concentration of high-boiling-point gas extinguishing agents Before introducing high-boiling-point gaseous extinguishing agents, the equipment should be adjusted, and a delivery system suitable for high-boiling-point gaseous extinguishing agents should be added to ensure the extinguishing effect. The extinguishing agent is fully vaporized. A schematic diagram of the extinguishing agent delivery system is shown in Figure

3.The design of the delivery system should ensure that the extinguishing agent can vaporize and remain stable. The extinguishing agent should be delivered to the cup burner in a controlled manner, and the temperature should be strictly controlled to avoid high-temperature decomposition of the extinguishing agent or the generation of impurities, which would affect the test results. The components of the conveying system are as follows:

---High-pressure syringe pump. Composed of a motor, transmission system, syringe, and control system, it works in conjunction with a check valve to seal the liquid inlet, forming a closed-loop system. The system ensures that the liquid extinguishing agent is output at a constant flow rate under high pressure.

---Vaporization Furnace. Utilizes a circulating tank heating method to vaporize liquid extinguishing agents. The vaporization furnace should be equipped with precise temperature control to ensure... The extinguishing agent is completely vaporized and the temperature is stable.

4.4 Test Procedure

4.4.1 Using flammable liquids as fuel The test procedure for determining the extinguishing concentration of a gaseous fire extinguishing agent using a flammable liquid as fuel is as follows:

a) Transfer the flammable liquid from the fuel tank into the combustion cup.

b) Start the heating device to bring the fuel temperature in the cup to (25±3)°C or above the open cup flash point (5±3)°C, whichever is higher. Flash point determination shall comply with the provisions of GB/T 3536.Adjust the liquid level in the combustion cup to ensure that the fuel level is above the temperature measuring device. The distance from the top of the cup is 5mm to 10mm.

c) Adjust the airflow to 40L/min.

d) Ignite the fuel and pre-ignite for 60s~120s, while adjusting the fuel level to be no more than 1mm from the top of the cup.

e) Introduce the extinguishing agent, gradually increasing the flow rate until the flames are extinguished. Record the flow rates of the extinguishing agent and air, or the air/extinguishing agent flow rate in the chimney, during extinguishing. Oxygen concentration in the extinguishing agent mixture. After adjusting the extinguishing agent flow rate, it should stabilize for at least 10 seconds to allow the new proportion of extinguishing agent in the gas collection pipe to reach the target concentration. The extinguishing agent and air should reach the combustion cup. The increase in extinguishing agent flow rate should not exceed 3% of the initial flow rate. Approaching the extinguishing point... At this time, the increase in extinguishing agent flow rate should be as small as possible. The final flow rate adjustment should be the smallest unit of measurement on the measuring device.

f) Calculate the extinguishing concentration of the extinguishing agent in accordance with the provisions of 4.4.3.

g) Remove fuel and all residues adhering to the combustion cup, as well as soot from the combustion, from the combustion cup in preparation for subsequent tests.

h) Repeat steps 4.4.1a) to 4.4.1g) for a total of 5 tests.

i) The average value of the 5 tests is taken as the extinguishing concentration of the extinguishing agent.

4.4.2 Using combustible gas as fuel Combustion cups used for gaseous fuels should achieve a uniform airflow at the top of the cup. For example, combustion cups for liquid fuels are filled with refractory material. The test procedure for determining the extinguishing concentration of a gaseous fire extinguishing agent using combustible gas as fuel is as follows:

a) The gaseous fuel shall be supplied through a calibrated regulating device that allows for adjustment and measurement of the gas flow rate.

b) Adjust the air flow rate to 40 L/min.

c) Pass the gaseous fuel into the cup and ignite it. Adjust the fuel flow rate so that the flame height reaches about 80 mm and pre-ignite for 60 seconds.

