GB 28527-2012Residual current devices with or without overcurrent protection for socket-outlets for household and similar uses (English PDF)
家用和类似用途的带或不带过电流保护的插座式剩余电流电器(SRCD)
This is a limited preview
Buy now to download the full PDF (99 pages)
Need quotation for your management?
Get a formal quotation for GB 28527-2012 in 30 minutes.
Issued by
Standardization Administration of China
Level / Type
National · Mandatory
Issue date
June 29, 2012
Implementation date
May 1, 2013
Scope
GB 28527-2012 is the English-translated version of 家用和类似用途的带或不带过电流保护的插座式剩余电流电器(SRCD).
GB 28527-2012 — This standard specifies the residual current collector comprises a function of detecting residual current, the residual current value and the residual operating current value is compared Function, and a function when the residual current exceeds this value, the disconnection of the protected circuit.
Maximum rated residual current is 30mA. Does not exceed the rated voltage of 250V AC SRCD, which is the maximum rated current. 16A; not exceed the rated voltage of AC 130V the SRCD, its maximum rated current is 20A.
Remaining power for use with the present standard applies to the special assembly or the use of household and similar with or without ground contacts pole sockets for electrical flow (SRCD. residual current electrical socket).
SRCD meet this standard by the phase - neutral power, phase - phase supply or Phase - the intermediate power supply conductor to ground. SRCD only provides additional protection to the outlet end thereof.
SRCD intended for use in the front stage it has to ensure fault protection (indirect access Contact protection) circuits. NOTE 1.
For example, fault protection (indirect contact) provided by the following means. -TT system, using the former stage of GB 16916.1 and GB 16917.1 RCCB or RCBO compliance. -TN system, the first stage may be employed overcurrent protection device.
SRCD can not provide isolation, it can not be used in IT systems. Note 2. Isolation provides protection for the intended function or malfunction, or SRCD the IT system should be used and GB 16916.1 and GB 16917.1 GB 2099.1 as with the applicable standards.
Note 3. Technical requirements and test intended for use in IT systems SRCD under consideration. SRCD distribution board should not be used, they are not a complete circuit of the terminal to protect the distribution circuit or complete.
These products Subject GB prospective mounting the mounting box 17466.1; or in compliance with GB/T 19215.1 cable trunking and ducting systems; or in compliance with IEC 61534 Supply piping system; or near the outlet box and meet one of the above standard installation box.
These products are not intended for use in accord GB 7251 GB 17466.24 or family housing. RCD household and similar purposes not covered by this standard, including in GB 16916 or GB 16917.
By a battery, or in addition to the power to other load circuits other than the power SRCD not included within the scope of this standard. This standard is also applicable to SRCD with overload or over-current protection.
This standard is also applicable to the assembly of a residual current wiring electrical components, the residual current collector is only used for a single wire assembly adjacent Fixing electrical equipment (example. hand dryer, water coolers, etc.) to provide protection.
Note 4. SRCD designed to be operated by non-professional and does not require maintenance. This standard applies to the technical requirements and environmental conditions of normal temperature.
Used under more severe environmental conditions you may need to fill SRCD Charge technical requirements. SRCD socket portion meets the requirements of GB 2099.1-2008.
Found what you need?
Document preview — GB 28527-2012
National Standard of the People's Republic of China
- ICS
- 29.120.50
- Classification
- K 31
Issued by: Standardization Administration of China
Contents
- Preface
- Introduction
- 1 Scope
- 2 Normative References
- 2 3 Definitions
- 3.1 The definition of the earth current flowing from the charging member
- 3.2 Definitions excitation residual current device
- 3.3 Residual current collector define actions and functions
- 3.4 Definitions related to the magnitude and the excitation range
- For definitions of 3.5 and influence the magnitude and scope
- 3.6 Operating Conditions
- 3.7 Test
- 3.8 Associated with the defined residual current protector
- Category 4
- 4.1 The operating conditions during power failure classification
- 4.2 Design based on classification
- 4.3 Classification 9 operating conditions when the DC component
- 4.4 The ground facilities classified
Foreword
All technical contents of this standard is mandatory.
This standard was drafted in accordance with rules GB/T 1.1-2009 given.
This Standard is a modified IEC 62640:2011 is electrically socket residual current "household and similar purposes with or without overcurrent protection Device "(in English).
This standard and IEC 62640:2011 The main differences are as follows.
--- applicability of the flat pin type socket. Considering the plug of the home system is a flat pin, 8.3.1 and increase of Home Single phase plug and socket type similar purposes, the basic parameters and dimensions of the content, an increase of 9.2 dedicated check the contents.
--- Note on the process. IEC 62640:2011 in all of the note, who did not tally with our country or our country do not apply to the situation in this standard are to be deleting and properly treated.
--- an increase of 4.10 based on content classification unprotected door.
--- SRCD for overcurrent protection, the overcurrent trip increase in Annex D test routine experiments.
--- "earth leakage current" to "fault current to ground." Since the fault current can cause a fire.
--- a note in Table 6 of "9.13.2" to "9.16." Because only in line with the impulse voltage test of 9.16, among the electric 8.3.2 the gap can be reduced.
--- 9.19.2 of "21h at the end of the last power-on period, the measurement terminals with thin thermocouple temperature, which temperature should not exceed 50K "to" 21h at the end of the last power-on period, with the temperature measuring terminals of fine wire thermocouples, the temperature should not exceed 60K ". This is consistent with the requirements in Table 8.
The standard proposed by China Electrical Equipment Industrial Association.
This low-voltage electrical standard by the National Standardization Technical Committee (SAC/TC189).
This standard is drafted. Shanghai Electric Apparatus Research Institute.
Participated in the drafting of this standard. Shanghai Electric Division Electrical Technology Co., Ltd. Zhejiang Chint electrical construction, through leading technology group, benefits the benefit (Group) Co., Ltd., Nanjing tripod Electric Co., Ltd. brand, Goodwin Electronics Co., Ltd. Yuyao City, Zhejiang Chint Electric Co. shares the company, Shi Naide Electric (China) Investment Co., Ltd., Shanghai electrical equipment testing by the Zhejiang People Electric Co., Ltd.
Introduction
GB 16916 and GB 16917 series of standards having one to four residual current electric poles suitable for installation in any part of the electrical device Device. The collector may be mounted at the end of the entire electrical device into the line, the front end or one or more fixed electrical circuit means, or to a power supply One or several outlets of the front end circuit. These appliances may be assembled with the receptacle in the same housing.
The RCD is possible to provide fault protection (indirect contact), additional protection (protection against direct contact) (if rated residual current is equal to or less than 30mA), and a fire hazard due to the fault current and the overcurrent protection is not provided due to the persistence of protection. Satisfies GB GB 16917 or 16916 series of standards to ensure isolation of the RCD, and similar household can withstand high the level of electromagnetic disturbances, and the electrical device can be used safely.
Although GB 16916 and GB 16917 series of standards applicable to the "combination in the socket of the RCD", but we know that due to the socket the particular use and mounting portion, the boundary fixed electrical installations, close to the front end of the electrical device taken through the electrical plug into the socket, these RCD requirements of different characteristics.
RCD socket usually installed by skilled or trained person can operate several times a day. Since it is considered the plug from the plug Block has been pulled provide effective isolation, it does not require isolation. Outlet end of the RCD is not permanently connected and long wire has Limit the number of electrical appliances to prove that it is reasonable to reduce the level of EMC. This standard includes the additional SRCD expected only for direct contact protection. Taking into account these unique characteristics, it is necessary to draw up a SRCD standards.
Household and similar uses or without overcurrent protection Residual current collector receptacle (SRCD)
1 Scope
This standard specifies the residual current collector comprises a function of detecting residual current, the residual current value and the residual operating current value is compared Function, and a function when the residual current exceeds this value, the disconnection of the protected circuit.