4.4.3 Calculation Method for Extinguishing Agent Concentration

4.4.3.1 Concentration Calculation Method The concentration of extinguishing agent vapor in an air/extinguishing agent mixture that just extinguishes a flame is determined using a method specific to the concentration range of the mixture being tested. A calibrated gas analysis device, which can be either a type with continuous sampling capability (such as an online gas analyzer) or a device that has been used for [specific purposes]. For analyzing discrete samples (such as gas chromatographs), continuous measurement techniques are preferable. A continuous oxygen concentration analyzer can also be used to measure the oxygen concentration in the air/extinguishing agent mixture in the chimney. Record the fuel flame. The oxygen concentration at the time of extinguishing is used to calculate the extinguishing agent concentration using formula (1).

4.4.3.2 Flow Calculation Method The concentration of extinguishing agent in the extinguishing agent-air mixture can also be calculated by measuring the flow rates of the extinguishing agent and air. If using mass... The mass flow rate measured by the flow meter can be converted into volumetric flow rate using formula (2).

4.5 Test Report The results report should include the following.

a) Equipment diagram, including dimensions and description of materials used.

b) The source and composition of extinguishing agents, fuels and air.

c) Test conditions, including the following. 1) Atmospheric pressure; 2) Laboratory temperature or air temperature entering the bottom of the chimney (if different); 3) Humidity of the air supplied to the chimney.

d) The fuel temperature at the start of each test, the fuel temperature at the time of extinguishing, and the air/extinguishing agent mixture temperature at the time of extinguishing. temperature.

4.4.3.2 is used, record the extinguishing agent and air flow rate during extinguishing; if method

4.4.3.1 is used, record the extinguishing... The concentration of the extinguishing agent and the oxygen concentration at that time.

f) Test the extinguishing concentration of high-boiling-point gas extinguishing agents, and provide a detailed process of vaporization of the extinguishing agent sample.

g) Methods for determining extinguishing concentration.

h) The concentration of the extinguishing agent during each fire extinguishing test, and the type of flammable liquid or flammable gas.

i) Measurement error analysis.

5 Test method for inerting concentration of gaseous fire extinguishing agents

5.1 Experimental Principle Under standard atmospheric pressure, ignite a fuel/extinguishing agent/air mixture, measure the pressure rise, and record the amount of extinguishing agent required to suppress combustion. Minimum volume fraction.

5.2 Test Apparatus The gas extinguishing agent inerting concentration test device consists of the following parts.

---The test container is spherical with a volume of (7.9±0.25)L, equipped with an inlet and outlet, a thermocouple, and a pressure sensor, as shown in Figure 4.

---The igniter consists of four graphite rods ("H" pencil leads), attached to one end by two wires, with a distance of approximately 3mm between the wires. The constant resistance is 1Omega.

--- Capacitors, two 525µF, 450V capacitors connected in series, connected to the ignition wire with a wire.

---Internal hybrid fan capable of withstanding the temperature and pressure during an explosion.

5.3 Test Procedure The test procedure for the inerting concentration of gaseous fire extinguishing agents is as follows:

a) The ball and components should be at (22±3)°C, and the actual temperature should be recorded.

b) Connect the pressure sensor to a suitable recorder to measure the pressure rise within the test vessel. The accuracy of the pressure sensor is [insert accuracy here]. 70Pa.

c) Activate the vacuum device to purge the air from the test container.

d) Introduce the extinguishing agent and use the partial pressure method to achieve the required concentration. If it is a liquid, allow sufficient time for it to evaporate. The sampling method shall comply with the provisions of GB/T 3723.

e) Under environmental conditions of relative humidity (50±5)%, the mixing ratio of fuel vapor and air is adjusted by the partial pressure method to achieve the target group When ...

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 17 pages — is available in the English PDF.

Referenced standards

Editions of GB/T 20702

EditionTitleRevisionStatus
GB/T 20702-2026Test method for the extinguishing performance of gaseous extinguishing agentscurrent editionCurrent
GB/T 20702-2006Test method for the extinguishing performance of gaseous extinguishing agentsprevious editionIn force until 1 October 2026

This page sells the current edition, GB/T 20702-2026. Earlier editions are listed for reference only.

How to Buy GB/T 20702-2026

  1. 1Add to cart. Click the "Buy GB/T 20702-2026" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
17 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 20702-2026

$260.00

$220.00for partners