Maximum rated residual current is 30mA.
Does not exceed the rated voltage of 250V AC SRCD, which is the maximum rated current. 16A; not exceed the rated voltage of AC 130V the SRCD, its maximum rated current is 20A.
Remaining power for use with the present standard applies to the special assembly or the use of household and similar with or without ground contacts pole sockets for electrical flow (SRCD. residual current electrical socket). SRCD meet this standard by the phase - neutral power, phase - phase supply or Phase - the intermediate power supply conductor to ground.
SRCD only provides additional protection to the outlet end thereof. SRCD intended for use in the front stage it has to ensure fault protection (indirect access Contact protection) circuits.
NOTE 1. For example, fault protection (indirect contact) provided by the following means.
-TT system, using the former stage of GB 16916.1 and GB 16917.1 RCCB or RCBO compliance.
-TN system, the first stage may be employed overcurrent protection device.
SRCD can not provide isolation, it can not be used in IT systems.
Note 2. Isolation provides protection for the intended function or malfunction, or SRCD the IT system should be used and GB 16916.1 and GB 16917.1 GB 2099.1 as with the applicable standards.
Note 3. Technical requirements and test intended for use in IT systems SRCD under consideration.
SRCD distribution board should not be used, they are not a complete circuit of the terminal to protect the distribution circuit or complete. These products Subject GB prospective mounting the mounting box 17466.1; or in compliance with GB/T 19215.1 cable trunking and ducting systems; or in compliance with IEC 61534 Supply piping system; or near the outlet box and meet one of the above standard installation box. These products are not intended for use in accord GB 7251 GB 17466.24 or family housing.
RCD household and similar purposes not covered by this standard, including in GB 16916 or GB 16917. By a battery, or in addition to the power to other load circuits other than the power SRCD not included within the scope of this standard.
This standard is also applicable to SRCD with overload or over-current protection.
This standard is also applicable to the assembly of a residual current wiring electrical components, the residual current collector is only used for a single wire assembly adjacent Fixing electrical equipment (example. hand dryer, water coolers, etc.) to provide protection.
Note 4. SRCD designed to be operated by non-professional and does not require maintenance.
This standard applies to the technical requirements and environmental conditions of normal temperature. Used under more severe environmental conditions you may need to fill SRCD Charge technical requirements.
SRCD socket portion meets the requirements of GB 2099.1-2008.
2 Normative references
The following documents for the application of this document is essential. For dated references, only applies to the version dated paper Pieces. For undated references, the latest edition (including any amendments) applies to this document.
GB 2099.1 household and similar purposes plug and socket - Part 1. General requirements (GB 2099.1-2008, IEC 60884-1.
2006, E3.1, MOD)
GB/T 2423.4 electric and electronic products Environmental testing - Part 2. Test Db Test Method. Damp heat, cyclic (12h 12h cycle Ring) (GB/T 2423.4-2008, IEC 60068-2-30:2005, IDT) GB/T 2424.2 electric and electronic products environmental testing damp heat tests (GB/T 2424.2-2005, IEC 60068-3-4.
2001, IDT)
GB/T 2900 (all parts) Electrotechnical term (GB/T 2900, IEC 60050 series, EQV) GB 4208 shell protection (IP code) (GB 4208-2008, IEC 60529:2001, IDT) GB/T 5169.10 fire hazard testing for electric and electronic products - Part 10. hot wire/hot wire based test methods Glow-wire apparatus Test apparatus and general methods (GB/T 5169.10-2006, IEC 60695-2-10:2000, IDT) GB/T 5169.11 fire hazard testing for electric and electronic products - Part 11. hot wire/hot wire based test methods finished burning Hot wire flammability test method (GB/T 5169.11-2006, IEC 60695-2-11:2000, IDT) GB 8898 Audio, video and similar electronic apparatus - Safety requirements (IEC 60065:2005, EQV) GB/T 14472 electronic equipment part 14 is fixed capacitors. electromagnetic interference suppression specification Fixed capacitors (GB/T 14472-1998, IEC 384-14:1993, IDT) GB/T 16842 and the housing of the protective equipment used in testing with test (GB/T 16842-2008, IEC 61032:1997, IDT) Residual current operated circuit breaker (the RCCB) without a GB 16916.1 household and similar uses overcurrent protection Part 1. a General rule (GB 16916.1-2003, IEC 61008-1:1996, MOD) GB 16917.1 with household and similar uses overcurrent protection residual current operated circuit breaker (the RCBO) - Part 1. General Rules (GB 16917.1-2003, IEC 61009-1:1996, MOD) GB/T 16935.3 insulation device with the low pressure system Part 3. the use of a coating, potting or molding for protection against pollution (GB/T 16935.3-2005, IEC 60664-3:2003, IDT) GB 17466.1 household and similar fixed electrical accessory mounting electrical boxes and the housing part 1. general requirements (GB 17466.1-2008, IEC 60670-1:2002, MOD) Part 24 of the housing and the electrical accessory mounting box GB 17466.24 household and similar fixed electrical devices. protective housings Particular requirements of the housing means and similar power consumption apparatus (GB 17466.24-2008, IEC 60670-24:2005, MOD) GB 18499 household and residual current operated protective devices similar use (RCD) Electromagnetic compatibility (GB 18499-2008, IEC 61543:1995, IDT) GB/T 19215.1 electrical installations cable trunking and ducting systems - Part 1. General requirements (GB/T 19215.1-2003, IEC 61084-1:1991 A1.1993, MOD) EMC requirements GB 4343.1-2009 household appliances, electric tools and similar apparatus Part 1. Emission (IEC/CISPR14-1.2005, IDT) IEC 61008-1:2008 the residual current operated circuit breaker without overcurrent protection for household and similar uses (the RCCB) Part 1 Points. General rules (Residualcurrentoperatedcircuit-breakerswithoutintegralovercurrentprotectionfor householdandsimilaruses (RCCBs) -Part 1. Generalrules) IEC 61009-1:2008 for household and similar uses overcurrent protection residual current operated circuit breaker (the RCBO) Part 1 Points. General rules (Residualcurrentoperatedcircuit-breakerswithintegralovercurrentprotectionfor householdandsimilaruses (RCBOs) -Part 1. Generalrules) IEC 61534-1:2003 Part 1 power supply piping systems. general requirements (Powertracksystems-Part 1. General requirements)
3 Terms and Definitions
GB/T 2900 and the definition of terms and definitions The following terms and definitions apply to this document.
3.1 the definition of the earth current flowing from the charging member 3.1.1.
Ground fault current earthfaultcurrent Since the insulating earth fault current flowing.
3.1.2.
Earth leakage current no insulation fault, current flows from the earth of the electrical device charging member.
3.1.3
Pulsating direct current pulsatingdirentcurrent Rated in each frequency cycle, a period of time represented by an angle of at least 150 ° of the current interval does not exceed a value of 0 or DC the pulsation waveform current 0.006A.
3.1.4
Current delay angle by controlling the phase, so that the starting time of the current conducting time lag represented by an angle.
3.1.5
Smooth direct current no DC current ripple.
Note. When the ripple factor is less than 10%, no ripple current can be considered.
3.2 Residual current device as defined excitation
3.2.1.
Residual current Idelta Electric current flowing through the residual vector of the main circuit current and the instantaneous value (effective value).
3.2.2.
Residual current residualoperatingcurrent Ideltan the residual electrical current residual current value in operation under a predetermined condition.
3.2.3
The remaining non-operating current residualnon-operatingcurrent Ideltano when the current is below the current or residual current residual electrical current value is not in operation under a predetermined condition.
3.3 Residual current collector define actions and functions of 3.3.1.
Residual current electrical residualcurrentdevice RCD Having a residual current detector, current value and the remaining residual current value is compared and open when the residual current exceeds the value of the insured Protection switch electrical circuit function.
3.3.2
Detection
Sensing the presence of a residual current function.
3.3.3
Discrimination evaluation when the reference residual current detector exceeds a predetermined value, so that the residual current protective devices may function operation.
3.3.4
Interrupt interruption So that the residual current protective device main contacts from the closed position to the open position, thereby cutting off the overcurrent flowing thereof.
3.3.5
Electric switch switchingdevice or distributor devoted to turning on or off a current of several electrical circuits.
[IEC 60050-442:1998,442-01-46] 3.3.6 Residual current collector free trip trip-freemechanismofaresidualcurrentdevice After the closing operation, when the opening operation performed, even if the close command is still maintained, and which can return the movable contacts held in an open position.
NOTE. To ensure proper breaking the current may be turned on, the contacts may need to instantaneously reaches the closed position.
3.3.7
Without overcurrent protection SRCD SRCDwithoutintegralovercurrentprotection can not be used SRCD performed overload and/or short-circuit protection function.
3.3.8
Overcurrent protection SRCD SRCDwithintegralovercurrentprotection it can be used to performed SRCD overload and/or short-circuit protection function.
3.3.9
Residual current unit A residual current detection can be performed simultaneously, the current value and the value of residual current comparison function, and a set of operating therewith it means devices mounted circuit breaker tripping mechanism or a combination thereof.
3.3.10
RCD breaking time break-timeofaRCD Until all current momentary pole a...
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 99 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 2423.4Environmental testing for electric and electronic products - Part 2: Test method - Test Db: Damp heat, cyclic (12 h + 12 h cycle)
- GB/T 2423.4-2008Environmental testing for electric and electronic products - Part 2: Test method - Test Db: Damp heat, cyclic (12 h + 12 h cycle)
- GB/T 5169.10Fire hazard testing for electric and electronic products -- Part 10: Glowing/hot-wire based test methods -- Glow-wire apparatus and common test procedure
- GB/T 5169.10-2006Fire hazard testing for electric and electronic products -- Part 10: Glowing/hot-wire based test methods -- Glow-wire apparatus and common test procedure
- GB/T 5169.11Fire hazard testing for electric and electronic products -- Part 11: Glowing/hot-wire based test methods -- Glow-wire flammability test method for end-products (GWEPT)
- GB/T 5169.11-2006Fire hazard testing for electric and electronic products -- Part 11: Glowing/hot-wire based test methods -- Glow-wire flammability test method for end-products (GWEPT)
GB 2099.1 · GB 2099.1-2008 · IEC 60884 · IEC 60068 · GB/T 2424.2 · GB/T 2424.2-2005 · GB/T 2900 · IEC 60050 · GB 4208 · GB 4208-2008 · IEC 60529 · IEC 60695 · GB 8898 · IEC 60065 · GB/T 14472 · GB/T 14472-1998 · IEC 384 · IEC 61032 · IEC 61008 · IEC 61009 · IEC 60664 · GB 17466.1 · GB 17466.1-2008 · IEC 60670 · GB 18499 · GB 18499-2008 · IEC 61543 · GB/T 19215.1 · GB/T 19215.1-2003 · IEC 61084 · IEC/CISPR14 · IEC 61534
How to Download GB 28527-2012
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 16916.1-2014 — [GB/T 16916.1-2014] Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB) -- Part 1: General rules
GB 16917.1-2014 — Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) -- Part 1: General rules
GB 17466.24-2008 — Boxes and enclosures for electrical accessories for household and similar fixed electrical installations -- Part 24: Particular requirements for enclosures for housing protective devices and other power dissipating electrical equipment
Secure payment via Stripe
Payments accepted
GB 28527-2012
$1,175.00